TUUB Series Universal Wall Mount Controller
“`html
Product Information
Specifications:
-
Product Name: Universal Wall-Mount Controller TUUB Series
Modbus Communication Module -
Supported Baud Rates: 9600, 19200, 38400, 57600
-
Address Range: 1 to 246
Product Usage Instructions:
Modbus Communication:
The Modbus Communication Module allows for various operations
including:
- Read Holding Registers (0x03)
- Write Single Register (0x06)
- Write Multiple Registers (0x10)
Baud Rate and Configuration:
The physical layer supports fixed baud rate selection or
automatic baud rate detection. Supported baud rates are 9600,
19200, 38400, and 57600. Parity control and stop bit configuration
can be adjusted through the Modbus Comport Config device menu.
Device Addressing:
The device’s unique address can be set from 1 to 246 through the
device menu or holding register index 0.
Holding Registers Table:
The holding registers table provides detailed information on
register indexes and their corresponding descriptions. It includes
various parameters such as communication port configuration, system
status, internal and external temperature sensor readings.
FAQ:
Q: How can I change the baud rate of the Modbus Communication
Module?
A: You can change the baud rate through the Modbus Auto Baud
Rate device menu item or holding register index 1.
Q: What is the range of supported baud rates?
A: The supported baud rates are 9600, 19200, 38400, and
57600.
“`
Universal Wall-Mount Controller
TUUB Series Modbus Communication Module User Guide
TUUB-Modbus Guide-240509
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Introduction
The TUUB Modbus Communication Module User Guide provides information for using
Neptronic® TUUB communication feature. The TUUB uses Modbus communication
protocol over serial line in the RTU mode and provides a Modbus network
interface between client devices and Neptronic TUUB Series devices. The TUUB
Modbus Guide assumes that you are familiar with Modbus terminology. The
following are the requirements for Modbus:
· Data Model. The TUUB Modbus server data model uses only the Holding
Registers table. · Function Codes. The TUUB Modbus server supports a limited
function codes subset comprising:
o Read Holding Registers (0x03) o Write Single Register (0x06) o Write
Multiple Registers (0x10)
· Exception Responses. The TUUB Modbus server supports the following exception
codes:
o Illegal data address o Illegal data value o Slave device busy
· Serial Line. The TUUB Modbus over serial line uses RTU transmission mode
over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
o The physical layer can use fixed baud rate selection or automatic baud rate
detection (default) as per the Modbus Auto Baud Rate device menu item or
holding register index 1.
o The supported baud rates are 9600, 19200, 38400, and 57600. o The physical
layer also supports variable parity control and stop bit configuration as per
the Modbus Comport
Config device menu item or holding register index 2. o In auto baud rate
configuration, if the device detects only consecutive bad frames (2 or more)
for one second with
any given baud rate, it will reinitialize itself to the next baud rate.
· Addressing. The TUUB device only answers at the following address:
o The device’s unique address (1 to 246) that can be set through the device
menu or through holding register index 0.
www.neptronic.com
Page | 1
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Holding Registers Table
Table Glossary
Name
Description
W RO Unsigned Signed Bit String
Writable Register Read Only Register For range of values from 0 to 65,535, unless otherwise specified For range of values from -32,768 to 32,767, unless otherwise specified For registers with multiple values using bit mask (example, flags)
Holding Register Table
Name
ASCII MSB LSB MSW LSW
Description
For registers containing ASCII (8-bit) characters Most Significant Byte Least
Significant Byte Most Significant Word Least Significant Word
Protocol Base
0
Register Index
40001
Description
Address – Neptronic ID and Modbus address of current device.
