Acrel ADL200 Digital Multi Meter Electric Power Meter Din Rail Smart Meter Instruction Manual

October 27, 2023
Acrel

ADL200 Digital Multi Meter Electric Power Meter Din Rail Smart Meter
Instruction Manual
Installation and operation instruction V1.3

Declaration

The copyright is the property of Acrel. Any information in any paragraph or section cannot be extracted, copied or otherwise reproduced or propagated. Otherwise offenders
shall take all consequences.
All rights are reserved.
Acrel reserves the right to modify the product specifications herein without notification. Please consult the local agent about the latest specifications before placing a purchase order.

Overview

ADL200 single phase electric meter is designed for single phase active energy measurement on low voltage system, in the same time it can measure the electrical parameters  like voltage, current, power and so on. There is also RS485 can be chosen. This electricity meter has advantages of smaller volume, high precision, good EMC, easily installing  etc, All meters meet the related technical requirements of electricity meter in the IEC62053-21、IEC62053-22 standards.

Function

Function Function description Function provide
Measurement of kWh Single-phase active kWh (positive and negative),3 months
historical energy data frozen storage
Measurement of electrical parameters Voltage, Current, Active power, Reactive
power, Apparent power, Power factor and Frequency
LCD Display 8 bits section LCD display
Key programming 3 keys to set parameters like code, address, baud rate,
multi-tariff and communication protocol
Pulse output Active energy pulse output
Multi-tariff Adapt 4 time zones, 2 time interval lists, 14 time interval by
day and 4 tariff rates □F
Communication Communication interface: RS485, Communication protocol: MODBUS-
RTU

Technical parameter

3.1 Electric performance

Input voltage Reference voltage AC 220V
Voltage range AC 75~260V
Reference frequency 50Hz
Power consumption <10VA
Input current Basic current 10A
Maximum current 80A
Starting current 4‰Ib
Consumption <4VA
Measurement performance Accuracy of measuring 1 class
Range of measuring 000000.00~99999999kWh
Clock accuracy Error≤0.5s/d
Active pulse Pulse width 80±20ms
Pulse constant 1000imp/kWh
Communicati on Interface RS485(A+、B-)
Connection mode Shielded twisted pair conductors
Protocol MODBUS-RTU

3.2 Mechanical performance

Outline| Length ×
Width  ×
Height| 90mm×36mm×65mm
---|---|---
Strong current terminal Torque| <1.8Nm

3. 3 Work environment

Temperature range Work temperature -25℃~55℃
Storage Temperature -40℃~70℃
Relative humidity ≤95%(No condensation)
Altitude <2000m

Outline (unit: mm)

Acrel ADL200 Digital Multi Meter Electric Power Meter Din Rail Smart
Meter

Wiring and installing

Acrel ADL200 Digital Multi Meter Electric Power
Meter Din Rail Smart Meter - fig

Diagnosis, analysis and elimination of common faults

6.1 Auxiliary power failure
Failure performance: the meter flashes and does not light up after being powered on.
Troubleshooting:

  1. Check whether the wiring of the auxiliary power supply is consistent with the wiring diagram of the instrument, and whether the wiring is loose or falling  off;
  2. Use a multimeter to measure whether the input voltage value of the auxiliary power supply is within the normal working voltage range of the instrument.

6.2 Signal input failure
Failure performance: After the meter is powered on, the display power or energy count is not accurate.
Troubleshooting: Switch the display interface of the meter to the power (active P, power factor λ) interface, check whether the power display is negative and whether the  power factor is between 0.9-0.95, and then check whether the input and output of the current signal line are reversed ( That is, the incoming line of the current must be  consistent with the incoming end of the instrument), And consistent with the wiring on the meter.
6.3 communication failure
Failure performance: After the meter is powered on, it cannot communicate with the host computer normally.
Troubleshooting:

  1. The voltage value between the communication output A and B of the measuring instrument should be between +(4.4-4.5)V;
  2. Check whether the communication wiring method is correctly wired according to the wiring diagram (that is, the communication terminal A/B of the instrument should  correspond to the communication serial port A/B);

Operation and display

7.1 Key description

Key icon Key name Key function
Key up View voltage and current in the view interface

Up and flashing shift in the programming interface
| Key down| View power in the view interface
Scroll down and modify flashing bits in the programming interface

| Key setting| View electrical energy in the viewing interface
Long press 3S to enter/exit the menu
Short press OK in the programming interface to save the settings

7.2 display description
Show total energy when connected. Change information while pressing down key. Display information as following:

| U、I、F、Time、MODBUS  Address、Baud、parity、Version、ALL-display;
---|---
| Total power active power total factor reactive powertotal apparent powertotal
| Total active energy, forward active total energy, reverse active total energy, total active spike energy, total active peak  energy, total active flat energy, total active valley energy, total reactive energy, forward reactive total energy, reverse total  reactive energy, total reactive spike energy, total reactive peak energy, total reactive flat energy, total reactive valley energy.

Note:

  1. Listed above are the names of all display interfaces of the ADL200 meter with double rate function. Three buttons can switch different types of display content, the  switching sequence is as described above;
  2. For the ADL200 meter without the double rate function, it does not display the date, time and various types of time-sharing energy (the energy in the four rate periods of sharp, peak, flat and valley).

