Product Information

Specifications:

  • Product Name: Universal Wall-Mount Controller TUUB Series
    Modbus Communication Module

  • Supported Baud Rates: 9600, 19200, 38400, 57600

  • Address Range: 1 to 246

Product Usage Instructions:

Modbus Communication:

The Modbus Communication Module allows for various operations
including:

  • Read Holding Registers (0x03)
  • Write Single Register (0x06)
  • Write Multiple Registers (0x10)

Baud Rate and Configuration:

The physical layer supports fixed baud rate selection or
automatic baud rate detection. Supported baud rates are 9600,
19200, 38400, and 57600. Parity control and stop bit configuration
can be adjusted through the Modbus Comport Config device menu.

Device Addressing:

The device’s unique address can be set from 1 to 246 through the
device menu or holding register index 0.

Holding Registers Table:

The holding registers table provides detailed information on
register indexes and their corresponding descriptions. It includes
various parameters such as communication port configuration, system
status, internal and external temperature sensor readings.

FAQ:

Q: How can I change the baud rate of the Modbus Communication

Module?

A: You can change the baud rate through the Modbus Auto Baud
Rate device menu item or holding register index 1.

Q: What is the range of supported baud rates?

A: The supported baud rates are 9600, 19200, 38400, and
57600.

“`

Universal Wall-Mount Controller
TUUB Series Modbus Communication Module User Guide
TUUB-Modbus Guide-240509

Universal Wall-Mount Controller
Modbus Communication Module User Guide
Introduction
The TUUB Modbus Communication Module User Guide provides information for using Neptronic® TUUB communication feature. The TUUB uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic TUUB Series devices. The TUUB Modbus Guide assumes that you are familiar with Modbus terminology. The following are the requirements for Modbus:
· Data Model. The TUUB Modbus server data model uses only the Holding Registers table. · Function Codes. The TUUB Modbus server supports a limited function codes subset comprising:
o Read Holding Registers (0x03) o Write Single Register (0x06) o Write Multiple Registers (0x10)
· Exception Responses. The TUUB Modbus server supports the following exception codes:
o Illegal data address o Illegal data value o Slave device busy
· Serial Line. The TUUB Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
o The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
o The supported baud rates are 9600, 19200, 38400, and 57600. o The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport
Config device menu item or holding register index 2. o In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with
any given baud rate, it will reinitialize itself to the next baud rate.
· Addressing. The TUUB device only answers at the following address:
o The device’s unique address (1 to 246) that can be set through the device menu or through holding register index 0.

www.neptronic.com

Page | 1

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Holding Registers Table
Table Glossary

Name

Description

W RO Unsigned Signed Bit String

Writable Register Read Only Register For range of values from 0 to 65,535, unless otherwise specified For range of values from -32,768 to 32,767, unless otherwise specified For registers with multiple values using bit mask (example, flags)

Holding Register Table

Name
ASCII MSB LSB MSW LSW

Description
For registers containing ASCII (8-bit) characters Most Significant Byte Least Significant Byte Most Significant Word Least Significant Word

Protocol Base
0

Register Index
40001

Description
Address – Neptronic ID and Modbus address of current device.

1

40002 MSTP Baud Rate.

2

40003 Communication port configuration.

3

40004 ProdName_87, characters 8-7 of 8 name characters.

4

40005 ProdName_65, characters 6-5 of 8 name characters.

5

40006 ProdName_43, characters 4-3 of 8 name characters.

6

40007 ProdName_21, characters 2-1 of 8 name characters.

7

40008 Controller Product_Version, actual firmware version.

8

40009 Controller parameters version.

9

40010 System Status 1.

www.neptronic.com

Data Type

Range

Unsigned Unsigned
Scale 100
Unsigned ASCII ASCII ASCII ASCII
Unsigned Unsigned
Bit String

MSB = 22, LSB = 1-246

0, 9600, 19200, 38400, or 57600, 0 = Auto Baud Rate Detection Value/100 (e.g. 38400 baud = 384)

1 = No parity, 2 Stop bits, 2 = Even parity, 1 stop bit, 3 = Odd parity, 1 stop bit

MSB = 84 (T), LSB = 85 (U)

MSB = 67 (C), LSB = 66 (B)

MSB = 50 (2), LSB = 52 (4)

MSB = 32 (Space), LSB = 0 (Null)

1 to 65535 (e.g. 115)

1 to 65535 (e.g. 102)

B0: System operation 0 = Normal, 1 = Fault
B2: System override by NSB or OCC 0 = Normal, 1 = OFF

B3: ChangeOverMode 0 = Cooling, 1 = Heating
B4: AL_FlowSwitch 0 = No alarm, 1 = Alarm activated
B6: AL_DirtyFilter 0 = No alarm, 1 = Alarm activated

Writable W W W W W W W RO RO
RO
Page | 2

Protocol Register

Base

Index

Description

10

40011 System Status 2.

11

40012 Internal temperature sensor reading.

12

40013 External temperature sensor reading.

13

40014 Changeover temperature sensor reading.

14

40015 Control temperature reading.

15

40016 Internal humidity sensor reading.

Not available on all models.

16

40017 External humidity sensor reading.

17

40018 Analog input 1 reading.

18

40019 Analog input 2 reading.

19

40020 Analog input 3 reading.

www.neptronic.com

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Bit String
Signed
Scale 100
Signed
Scale 100
Signed
Scale 100
Signed
Scale 100
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 100
Signed
Scale 100
Signed Scale 100

B0: Selector Switch Status 0 = Remote Mode, 1 = Local Mode
B2: CO2 Alarm 0 = Normal, 1 = Alarm

B10: AL_UI1 0 = Off, 1 = On
B11: AL_UI2 0 = Off, 1 = On

B7: AL_Override 0 = Off, 1 = On

B12: AL_UI3 0 = Off, 1 = On

B8: AL_WindowOpened 0 = Off, 1 = On

B13: AL_UI4 0 = Off, 1 = On

B9: AL_DoorOpened 0 = Off, 1 = On

B15: AL_OverHeat 0 = Off, 1 = On

Unit: ºC/ºF, Range: 0ºC to 50ºC or 32ºF to 122ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

Unit: % RH, Range: 10%RH to 90%RH, Value x 10 (e.g. 30%RH = 300)

Unit: % RH, Range: 10%RH to 90%RH, Value x 10 (e.g. 30%RH = 300)
Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0 (open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300) Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0 (open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300) Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0 (open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300)

Writable
RO
RO RO RO W RO RO RO RO RO
Page | 3

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Protocol Register

Base

Index

Description

20

40021 Analog input 4 reading.

21

40022 External CO2 sensor value in ppm.

22

40023 Internal CO2 sensor value in ppm.

23

40024 CO2 control value in ppm.

24

40025 Actual system occupancy state.

25

40026 Actual night setback state of the system.

26

40027 Actual heating demand of ramp 1.

27

40028 Actual heating demand of ramp 2.

28

40029 Actual cooling demand of ramp 1.

29

40030 Actual cooling demand of ramp 2.

30

40031 Actual changeover demand.

31

40032 Actual fan demand.

32

40033 Actual dehumidification demand.

33

40034 Actual humidification demand.

34

40035

Cooling Heating SwitchTimerCount – countdown until the system is able to swap the demand.

35

40036 Analog output 1 value.

36

40037 Analog output 2 value.

37

40038 Analog output 3 value.

www.neptronic.com

Data Type

Range

Signed Scale 100
Signed
Scale 1
Signed
Scale 1
Signed
Scale 1
Unsigned
Unsigned
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10

Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0 (open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300) Unit: ppm, 0 to Register (CO2 range), Value x 1 (e.g. 500 ppm = 500) Unit: ppm, 0 to Register (CO2 range), Value x 1 (e.g. 500 ppm = 500) Unit: ppm, 0 to Register (CO2 range), Value x 1 (e.g. 500 ppm = 500) 1 = NoOccupancy, 2 = Occupancy, 3 = Override 1 = Day, 2 = Night, 3 = Override Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: Seconds, Range: 0 to 7200 seconds, Value/1 (e.g. 100 secs = 100) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000)

Writable
RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO W W W
Page | 4

Protocol Register

Base

Index

Description

38

40039 Analog output 4 value.

39

40040 Binary output – 6 relays output status.

40

40041 System command.

41

40042 System mode status.

42

40043 Fan speed selection by user.

43

40044 Temperature setpoint in occupancy or day mode.

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Unsigned
Scale 10
Bit String
Bit String

Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000)

B0: Binary Output 1 0 = Open, 1 = Close
B1: Binary Output 2 0 = Open, 1 = Close
B2: Binary Output 3 0 = Open, 1 = Close [B2, B6, B9 – B15]: Reserved
B0: Cfg_ServiceDisplayAddress 0 = Normal, 1 = Display address on LCD

B3: Binary Output 4 0 = Open, 1 = Close
B4: Binary Output 5 0 = Open, 1 = Close
B5: Binary Output 6 0 = Open, 1 = Close
B6: Binary Output 7 0 = Open, 1 =Close B4: Cfg_HeatingRamp2Lock 0 = Off, 1 = On
B5: Cfg_ChangeOverRampLock 0 = Off, 1 = On

B1: Cfg_CoolingRampLock 0 = Off, 1 = On

B7: Cfg_HumidifyRampLock 0 = Off, 1 = On

Unsigned
Unsigned Signed
Scale 10

B3: Cfg_HeatingRamp1Lock 0 = Off, 1 = On

B8: Cfg_DehumidifyRampLock 0 = Off, 1 = On

1 = Auto [Register 40074 allows Auto Mode (1 or 5)]

2 = Heating [Register 40074 allows Heating Mode (1, 2 or 4)]

3 = EMH [Register 40041 Bits 2 and 1 = On and Enable (1) and

Register 40074 allows Heating Mode (1, 2 or 4)]

4 = Cooling [Register 40074 allows Cooling Mode (1, 3 or 4)]

5 = Fan [Register 40040 Bit 12 = Advanced (1) and Bit 13 = Enable]

6 = Off [Register 40044 Bit 6 = Enable (0)]

1 = Auto, 2 = Low, 3 = Med, 4 = High

Unit: ºC/ºF, Range: min to max setpoint, Value x 10 (e.g. 18°C = 180)

Writable W W
W
W W W

www.neptronic.com

Page | 5

Protocol Register

Base

Index

Description

44

40045 System option1.

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

B0: Cfg_TempUnitTstat 0 = ºC, 1 = ºF

B8: Cfg_KeyPadUpperLeftLock 0 = Off, 1 = On

B1: Cfg_TempUnitModbus 0 = ºC, 1 = ºF

B9: Cfg_KeyPadArrowsLock 0 = Off, 1 = On

Bit String

B2: Cfg_TempSetPointLock 0 = Off, 1 = On
B3: Cfg_HumSetPointLock 0 = Off, 1 = On
B4: Cfg_ProgramModeLock 0 = Off, 1 = On
B5: AL_FreezeProtection 0 = Off, 1 = On

B6: Cfg_UserSysOffModes 0 = Enable, 1 = Disable
B7: Cfg_KeyPadBottomLeftLock 0 = Off, 1 = On

B10: CfgUserFanAutoMode 0 = Enable, 1 = Disable
B11: Cfg
NightOrNoOccMode 0 = Setpoint, 1 = OFF
B12: Cfg_HumControlSource 0 = Intern Sensor, 1 = Extern Sensor Not available on all models.
B13: Time Mode 0 = 24h, 1 = 12h
B14: Cfg_WindowOpenedMode 0 = Setpoint, 1 = OFF
B15: Cfg_DoorOpenedMode 0 = Setpoint, 1 = OFF

Writable W

www.neptronic.com

Page | 6

Protocol Register

Base

Index

Description

45

40046 System option2.

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

B0: Baud Rate 0 = Auto, 1 = Manual
B1: Cfg_ActivateSchedule 0 = Off, 1 = On

Bit String

B2: Cfg_AnalogOutput1Direction 0 = Direct, 1 = Reverse
B3: Cfg_AnalogOutput2Direction 0 = Direct, 1 = Reverse
B4: Cfg_AnalogOutput3Direction 0 = Direct, 1 = Reverse
B5: Cfg_AnalogOutput4Direction 0 = Direct, 1 = Reverse

B6: Cfg_BinaryOutput1Direction 0 = Direct, 1 = Reverse
B7: Cfg_BinaryOutput2Direction 0 = Direct, 1 = Reverse

B8: Cfg_BinaryOutput3Direction 0 = Direct, 1 = Reverse
B9: Cfg_BinaryOutput4Direction 0 = Direct, 1 = Reverse
B10: Cfg_BinaryOutput5Direction 0 = Direct, 1 = Reverse
B11: Cfg_BinaryOutput6Direction 0 = Direct, 1 = Reverse
B12: CfgBinaryOutput7Direction 0 = Direct, 1 = Reverse
B12: Cfg
FanSpeedOption 0 = Standard, 1 = Advanced (OE1)
B13: Cfg_UserSysFanMode 0 = Disable, 1 = Enable
B14: Cfg_HideFanDisplay 0 = No, 1 = Yes

Writable W

www.neptronic.com

Page | 7

Protocol Register

Base

Index

Description

46

40047 System option3.

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Bit String

B0: DAYLIGHT_SAVINGS_STATUS 0 = Normal, 1 = Summer
B1: CfgEMHOutput 0 = Disable, 1 = Enable
B2: Cfg
HeatPumpMode 0 = Off (General Unit), 1 = On (HeatPump)
B3: Cfg_ReversingValve (O/B) 0 = O, 1 = B
B4: Cfg_EMHAutoMode 0 = No, 1 = Yes
B5: Cfg_Y2Output 0 = Disable, 1 = Enable
B6: Cfg_AnalogInput1MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt

B7: Cfg_AnalogInput2MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B8: Cfg_AnalogInput3MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B9: Cfg_AnalogInput4MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B10: Cfg_VFDTempInput 0 = Intern Sensor, 1 = Extern Sensor
B12: Cfg_FloatingBO1/BO2Direction 0 = Direct, 1 = Reverse
B13: Cfg_FloatingBO3/BO7Direction 0 = Direct, 1 = Reverse
B15: Cfg_DeltaTempLogic 0 = Off, 1 = On

Writable W

www.neptronic.com

Page | 8

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Protocol Register

Base

Index

Description

47

40048 System option4.

48

40049 Display information.

49

40050 Temperature control source.

50

40051 Network fallback timeout.

51

40052 Minimum occupancy/day setpoint.

52

40053 Maximum occupancy/day setpoint.

53

40054

Cooling temperature setpoint in unoccupied or night mode.

www.neptronic.com

Data Type

Range

Bit String
Unsigned Unsigned Unsigned
Scale 1
Signed
Scale 10
Signed
Scale 10
Signed
Scale 10

B0: Cfg_CO2ControlSource 0 = Internal Sensor, 1 = External Sensor
B1: Cfg_DisplayHumidity 0 = Display the temperature only, 1 = Display the temperature and humidity
B2: Cfg_DisplayCO2 0 = Don’t display CO2 control value, 1 = Display CO2 control value
B6: Cfg_VFDTempSetpointSource 0 = VFDTempSetpoint, 1 = TempSetpoint
B7: Cfg_AnalogOutput1OffVoltage 0 = Off, 1 = Minimum
B8: Cfg_AnalogOutput2OffVoltage 0 = Off, 1 = Minimum
B9: Cfg_AnalogOutput3OffVoltage 0 = Off, 1 = Minimum
B10: Cfg_AnalogOutput4OffVoltage 0 = Off, 1 = Minimum
B11: Cfg_CO2AutoSelfCalib 0 = Off, 1 = On 1 = Temperature and Demand, 2 = Setpoint and Demand, 3 = Temperature Only, 4 = Setpoint Only, 5 = Off 1 = Network Temp, 2 = Intern Temp, 3 = Extern Temp
Unit: Minutes, Range: 0 to 60, Value/1 (e.g. 30 mins = 30)
Unit: ºC/ºF, Range: 10ºC to max or 50ºF to max Value x 10 (e.g. 18°C = 180 or 60ºF = 600) Unit: ºC/ºF, Range: min to 40ºC or min to 104ºF Value x 10 (e.g. 18°C = 180 or 60ºF = 600) Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF Value x 10 (e.g.18°C = 180 or 60ºF = 600)

Writable
W
W W W W W W

Page | 9

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Protocol Register

Base

Index

Description

54

40055

Heating temperature setpoint in unoccupied or night mode.

55

40056 Heating proportional band for ramp 1.

56

40057 Heating proportional band for ramp 2.

57

40058 Cooling proportional band for ramp 1.

58

40059 Cooling proportional band for ramp 2.

59

40060 Changeover proportional band.

60

40061 Heating deadband for ramp 1.

61

40062 Heating deadband for ramp 2.

62

40063 Cooling deadband for ramp 1.

63

40064 Cooling deadband for ramp 2.

64

40065 Changeover deadband.

65

40066 Changeover setpoint.

66

40067 Fan time out in seconds.

67

40068 Fan damping factor in seconds.

68

40069 Heating integral time factor in seconds.

69

40070 Cooling integral time factor in seconds.

Data Type

Range

Signed
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 10
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1

Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF Value x 10 (e.g. 18°C = 180 or 60ºF = 600) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9Fº Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9Fº Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC = 10 or 2ºF = 20) Unit: ºC/ºF, 10ºC to 40ºC or 50ºF to 104ºF Value x 10 (e.g. 12ºC = 120 or 60ºF = 600)
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g.100 secs = 100)
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g.100 secs = 100)
Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g.100 secs = 100)
Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g.100 secs = 100)

Writable W W W W W W W W W W W W W W W W

www.neptronic.com

Page | 10

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Protocol Register

Base

Index

Description

70

40071

Cooling Heating SwitchTimer – Delay between cool and heat or vice versa.

71

40072 Cooling anticycle delay in minutes.

72

40073 NSB override delay in minutes.

73

40074 Unoccupied override delay in minutes.

74

40075 Occupancy minimum time in minutes.

75

40076 Unoccupied override delay count down in minutes.

76

40077 Fan mode (speed) in unoccupied or NSB mode.

77

40078 Fan mode (speed) when window is opened (alarm).

78

40079 Fan mode (speed) when door is opened (alarm).

79

40080 System control mode.

80

40081 Override System occupancy/NSB mode.

81

40082 Internal temperature sensor offset correction.

82

40083 Universal Input 1 signal.

Data Type

Range

Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned Unsigned Unsigned Unsigned Unsigned
Signed
Scale 100
Unsigned

Unit: Minutes, Range: 0 to 120 minutes, Value x 1 (e.g.100 mins = 100)

Unit: Minutes, Range: 0 to 15 minutes, Value x 1 (e.g.10 mins = 10)

Unit: Minutes, Range: 0 to 180 minutes, Value x 1 (e.g.100 mins = 100)

Unit: Minutes, Range: 0 to 180 minutes, Value x 1 (e.g.100 mins = 100)

Unit: Minutes, Range: 0 to 720 minutes, Value x 1 (e.g.100 mins = 100)

Unit: Minutes, Range: 0 to 180 minutes, Value x 1 (e.g.100 mins = 100)

1 = Low, 2 = Med, 3 = High, 4 = Auto

1 = Low, 2 = Med, 3 = High, 4 = Auto

1 = Low, 2 = Med, 3 = High, 4 = Auto

1 = Auto, 2 = Heat, 3 = Cool, 4 = Heat or Cool, 5 = Auto Lock

1 = Locally, 2 = OFF, 3 = Occupied, 4 = Unoccupied, 5 = Day, 6 = Night

Unit: depends on system unit, Range: ± 5ºC or +/-9ºF

Value x 100 (e.g.2ºC = 200 or 3ºF = 300)

1 = OFF 2 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor 0-10V 8 = CO2 sensor 0-10V 9 = Occupancy binary input 10 = NSB binary input 11 = Override binary input 12 = Window binary input 13 = Door binary input

14 = Dirty Filter binary input 15 = Flow switch binary input 16 = OverHeat binary input 17 = Selector switch binary input 18 = Fan Feedback 19 = Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern sensor TT-012 22 = Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 = Delta T Outlet 0-10V

Writable W W W W W W W W W W W W
W

www.neptronic.com

Page | 11

Protocol Register

Base

Index

Description

83

40084 Universal Input 2 signal.

84

40085 Universal Input 3 signal.

85

40086 Universal Input 4 signal.

86

40087 External temperature sensor offset correction.

87

40088 Changeover control mode.

www.neptronic.com

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Unsigned
Unsigned
Unsigned Signed
Scale 100
Unsigned

1 = OFF 2 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor 0-10V 8 = CO2 sensor 0-10V 9 = Occupancy binary input 10 = NSB binary input 11 = Override binary input 12 = Window binary input 13 = Door binary input
1 = OFF 1 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor 0-10V 8 = CO2 sensor 0-10V 9 = Occupancy digital input 10 = NSB digital input 11 = Override digital input 12 = Window digital input 13 = Door digital input
1 = OFF 2 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor 0-10V 8 = CO2 sensor 0-10V 9 = Occupancy digital input 10 = NSB digital input 11 = Override digital input 12 = Window digital input 13 = Door digital input

14 = Dirty Filter binary input 15 = Flow switch binary input 16 = OverHeat binary input 17 = Selector switch binary input 18 = Fan Feedback 19 = Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern sensor TT-012 22 = Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 = Delta T Outlet 0-10V
14 = Dirty Filter digital input 15 = Flow switch digital input 16 = OverHeat digital input 17 = Selector switch digital input 18 = Fan Feedback 19 = Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern Sensor TT-012 22 = Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 = Delta T Outlet 0-10V
14 = Dirty Filter digital input 15 = Flow switch digital input 16 = OverHeat digital input 17 = Selector switch digital input 18 = Fan Feedback 19 = Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern Sensor TT-012 22 = Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 = Delta T Outlet 0-10V

Unit: depends on system unit, Range: ± 5ºC or +/-9ºF

Value x 100 (e.g.2ºC = 200 or 3ºF = 300)

1 = Local, 2 = Cool, 3 = Heat

Writable W
W
W W W
Page | 12

Protocol Register

Base

Index

Description

88

40089 Minimum external temperature reading.

89

40090 Maximum external temperature reading.

90

40091 Maximum CO2 reading.

91

40092 Alarm level of CO2.

92

40093 Fan output signal.

93

40094 Ramp to control analog output 1.

94

40095 Minimum voltage for analog output 1 (volt).

95

40096 Maximum voltage for analog output 1 (volt).

96

40097 Ramp to control analog output 2.

97

40098 Minimum voltage for analog output 2 (volt).

98

40099 Maximum voltage for analog output 2 (volt).

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Signed
Scale 10
Signed
Scale 10
Signed
Scale 1
Signed
Scale 1
Unsigned
Unsigned
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Unsigned
Scale 10
Unsigned
Scale 10

Unit: depends on system unit, Range: -40ºC to 0ºC or -40ºF to 32ºF Value x 10 (e.g.-20°C = -200 or -20°F = 200) Unit: depends on system unit, Range: 50ºC to 100ºC or 122ºF to 212ºF Value x 10 (e.g.60°C = 600 or 140°F = 1400)
Unit: PPM, Range: 1000 to 5000, Value x 1 (e.g.2000 = 2000)

Unit: PPM, Range: 1000 to CO2 range, Value x 1 (e.g.1000 = 1000)

1 = 1 speed, 2 = 2 speeds, 3 = 3 speeds, 4 = Analog

1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan 7 = Heating 2

8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperture 13 = VFD/ECMTempLoopEnable 14 = VFD Pressure Loop

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan

9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperature 13 = VFD/ECMTempLoopEnable 14 = VFD Pressure Loop 15 = FAN (not available if AO1 is set to VFD/ECMTempLoopEnable or VFD Pressure Loop)

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

Writable W W W W W
W
W W
W
W W

www.neptronic.com

Page | 13

Protocol Register

Base

Index

Description

99

40100 Ramp to control analog output 3.

100

40101 Minimum voltage for analog output 3 (volt).

101

40102 Maximum voltage for analog output 3 (volt).

102

40103 Ramp to control analog output 4.

103

40104 Minimum voltage for analog output 4 (volt).

104

40105 Maximum voltage for analog output 4 (volt).

105

40106 Position of CH1 AO output while heating (%).

106

40107 Ramp to control binary output 1.

107

40108 Delay before activation of BO1 in minutes.

108

40109 Close position percentage for contact BO1.

109

40110 Open position percentage for contact BO1.

110

40111 Ramp to control binary output 2.

www.neptronic.com

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned

1= Off
2 = Change Over with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan

7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperature

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

1 = Off 2 = Change Over with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan

7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperature

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)

Unit: %, Range: 0% to 100%, Value x 1 (e.g. 10% = 10)

1 = Off 2 = Changeover with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan

6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm

Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)

Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)

Unit: %, Range: 0% to BO1closepos-4%, Value x 1 (e.g. 20% = 20)

1 = Off 2 = Changeover with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan

6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm

Writable
W W W
W W W W W W W W
Page | 14

Protocol Register

Base

Index

Description

111

40112 Delay before activation of BO2 in minutes.

112

40113 Close position percentage for contact BO2.

113

40114 Open position percentage for contact BO2.

114

40115 Ramp to control binary output 3.

115

40116 Delay before activation of BO3 in minutes.

116

40117 Close position percentage for contact BO3.

117

40118 Open position percentage for contact BO3.

118

40119 Ramp to control binary output 4.

119

40120 Delay before activation of BO4 in minutes.

120

40121 Close position percentage for contact BO4.

121

40122 Open position percentage for contact BO4.

122

40123 Ramp to control binary output 5.

www.neptronic.com

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned

Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)

Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)

Unit: %, Range: 0% to BO2closepos-4%, Value x 1 (e.g. 20%= 20)

1 = Off 2 = Changeover with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan

6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm

Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)

Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)

Unit: %, Range: 0% to BO3closepos-4%, Value x 1 (e.g. 20% = 20)

1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan

7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm
11 = FAN

Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)

Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)

Unit: %, Range: 0% to BO4closepos-4%, Value x 1 (e.g. 20% = 20)

1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan

7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm
11 = FAN

Writable W W W W W W W
W
W W W
W
Page | 15

Protocol Register

Base

Index

Description

123

40124 Delay before activation of BO5 in minutes.

124

40125 Close position percentage for contact BO5.

125

40126 Open position percentage for contact BO5.

126

40127 Ramp to control binary output 6.

127

40128 Delay before activation of BO6 in minutes.

128

40129 Close position percentage for contact BO6.

129

40130 Open position percentage for contact BO6.

130

40131 Ramp to control binary output 7.

131

40132 Delay before activation of BO7 in minutes.

132

40133 Close position percentage for contact BO7.

133

40134 Open position percentage for contact BO7.

www.neptronic.com

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Writable

Unsigned Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)

W

Scale 1

Unsigned Unit: %, Range: 15% to 80%, Value/1 (e.g. 20% = 20)

W

Scale 1

Unsigned Unit: %, Range: 0% to BO5closepos-4%, Value/1 (e.g. 20% = 20)

W

Scale 1

Unsigned

1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan 7 = Heating 2

8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan

10 = CO2 alarm

11 =6 Way valve

12 = Delta temperature

W

13 = FAN (available only if fan type is 12-3 speeds)

14 = VFD/ECMTempLoopEnable 15 = VFD Pressure Loop

Unsigned Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 = 5 mins)

W

Scale 1

Unsigned Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)

W

Scale 1

Unsigned Unit: %, Range: 0% to BO6closepos-4%, Value x 1 (e.g. 20% = 20)

W

Scale 1

Unsigned

1 = Off
2 = Change Over with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan

6 = Heating 2 with fan

7 = Heating 2

8 = Cooling 1 Heating 1 With Fan

W

9 = HumidifyWithFan

10 = CO2 alarm

Unsigned Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 = 5 mins)

W

Scale 1

Unsigned Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)

W

Scale 1

Unsigned Unit: %, Range: 0% to BO7closepos-4%, Value x 1 (e.g. 20% = 20)

W

Scale 1

Page | 16

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Protocol Register

Base

Index

Description

134

40135 Input contact of analog 1, 2, 3 and 4.

135

40136 Delay before activation of UI1 in seconds.

136

40137 Delay before activation of UI2 in seconds.

137

40138 Delay before activation of UI3 in seconds.

138

40139 Delay before activation of UI4 in seconds.

139

40140 Humidity control mode status.

140

40141 Humidity setpoint (%RH) in occupancy or day mode.

141

40142

Dehumidification setpoint (%RH) in unoccupied or night mode.

142

40143

Humidification setpoint (%RH) in unoccupied or night mode.

143

40144 Minimum user setpoint.

144

40145 Maximum user setpoint.

145

40146 Humidity proportional band.

146

40147 Humidity deadband.

147

40148 Internal humidity sensor offset correction. *

Not available on all models.

148

40149 External humidity sensor offset correction.

Data Type

Range

Bit String
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 10
Signed
Scale 10

B0: Analog input 1 0 = Normally Open, 1 = Normally Close
B1: Analog input 2 0 = Normally Open, 1 = Normally Close

B2: Analog input 3 0 = Normally Open, 1 = Normally Close
B3: Analog input 4 0 = Normally Open, 1 = Normally Close

Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs = 20)

Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs = 20)

Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs = 20) Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs =20) 1 = Auto, 2 = Dehumidification, 3 = Humidification, 4 = Off Unit: %RH, Limited by min/max humidity setpoint, Value x 10 (e.g. 20%RH = 200)

Unit: %RH, Range: 10%RH to 65%RH, Value x 10 (e.g. 20%RH = 200)

Unit: %RH, Range: 10%RH to 65%RH, Value x 10 (e.g. 20%RH = 200)

Unit: %RH, Range: 10%RH to max, Value x 10 (e.g. 20%RH = 200)

Unit: %RH, Range: min to 90%RH, Value x 10 (e.g. 20%RH = 200)

Unit: %RH, Range: 3%RH to 10%RH, Value x 10 (e.g. 4%RH = 40)

Unit: %RH, Range: 0%RH to 5%RH, Value x 10 (e.g. 4%RH = 40)

Unit: %RH, Range: ± 5%RH, Value x 10 (e.g. 2%RH = 20)

Unit: %RH, Range: ± 5%RH, Value x 10 (e.g. 2%RH = 20)

Writable
W
W W W W W W W W W W W W W W

www.neptronic.com

Page | 17

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Protocol Register

Base

Index

Description

149

40150 Pressure sensor value in Pascals.

150

40151 Maximum pressure value range.

151

40152 Actual VFD pressure loop x 10 (%).

152

40153 VFD pressure loop setpoint.

153

40154 VFD pressure loop deadband.

154

40155 VFD pressure loop proportional band.

155

40156 VFD pressure loop integral time.

156

40157 Actual VFD temperature loop while cooling x 10 (%).

157

40158 Actual VFD temperature loop while heating x 10 (%).

158

40159 VFD temperature loop setpoint x 10 (ºC or ºF).

159

40160 VFD temperature loop deadband x 10 (ºC or ºF).

160

40161

VFD temperature loop proportional band x 10 (ºC or ºF).

161

40162 VFD temperature loop integral time.

162

40163 Voltage required for closing the 6-way valve.

163

40164

Minimum output voltage required for cooling for the 6way valve.

164

40165

Minimum output voltage required for heating for the 6-way valve.

165

40166 6-way valve size selection in inches.

166

40167 Signal type for Analog output 1.

Data Type
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Scale 100
Unsigned
Scale 100
Unsigned
Scale 100
Unsigned Unsigned

Range
Unit: Pascals, Range: 100 to Register Maximum pressure value range [40135], Value/1 (e.g. 200Pa = 200) Unit: Pascals, Range: 200 to 20000, Value/1 (e.g. 200Pa = 200)
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: Pascals, Range: 100 to Register Maximum pressure value range [40135], Value/1 (e.g. 200Pa = 200) Unit: Pascals, Range: 0 to 100, Value x 1 (e.g. 20Pa = 20)
Unit: Pascals, Range: 100 to 500, Value x 1 (e.g. 250Pa = 250)
Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g. 50 secs = 50)
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20)
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: depends on system unit, Range: 10ºC to 40ºC or 50ºF to 104ºF, Value x 10 (e.g. 30°C = 300 or 60ºF = 600) Unit: depends on system unit, Range: 0ºC to 5ºC or 0ºF to 9ºF, Value x 10 (e.g. 2°C = 20 or 4ºF = 40) Unit: depends on system unit, Range: 0.5ºC to 5ºC or 1ºF to 9ºF, Value x 10 (e.g. 2°C= 20 or 4ºF = 40) Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g. 50 secs = 50)
Unit: V, Range: 0 to 11 V, Value x 100 (e.g. 2V = 200)
Unit: V, Range: 0 to 11 V, Value x 100 (e.g. 2V = 200)
Unit: V, Range: 0 to 11 V, Value x 100 (e.g. 2V = 200) 1 = 1/2, 2 = 3/4, 3 = 1 1 = Analog, 2 = On-Off, 3 = Pulsing

Writable
RO W RO W W W W RO RO W W W W W W W W W

www.neptronic.com

Page | 18

Protocol Register

Base

Index

Description

167

40168 Signal type for Analog output 2.

168

40169 Signal type for Analog output 3.

169

40170 Signal type for Analog output 4.

170

40171 Signal type for Binary output 1.

171

40172 Signal type for Binary output 2.

172

40173 Signal type for Binary output 3.

173

40174 Signal type for Binary output 4.

174

40175 Signal type for Binary output 5.

175

40176 Signal type for Binary output 6.

176

40177 Signal type for Binary output 7.

177

40178 PIR Relay sensor.

178

40179 Floating output motor timing for BO1/BO2.

179

40180 Floating output motor timing for BO3/BO7.

180

40181 Reserved

181

40182 Floating output value for BO1/BO2.

182

40183 Floating output value for BO3/BO7.

183

40184 Reserved

184

40185 Value for Pulse output 1.

185

40186 Value for Pulse output 2.

186

40187 Value for Pulse output 3.

187

40188 Value for Pulse output 4.

188

40189 Value for Pulse output 5.

189

40190 Value for Pulse output 6.

www.neptronic.com

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned
Scale 1
Unsigned
Scale 1

1 = Analog, 2 = On-Off, 3 = Pulsing 1 = Analog, 2 = On-Off, 3 = Pulsing 1 = Analog, 2 = On-Off, 3 = Pulsing 1 = Pulsing, 2 = On-Off, 3 = Floating 1 = Pulsing, 2 = On-Off 1 = Pulsing, 2 = On-Off, 3 = Floating 1 = Pulsing, 2 = On- Off 1 = Pulsing, 2 = On-Off 1 = Pulsing, 2 = On-Off 1 = Pulsing, 2 = On-Off 0 = Relay was not activated, 1 = Relay was activated
Unit: Seconds, Range: 15 to 250 seconds, Value x 1 (e.g. 20 secs = 20)
Unit: Seconds, Range: 15 to 250 seconds, Value x 1 (e.g. 20 secs = 20)

Unsigned
Scale 10
Unsigned
Scale 10

Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20)

Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10

Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20)

Writable W W W W W W W W W W W W W
W W
W W W W W W
Page | 19

Protocol Register

Base

Index

Description

190

40191 Value for Pulse output 7.

191

40192 Delta temperature between inlet and outlet.

192

40193 Delta temperature set point.

193
194 195 196 197 to 198 199
200
201

40194 Light intensity sensor value.

40195 Light intensity sensor maximum range.

40196 Reserved

40197 VOC sensor value.

40198 to 40199

Reserved

40200 User backlight or contrast intensity.

40201 Occupancy backlight or contrast intensity.

40202 Unoccupancy backlight or contrast intensity.

Universal Wall-Mount Controller
Modbus Communication Module User Guide

Data Type

Range

Unsigned
Scale 10
Signed
Scale 100
Signed
Scale 100
Unsigned
Scale 1
Unsigned
Scale 1

Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20)
Unit: depends on system unit, Range: -12°C to 12°C or 10.4°F to 53.6°F Value x 100 (e.g. 8°C = 800 or 6ºF = 600) Unit: depends on system unit, Range: -12°C to 12°C or 10.4°F to 53.6°F Value x 100 (e.g. 8°C = 800 or 6ºF = 600) Unit: Luxes, Range: 0 to 16000 Luxes, Value x 1 (e.g. 20 Luxes = 20)
Unit: Luxes, Range: 1000 to 16000 Luxes, Value x 1 (e.g. 20 Luxes = 20)

Unsigned
Scale 1

Unit: PPB, Range: 0 to 30000 PPB, Value x 1 (e.g. 20 PPB= 20)

Writable W W W RO W
RO

Unsigned Unit: %, Range: 0% to 100%, Value x 1 (e.g. 30% = 30)

W

Scale 1

Unsigned Unit: %, Range: 0% to 100%, Value x 1 (e.g. 30% = 30)

W

Scale 1

Unsigned Unit: %, Range: 0% to 100%, Value x 1 (e.g. 30% = 30)

W

Scale 1

www.neptronic.com

Page | 20

Notes

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada neptronic.com
Toll free in North America: 1-800-361-2308 Tel.: 514-333-1433 Fax: 514-333-3163
Customer service fax: 514-333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)

References

Read User Manual Online (PDF format)