1
40002 MSTP Baud Rate.
2
40003 Communication port configuration.
3
40004 ProdName_87, characters 8-7 of 8 name characters.
4
40005 ProdName_65, characters 6-5 of 8 name characters.
5
40006 ProdName_43, characters 4-3 of 8 name characters.
6
40007 ProdName_21, characters 2-1 of 8 name characters.
7
40008 Controller Product_Version, actual firmware version.
8
40009 Controller parameters version.
9
40010 System Status 1.
www.neptronic.com
Data Type
Range
Unsigned Unsigned
Scale 100
Unsigned ASCII ASCII ASCII ASCII
Unsigned Unsigned
Bit String
MSB = 22, LSB = 1-246
0, 9600, 19200, 38400, or 57600, 0 = Auto Baud Rate Detection Value/100 (e.g. 38400 baud = 384)
1 = No parity, 2 Stop bits, 2 = Even parity, 1 stop bit, 3 = Odd parity, 1 stop bit
MSB = 84 (T), LSB = 85 (U)
MSB = 67 (C), LSB = 66 (B)
MSB = 50 (2), LSB = 52 (4)
MSB = 32 (Space), LSB = 0 (Null)
1 to 65535 (e.g. 115)
1 to 65535 (e.g. 102)
B0: System operation 0 = Normal, 1 = Fault
B2: System override by NSB or OCC 0 = Normal, 1 = OFF
B3: ChangeOverMode 0 = Cooling, 1 = Heating
B4: AL_FlowSwitch 0 = No alarm, 1 = Alarm activated
B6: AL_DirtyFilter 0 = No alarm, 1 = Alarm activated
Writable W W W W W W W RO RO
RO
Page | 2
Protocol Register
Base
Index
Description
10
40011 System Status 2.
11
40012 Internal temperature sensor reading.
12
40013 External temperature sensor reading.
13
40014 Changeover temperature sensor reading.
14
40015 Control temperature reading.
15
40016 Internal humidity sensor reading.
Not available on all models.
16
40017 External humidity sensor reading.
17
40018 Analog input 1 reading.
18
40019 Analog input 2 reading.
19
40020 Analog input 3 reading.
www.neptronic.com
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Bit String
Signed
Scale 100
Signed
Scale 100
Signed
Scale 100
Signed
Scale 100
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 100
Signed
Scale 100
Signed Scale 100
B0: Selector Switch Status 0 = Remote Mode, 1 = Local Mode
B2: CO2 Alarm 0 = Normal, 1 = Alarm
B10: AL_UI1 0 = Off, 1 = On
B11: AL_UI2 0 = Off, 1 = On
B7: AL_Override 0 = Off, 1 = On
B12: AL_UI3 0 = Off, 1 = On
B8: AL_WindowOpened 0 = Off, 1 = On
B13: AL_UI4 0 = Off, 1 = On
B9: AL_DoorOpened 0 = Off, 1 = On
B15: AL_OverHeat 0 = Off, 1 = On
Unit: ºC/ºF, Range: 0ºC to 50ºC or 32ºF to 122ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)
Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)
Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)
Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)
Unit: % RH, Range: 10%RH to 90%RH, Value x 10 (e.g. 30%RH = 300)
Unit: % RH, Range: 10%RH to 90%RH, Value x 10 (e.g. 30%RH = 300)
Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0
(open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300)
Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0
(open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300)
Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0
(open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300)
Writable
RO
RO RO RO W RO RO RO RO RO
Page | 3
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Protocol Register
Base
Index
Description
20
40021 Analog input 4 reading.
21
40022 External CO2 sensor value in ppm.
22
40023 Internal CO2 sensor value in ppm.
23
40024 CO2 control value in ppm.
24
40025 Actual system occupancy state.
25
40026 Actual night setback state of the system.
26
40027 Actual heating demand of ramp 1.
27
40028 Actual heating demand of ramp 2.
28
40029 Actual cooling demand of ramp 1.
29
40030 Actual cooling demand of ramp 2.
30
40031 Actual changeover demand.
31
40032 Actual fan demand.
32
40033 Actual dehumidification demand.
33
40034 Actual humidification demand.
34
40035
Cooling Heating SwitchTimerCount – countdown until the system is able to swap the demand.
35
40036 Analog output 1 value.
36
40037 Analog output 2 value.
37
40038 Analog output 3 value.
www.neptronic.com
Data Type
Range
Signed Scale 100
Signed
Scale 1
Signed
Scale 1
Signed
Scale 1
Unsigned
Unsigned
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF, 0 (open), 1 (close). Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300) Unit: ppm, 0 to Register (CO2 range), Value x 1 (e.g. 500 ppm = 500) Unit: ppm, 0 to Register (CO2 range), Value x 1 (e.g. 500 ppm = 500) Unit: ppm, 0 to Register (CO2 range), Value x 1 (e.g. 500 ppm = 500) 1 = NoOccupancy, 2 = Occupancy, 3 = Override 1 = Day, 2 = Night, 3 = Override Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: Seconds, Range: 0 to 7200 seconds, Value/1 (e.g. 100 secs = 100) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000)
Writable
RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO W W W
Page | 4
Protocol Register
Base
Index
Description
38
40039 Analog output 4 value.
39
40040 Binary output – 6 relays output status.
40
40041 System command.
41
40042 System mode status.
42
40043 Fan speed selection by user.
43
40044 Temperature setpoint in occupancy or day mode.
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Unsigned
Scale 10
Bit String
Bit String
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 100% = 1000)
B0: Binary Output 1 0 = Open, 1 = Close
B1: Binary Output 2 0 = Open, 1 = Close
B2: Binary Output 3 0 = Open, 1 = Close [B2, B6, B9 – B15]: Reserved
B0: Cfg_ServiceDisplayAddress 0 = Normal, 1 = Display address on LCD
B3: Binary Output 4 0 = Open, 1 = Close
B4: Binary Output 5 0 = Open, 1 = Close
B5: Binary Output 6 0 = Open, 1 = Close
B6: Binary Output 7 0 = Open, 1 =Close B4: Cfg_HeatingRamp2Lock 0 = Off, 1 =
On
B5: Cfg_ChangeOverRampLock 0 = Off, 1 = On
B1: Cfg_CoolingRampLock 0 = Off, 1 = On
B7: Cfg_HumidifyRampLock 0 = Off, 1 = On
Unsigned
Unsigned Signed
Scale 10
B3: Cfg_HeatingRamp1Lock 0 = Off, 1 = On
B8: Cfg_DehumidifyRampLock 0 = Off, 1 = On
1 = Auto [Register 40074 allows Auto Mode (1 or 5)]
2 = Heating [Register 40074 allows Heating Mode (1, 2 or 4)]
3 = EMH [Register 40041 Bits 2 and 1 = On and Enable (1) and
Register 40074 allows Heating Mode (1, 2 or 4)]
4 = Cooling [Register 40074 allows Cooling Mode (1, 3 or 4)]
5 = Fan [Register 40040 Bit 12 = Advanced (1) and Bit 13 = Enable]
6 = Off [Register 40044 Bit 6 = Enable (0)]
1 = Auto, 2 = Low, 3 = Med, 4 = High
Unit: ºC/ºF, Range: min to max setpoint, Value x 10 (e.g. 18°C = 180)
Writable W W
W
W W W
www.neptronic.com
Page | 5
Protocol Register
Base
Index
Description
44
40045 System option1.
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
B0: Cfg_TempUnitTstat 0 = ºC, 1 = ºF
B8: Cfg_KeyPadUpperLeftLock 0 = Off, 1 = On
B1: Cfg_TempUnitModbus 0 = ºC, 1 = ºF
B9: Cfg_KeyPadArrowsLock 0 = Off, 1 = On
Bit String
B2: Cfg_TempSetPointLock 0 = Off, 1 = On
B3: Cfg_HumSetPointLock 0 = Off, 1 = On
B4: Cfg_ProgramModeLock 0 = Off, 1 = On
B5: AL_FreezeProtection 0 = Off, 1 = On
B6: Cfg_UserSysOffModes 0 = Enable, 1 = Disable
B7: Cfg_KeyPadBottomLeftLock 0 = Off, 1 = On
B10: CfgUserFanAutoMode 0 = Enable, 1 = Disable
B11: Cfg NightOrNoOccMode 0 = Setpoint, 1 = OFF
B12: Cfg_HumControlSource 0 = Intern Sensor, 1 = Extern Sensor Not available
on all models.
B13: Time Mode 0 = 24h, 1 = 12h
B14: Cfg_WindowOpenedMode 0 = Setpoint, 1 = OFF
B15: Cfg_DoorOpenedMode 0 = Setpoint, 1 = OFF
Writable W
www.neptronic.com
Page | 6
Protocol Register
Base
Index
Description
45
40046 System option2.
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
B0: Baud Rate 0 = Auto, 1 = Manual
B1: Cfg_ActivateSchedule 0 = Off, 1 = On
Bit String
B2: Cfg_AnalogOutput1Direction 0 = Direct, 1 = Reverse
B3: Cfg_AnalogOutput2Direction 0 = Direct, 1 = Reverse
B4: Cfg_AnalogOutput3Direction 0 = Direct, 1 = Reverse
B5: Cfg_AnalogOutput4Direction 0 = Direct, 1 = Reverse
B6: Cfg_BinaryOutput1Direction 0 = Direct, 1 = Reverse
B7: Cfg_BinaryOutput2Direction 0 = Direct, 1 = Reverse
B8: Cfg_BinaryOutput3Direction 0 = Direct, 1 = Reverse
B9: Cfg_BinaryOutput4Direction 0 = Direct, 1 = Reverse
B10: Cfg_BinaryOutput5Direction 0 = Direct, 1 = Reverse
B11: Cfg_BinaryOutput6Direction 0 = Direct, 1 = Reverse
B12: CfgBinaryOutput7Direction 0 = Direct, 1 = Reverse
B12: Cfg FanSpeedOption 0 = Standard, 1 = Advanced (OE1)
B13: Cfg_UserSysFanMode 0 = Disable, 1 = Enable
B14: Cfg_HideFanDisplay 0 = No, 1 = Yes
Writable W
www.neptronic.com
Page | 7
Protocol Register
Base
Index
Description
46
40047 System option3.
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Bit String
B0: DAYLIGHT_SAVINGS_STATUS 0 = Normal, 1 = Summer
B1: CfgEMHOutput 0 = Disable, 1 = Enable
B2: Cfg HeatPumpMode 0 = Off (General Unit), 1 = On (HeatPump)
B3: Cfg_ReversingValve (O/B) 0 = O, 1 = B
B4: Cfg_EMHAutoMode 0 = No, 1 = Yes
B5: Cfg_Y2Output 0 = Disable, 1 = Enable
B6: Cfg_AnalogInput1MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B7: Cfg_AnalogInput2MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B8: Cfg_AnalogInput3MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B9: Cfg_AnalogInput4MinVolt 0 = 0.0 Volt, 1 = 2.0 Volt
B10: Cfg_VFDTempInput 0 = Intern Sensor, 1 = Extern Sensor
B12: Cfg_FloatingBO1/BO2Direction 0 = Direct, 1 = Reverse
B13: Cfg_FloatingBO3/BO7Direction 0 = Direct, 1 = Reverse
B15: Cfg_DeltaTempLogic 0 = Off, 1 = On
Writable W
www.neptronic.com
Page | 8
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Protocol Register
Base
Index
Description
47
40048 System option4.
48
40049 Display information.
49
40050 Temperature control source.
50
40051 Network fallback timeout.
51
40052 Minimum occupancy/day setpoint.
52
40053 Maximum occupancy/day setpoint.
53
40054
Cooling temperature setpoint in unoccupied or night mode.
www.neptronic.com
Data Type
Range
Bit String
Unsigned Unsigned Unsigned
Scale 1
Signed
Scale 10
Signed
Scale 10
Signed
Scale 10
B0: Cfg_CO2ControlSource 0 = Internal Sensor, 1 = External Sensor
B1: Cfg_DisplayHumidity 0 = Display the temperature only, 1 = Display the
temperature and humidity
B2: Cfg_DisplayCO2 0 = Don’t display CO2 control value, 1 = Display CO2
control value
B6: Cfg_VFDTempSetpointSource 0 = VFDTempSetpoint, 1 = TempSetpoint
B7: Cfg_AnalogOutput1OffVoltage 0 = Off, 1 = Minimum
B8: Cfg_AnalogOutput2OffVoltage 0 = Off, 1 = Minimum
B9: Cfg_AnalogOutput3OffVoltage 0 = Off, 1 = Minimum
B10: Cfg_AnalogOutput4OffVoltage 0 = Off, 1 = Minimum
B11: Cfg_CO2AutoSelfCalib 0 = Off, 1 = On 1 = Temperature and Demand, 2 =
Setpoint and Demand, 3 = Temperature Only, 4 = Setpoint Only, 5 = Off 1 =
Network Temp, 2 = Intern Temp, 3 = Extern Temp
Unit: Minutes, Range: 0 to 60, Value/1 (e.g. 30 mins = 30)
Unit: ºC/ºF, Range: 10ºC to max or 50ºF to max Value x 10 (e.g. 18°C = 180 or
60ºF = 600) Unit: ºC/ºF, Range: min to 40ºC or min to 104ºF Value x 10 (e.g.
18°C = 180 or 60ºF = 600) Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF
Value x 10 (e.g.18°C = 180 or 60ºF = 600)
Writable
W
W W W W W W
Page | 9
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Protocol Register
Base
Index
Description
54
40055
Heating temperature setpoint in unoccupied or night mode.
55
40056 Heating proportional band for ramp 1.
56
40057 Heating proportional band for ramp 2.
57
40058 Cooling proportional band for ramp 1.
58
40059 Cooling proportional band for ramp 2.
59
40060 Changeover proportional band.
60
40061 Heating deadband for ramp 1.
61
40062 Heating deadband for ramp 2.
62
40063 Cooling deadband for ramp 1.
63
40064 Cooling deadband for ramp 2.
64
40065 Changeover deadband.
65
40066 Changeover setpoint.
66
40067 Fan time out in seconds.
67
40068 Fan damping factor in seconds.
68
40069 Heating integral time factor in seconds.
69
40070 Cooling integral time factor in seconds.
Data Type
Range
Signed
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 10
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF Value x 10 (e.g. 18°C = 180
or 60ºF = 600) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9Fº Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9Fº Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0.5ºC to 5ºC or 1ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 0ºC to 5ºC or 0ºF to 9ºF Value x 10 (e.g. 1ºC =
10 or 2ºF = 20) Unit: ºC/ºF, 10ºC to 40ºC or 50ºF to 104ºF Value x 10 (e.g.
12ºC = 120 or 60ºF = 600)
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g.100 secs = 100)
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g.100 secs = 100)
Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g.100 secs = 100)
Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g.100 secs = 100)
Writable W W W W W W W W W W W W W W W W
www.neptronic.com
Page | 10
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Protocol Register
Base
Index
Description
70
40071
Cooling Heating SwitchTimer – Delay between cool and heat or vice versa.
71
40072 Cooling anticycle delay in minutes.
72
40073 NSB override delay in minutes.
73
40074 Unoccupied override delay in minutes.
74
40075 Occupancy minimum time in minutes.
75
40076 Unoccupied override delay count down in minutes.
76
40077 Fan mode (speed) in unoccupied or NSB mode.
77
40078 Fan mode (speed) when window is opened (alarm).
78
40079 Fan mode (speed) when door is opened (alarm).
79
40080 System control mode.
80
40081 Override System occupancy/NSB mode.
81
40082 Internal temperature sensor offset correction.
82
40083 Universal Input 1 signal.
Data Type
Range
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned Unsigned Unsigned Unsigned Unsigned
Signed
Scale 100
Unsigned
Unit: Minutes, Range: 0 to 120 minutes, Value x 1 (e.g.100 mins = 100)
Unit: Minutes, Range: 0 to 15 minutes, Value x 1 (e.g.10 mins = 10)
Unit: Minutes, Range: 0 to 180 minutes, Value x 1 (e.g.100 mins = 100)
Unit: Minutes, Range: 0 to 180 minutes, Value x 1 (e.g.100 mins = 100)
Unit: Minutes, Range: 0 to 720 minutes, Value x 1 (e.g.100 mins = 100)
Unit: Minutes, Range: 0 to 180 minutes, Value x 1 (e.g.100 mins = 100)
1 = Low, 2 = Med, 3 = High, 4 = Auto
1 = Low, 2 = Med, 3 = High, 4 = Auto
1 = Low, 2 = Med, 3 = High, 4 = Auto
1 = Auto, 2 = Heat, 3 = Cool, 4 = Heat or Cool, 5 = Auto Lock
1 = Locally, 2 = OFF, 3 = Occupied, 4 = Unoccupied, 5 = Day, 6 = Night
Unit: depends on system unit, Range: ± 5ºC or +/-9ºF
Value x 100 (e.g.2ºC = 200 or 3ºF = 300)
1 = OFF 2 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor 0-10V 8 = CO2 sensor 0-10V 9 = Occupancy binary input 10 = NSB binary input 11 = Override binary input 12 = Window binary input 13 = Door binary input
14 = Dirty Filter binary input 15 = Flow switch binary input 16 = OverHeat binary input 17 = Selector switch binary input 18 = Fan Feedback 19 = Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern sensor TT-012 22 = Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 = Delta T Outlet 0-10V
Writable W W W W W W W W W W W W
W
www.neptronic.com
Page | 11
Protocol Register
Base
Index
Description
83
40084 Universal Input 2 signal.
84
40085 Universal Input 3 signal.
85
40086 Universal Input 4 signal.
86
40087 External temperature sensor offset correction.
87
40088 Changeover control mode.
www.neptronic.com
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Unsigned
Unsigned
Unsigned Signed
Scale 100
Unsigned
1 = OFF 2 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally
cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor
0-10V 8 = CO2 sensor 0-10V 9 = Occupancy binary input 10 = NSB binary input 11
= Override binary input 12 = Window binary input 13 = Door binary input
1 = OFF 1 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally
cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor
0-10V 8 = CO2 sensor 0-10V 9 = Occupancy digital input 10 = NSB digital input
11 = Override digital input 12 = Window digital input 13 = Door digital input
1 = OFF 2 = Extern sensor 10K 3 = Change over sensor 4 = Change over normally
cool 5 = Change over normally heat 6 = Outside air sensor 7 = Extern sensor
0-10V 8 = CO2 sensor 0-10V 9 = Occupancy digital input 10 = NSB digital input
11 = Override digital input 12 = Window digital input 13 = Door digital input
14 = Dirty Filter binary input 15 = Flow switch binary input 16 = OverHeat
binary input 17 = Selector switch binary input 18 = Fan Feedback 19 = Humidity
sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern sensor TT-012 22 = Delta T
Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 = Delta T Outlet
0-10V
14 = Dirty Filter digital input 15 = Flow switch digital input 16 = OverHeat
digital input 17 = Selector switch digital input 18 = Fan Feedback 19 =
Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern Sensor TT-012 22
= Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 =
Delta T Outlet 0-10V
14 = Dirty Filter digital input 15 = Flow switch digital input 16 = OverHeat
digital input 17 = Selector switch digital input 18 = Fan Feedback 19 =
Humidity sensor 0-10V 20 = Pressure sensor 0-10V 21 = Extern Sensor TT-012 22
= Delta T Inlet 10K 23 = Delta T Inlet 0-10V 24 = Delta T Outlet 10K 25 =
Delta T Outlet 0-10V
Unit: depends on system unit, Range: ± 5ºC or +/-9ºF
Value x 100 (e.g.2ºC = 200 or 3ºF = 300)
1 = Local, 2 = Cool, 3 = Heat
Writable W
W
W W W
Page | 12
Protocol Register
Base
Index
Description
88
40089 Minimum external temperature reading.
89
40090 Maximum external temperature reading.
90
40091 Maximum CO2 reading.
91
40092 Alarm level of CO2.
92
40093 Fan output signal.
93
40094 Ramp to control analog output 1.
94
40095 Minimum voltage for analog output 1 (volt).
95
40096 Maximum voltage for analog output 1 (volt).
96
40097 Ramp to control analog output 2.
97
40098 Minimum voltage for analog output 2 (volt).
98
40099 Maximum voltage for analog output 2 (volt).
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Signed
Scale 10
Signed
Scale 10
Signed
Scale 1
Signed
Scale 1
Unsigned
Unsigned
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Unsigned
Scale 10
Unsigned
Scale 10
Unit: depends on system unit, Range: -40ºC to 0ºC or -40ºF to 32ºF Value x 10
(e.g.-20°C = -200 or -20°F = 200) Unit: depends on system unit, Range: 50ºC to
100ºC or 122ºF to 212ºF Value x 10 (e.g.60°C = 600 or 140°F = 1400)
Unit: PPM, Range: 1000 to 5000, Value x 1 (e.g.2000 = 2000)
Unit: PPM, Range: 1000 to CO2 range, Value x 1 (e.g.1000 = 1000)
1 = 1 speed, 2 = 2 speeds, 3 = 3 speeds, 4 = Analog
1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan 7 =
Heating 2
8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperture 13 = VFD/ECMTempLoopEnable 14 = VFD Pressure Loop
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan 7 =
Heating 2 8 = Cooling 1 Heating 1 With Fan
9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperature 13 = VFD/ECMTempLoopEnable 14 = VFD Pressure Loop 15 = FAN (not available if AO1 is set to VFD/ECMTempLoopEnable or VFD Pressure Loop)
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
Writable W W W W W
W
W W
W
W W
www.neptronic.com
Page | 13
Protocol Register
Base
Index
Description
99
40100 Ramp to control analog output 3.
100
40101 Minimum voltage for analog output 3 (volt).
101
40102 Maximum voltage for analog output 3 (volt).
102
40103 Ramp to control analog output 4.
103
40104 Minimum voltage for analog output 4 (volt).
104
40105 Maximum voltage for analog output 4 (volt).
105
40106 Position of CH1 AO output while heating (%).
106
40107 Ramp to control binary output 1.
107
40108 Delay before activation of BO1 in minutes.
108
40109 Close position percentage for contact BO1.
109
40110 Open position percentage for contact BO1.
110
40111 Ramp to control binary output 2.
www.neptronic.com
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
1= Off
2 = Change Over with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 =
Heating 1 with fan 6 = Heating 2 with fan
7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperature
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
1 = Off 2 = Change Over with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan
7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan 10 = CO2 alarm 11 = 6 Way Valve 12 = Delta temperature
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
Unit: Volt, Range: 0V to 10V, Value x 10 (e.g. 3 V = 30)
Unit: %, Range: 0% to 100%, Value x 1 (e.g. 10% = 10)
1 = Off 2 = Changeover with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan
6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 =
HumidifyWithFan
10 = CO2 alarm
Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)
Unit: %, Range: 0% to BO1closepos-4%, Value x 1 (e.g. 20% = 20)
1 = Off 2 = Changeover with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan
6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 =
HumidifyWithFan
10 = CO2 alarm
Writable
W W W
W W W W W W W W
Page | 14
Protocol Register
Base
Index
Description
111
40112 Delay before activation of BO2 in minutes.
112
40113 Close position percentage for contact BO2.
113
40114 Open position percentage for contact BO2.
114
40115 Ramp to control binary output 3.
115
40116 Delay before activation of BO3 in minutes.
116
40117 Close position percentage for contact BO3.
117
40118 Open position percentage for contact BO3.
118
40119 Ramp to control binary output 4.
119
40120 Delay before activation of BO4 in minutes.
120
40121 Close position percentage for contact BO4.
121
40122 Open position percentage for contact BO4.
122
40123 Ramp to control binary output 5.
www.neptronic.com
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)
Unit: %, Range: 0% to BO2closepos-4%, Value x 1 (e.g. 20%= 20)
1 = Off 2 = Changeover with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan
6 = Heating 2 with fan 7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 =
HumidifyWithFan
10 = CO2 alarm
Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)
Unit: %, Range: 0% to BO3closepos-4%, Value x 1 (e.g. 20% = 20)
1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 = Heating 1 with fan 6 =
Heating 2 with fan
7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm
11 = FAN
Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)
Unit: %, Range: 0% to BO4closepos-4%, Value x 1 (e.g. 20% = 20)