Acrel ADL200 Digital Multi Meter Electric Power Meter Din Rail Smart Meter -
fig 1Acrel ADL200
Digital Multi Meter Electric Power Meter Din Rail Smart Meter - fig
2

Note:The above is just a part of the display interface. The display mode of other interfaces is similar to the above figure. You can judge the display meaning according to the information displayed on the interface.
7.3Programming display menu

Press at any main menu and get in interface, and then press show , and enter the code. If you enter a wrong code, it will show“0000”and enter the code again; and if you enter a right code, you can set the parameter. After setting the parameter, it will show and save the change by pressing and quit without save by pressing .

Acrel ADL200 DigitalAcrel ADL200 Digital Multi Meter Electric Power Meter
Din Rail Smart Meter - fig 3 Multi Meter Electric Power Meter Din Rail Smart
Meter - fig 3

7.4 Item can be set
Setting item description

Mum Secondly menu
Symbol Meaning
1 ADDR
2 Baud
3 Pari
4 LED
5 S-TY
calculation PQS,RMS
6 EF-E
7 DIR
8 CoDE

Communication description

8.1 Communication protocol
The meters adapt Modbus . Please refer to the relevant standards for more information. The multi-tariff data mean nothing when multi-tariff function (F) is not applied.
8.2 MODBUS Address list

Address Variable Length Attributes Note
0000H Current combined total active energy 4 R unit:0.01kWh
0002H Current combined spike active energy 4 R
0004H Current combined peak active energy 4 R
0006H Current combined flat active energy 4 R
0008H Current combined valley active energy 4 R
000AH Code 2 R
000BH Voltage 2 R unit:0.1V
000CH Current 2 R unit:0.01A
000DH Active power 2 R unit:0.001kW
000EH Reactive power 2 R unit:0.001kvar
000FH Apparent power 2 R unit:0.001kVA
0010H power factor 2 R unit:0.001
0011H Frequency 2 R unit:0.01Hz
0012H Year, month 2 R/W
0013H Day, hour 2 R/W
0014H Minute, second 2 R/W
0015H Address 1 R/W 0~254
0015H Communication baud rate 1 R/W 00:1200

01:2400
02:4800
03:9600
04:19200
05:38400
0016H| light time| 2| R/W|
0017H~

0021H

| Reserve
0022H| Total active energy of last month| 4| R| unit:0.01kWh
0024H| Spike active energy of last month| 4| R
0026H| Peak active energy of last month| 4| R
0028H| Flat active energy of last month| 4| R
002AH| Valley active energy of last month| 4| R
002CH| Total active energy of last 2 month| 4| R|
---|---|---|---|---
002EH| Spike active energy of last 2 month| 4| R
0030H| Peak active energy of last 2 month| 4| R
0032H| Flat active energy of last 2 month| 4| R
0034H| Valley active energy of last 2 month| 4| R
0036H| Total active energy of last 3 month| 4| R
0038H| Spike active energy of last 3 month| 4| R
003AH| Peak active energy of last 3 month| 4| R
003CH| Flat active energy of last 3 month| 4| R
003EH| Valley active energy of last 3 month| 4| R
0040H~ 0044H| reserve
0045H| status| 2| R/W| Bit0:0-E-no, 1-EF-YES;Bit1:0-forward, 1-reverse; Bit3:0-PQS 1-RMS.
0046H~ 0047H| reserve
0048H| parity| 2| R| 0000:None
0002:Even
0049H| reserve
004AH
004BH
004CH~0067H| reserve
0068H| Current forward active total energy| 4| R| unit:0.01kWh
006AH| Current forward active spike energy| 4| R
006CH| Current forward active peak energy| 4| R
006EH| Current forward active flat energy| 4| R
0070H| Current forward active valley energy| 4| R
0072H| Current reversing active total energy| 4| R
0074H| Current reversing active spike energy| 4| R
0076H| Current reversing Active peak energy| 4| R
0078H| Current reversing active flat energy| 4| R
007AH| Current reversing Active valley energy| 4| R
007C~0

0AFH

| reserve
00B0H| Current total reactive energy| 4| R|
00B2H| Current spike reactive energy| 4| R
00B4H| Current peak reactive energy| 4| R
00B6H| Current flat reactive energy| 4| R
00B8H| Current valley reactive energy| 4| R| unit:0.01kVarh
---|---|---|---|---
00BAH| Current forward reactive total energy| 4| R
00BCH| Current forward reactive spike energy| 4| R
00BEH| Current forward reactive peak energy| 4| R
00C0H| Current forward reactive flat energy| 4| R
00C2H| Current forward reactive valley energy| 4| R
00C4H| Current reversing reactive total energy| 4| R
00C6H| Current reversing reactive spike energy| 4| R
00C8H| Current reversing reactive peak energy| 4| R
00CAH| Current reversing reactive flat energy| 4| R
00CCH| Current reversing reactive valley energy| 4| R
00CEH~ 52FFH| reserve
5300H| Voltage| 4| R| Float
5302H| Current| 4| R
5304H| Active power| 4| R
5306H| Reactive power| 4| R
5308H| Apparent power| 4| R
530AH| power factor| 4| R
530CH| Frequency| 4| R

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals