INSTALLATION INSTRUCTIONS FOR MODBUS COMMUNICATIONS CABLES REPLACEMENT KIT (22A26, 22A27, 24N57, 28B30)

CAUTION
Electrostatic discharge can affect electronic components.
Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.

IMPORTANT
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.

WARNING
ELECTRICAL SHOCK HAZARD
STOP! Before you continue,make sure that power to the VFD has been off for at least 10 minutes. The capacitor in the VFD holds high voltage power for up to 10 minutes after power has been disconnected.
WARNING
ELECTRICAL SHOCK HAZARD
Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electrical power supplies before opening access panel. Unit may have multiple power supplies.

Shipping and Packing List

Package 1 of 1 contains:
1 – MODBUS Cables Set
1 – Installation Instruction

Table 1. MODBUS Cables

Roof Top Units| Catalog and Part Numbers| Unit Voltage| Number of Cables
---|---|---|---
LGM 156-300| 22A26/622789-01| All| 4
LC/LH 156-300| 22A27/622789-02| All| 3
LGT/LDT 156-300| 24N57/622789-03| All| 2
LG/LD 156-300| 28B30/622789-04| All| 3

Installation

The MODBUS cables were designed for use with the following rooftop units:

  • LCM156-300
  • LGM156-300
  • LCX180-300
  • LCT156-300
  • LHT156-300
  • LHX180-240
  • LGT156-300
  • LDT156-300
  1. Disconnect all power to the roof top unit.

  2. Open compressor access panel.

  3. (LGM models only) Remove ignition controller enclosure cover.

  4. Remove old set of MODBUS cables from unit. Install and route new set of cables in the unit (see FIGURE 1, FIGURE 2, FIGURE 3, and FIGURE 4).
    NOTE: Replace damage wire ties (field-provided).

  5. Install ignition controller enclosure cover.

Table 2. LGM R410-A Catalog & Part Numbers

MODBUS Cable Catalog Number Pad Number Quantity
LGM 22A26 / 622789-01 106644-01 2
106597-01 1
106647-01 1

LG 22A26 Modbus Communication Harness Kit - Fig 1

Table 3. LC/LH Catalog & Part Numbers

MODBUS Cable Catalog Number Pad Number Quantity
LC/LH 22A27 / 622789-02 106646-01 1
106597-01 1

LG 22A26 Modbus Communication Harness Kit - Fig 2

Table 4. LGT/LDT Catalog & Part Numbers

MODBUS Cable Catalog Number Part Number Quantity
LGT / LDT 24N57 / 622789-03 106597-01 1
107175-01 1

LG 22A26 Modbus Communication Harness Kit - Fig 3

Table 5. LG/LD Catalog and Part Numbers

MODBUS Cable Catalog Number Part Number Quantity
LGT / LDT 28B30 / 622789-04 106597-01 1
107927-01 1
108009-01 1

LG 22A26 Modbus Communication Harness Kit - Fig 4