1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan
7 = Heating 2 8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm
11 = FAN
Writable W W W W W W W
W
W W W
W
Page | 15
Protocol Register
Base
Index
Description
123
40124 Delay before activation of BO5 in minutes.
124
40125 Close position percentage for contact BO5.
125
40126 Open position percentage for contact BO5.
126
40127 Ramp to control binary output 6.
127
40128 Delay before activation of BO6 in minutes.
128
40129 Close position percentage for contact BO6.
129
40130 Open position percentage for contact BO6.
130
40131 Ramp to control binary output 7.
131
40132 Delay before activation of BO7 in minutes.
132
40133 Close position percentage for contact BO7.
133
40134 Open position percentage for contact BO7.
www.neptronic.com
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Writable
Unsigned Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 mins = 5)
W
Scale 1
Unsigned Unit: %, Range: 15% to 80%, Value/1 (e.g. 20% = 20)
W
Scale 1
Unsigned Unit: %, Range: 0% to BO5closepos-4%, Value/1 (e.g. 20% = 20)
W
Scale 1
Unsigned
1 = Off
2 = Changeover with fan
3 = Cooling 1 with fan
4 = Cooling 2 with fan 5 = Heating 1 with fan 6 = Heating 2 with fan 7 =
Heating 2
8 = Cooling 1 Heating 1 With Fan 9 = HumidifyWithFan
10 = CO2 alarm
11 =6 Way valve
12 = Delta temperature
W
13 = FAN (available only if fan type is 12-3 speeds)
14 = VFD/ECMTempLoopEnable 15 = VFD Pressure Loop
Unsigned Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 = 5 mins)
W
Scale 1
Unsigned Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)
W
Scale 1
Unsigned Unit: %, Range: 0% to BO6closepos-4%, Value x 1 (e.g. 20% = 20)
W
Scale 1
Unsigned
1 = Off
2 = Change Over with fan 3 = Cooling 1 with fan 4 = Cooling 2 with fan 5 =
Heating 1 with fan
6 = Heating 2 with fan
7 = Heating 2
8 = Cooling 1 Heating 1 With Fan
W
9 = HumidifyWithFan
10 = CO2 alarm
Unsigned Unit: Minutes, Range: 0 to 15 Minutes, Value x 1 (e.g. 5 = 5 mins)
W
Scale 1
Unsigned Unit: %, Range: 15% to 80%, Value x 1 (e.g. 20% = 20)
W
Scale 1
Unsigned Unit: %, Range: 0% to BO7closepos-4%, Value x 1 (e.g. 20% = 20)
W
Scale 1
Page | 16
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Protocol Register
Base
Index
Description
134
40135 Input contact of analog 1, 2, 3 and 4.
135
40136 Delay before activation of UI1 in seconds.
136
40137 Delay before activation of UI2 in seconds.
137
40138 Delay before activation of UI3 in seconds.
138
40139 Delay before activation of UI4 in seconds.
139
40140 Humidity control mode status.
140
40141 Humidity setpoint (%RH) in occupancy or day mode.
141
40142
Dehumidification setpoint (%RH) in unoccupied or night mode.
142
40143
Humidification setpoint (%RH) in unoccupied or night mode.
143
40144 Minimum user setpoint.
144
40145 Maximum user setpoint.
145
40146 Humidity proportional band.
146
40147 Humidity deadband.
147
40148 Internal humidity sensor offset correction. *
Not available on all models.
148
40149 External humidity sensor offset correction.
Data Type
Range
Bit String
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 10
Signed
Scale 10
B0: Analog input 1 0 = Normally Open, 1 = Normally Close
B1: Analog input 2 0 = Normally Open, 1 = Normally Close
B2: Analog input 3 0 = Normally Open, 1 = Normally Close
B3: Analog input 4 0 = Normally Open, 1 = Normally Close
Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs = 20)
Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs = 20)
Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs = 20) Unit: Seconds, Range: 0 to 3600 seconds, Value/1 (e.g. 20 secs =20) 1 = Auto, 2 = Dehumidification, 3 = Humidification, 4 = Off Unit: %RH, Limited by min/max humidity setpoint, Value x 10 (e.g. 20%RH = 200)
Unit: %RH, Range: 10%RH to 65%RH, Value x 10 (e.g. 20%RH = 200)
Unit: %RH, Range: 10%RH to 65%RH, Value x 10 (e.g. 20%RH = 200)
Unit: %RH, Range: 10%RH to max, Value x 10 (e.g. 20%RH = 200)
Unit: %RH, Range: min to 90%RH, Value x 10 (e.g. 20%RH = 200)
Unit: %RH, Range: 3%RH to 10%RH, Value x 10 (e.g. 4%RH = 40)
Unit: %RH, Range: 0%RH to 5%RH, Value x 10 (e.g. 4%RH = 40)
Unit: %RH, Range: ± 5%RH, Value x 10 (e.g. 2%RH = 20)
Unit: %RH, Range: ± 5%RH, Value x 10 (e.g. 2%RH = 20)
Writable
W
W W W W W W W W W W W W W W
www.neptronic.com
Page | 17
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Protocol Register
Base
Index
Description
149
40150 Pressure sensor value in Pascals.
150
40151 Maximum pressure value range.
151
40152 Actual VFD pressure loop x 10 (%).
152
40153 VFD pressure loop setpoint.
153
40154 VFD pressure loop deadband.
154
40155 VFD pressure loop proportional band.
155
40156 VFD pressure loop integral time.
156
40157 Actual VFD temperature loop while cooling x 10 (%).
157
40158 Actual VFD temperature loop while heating x 10 (%).
158
40159 VFD temperature loop setpoint x 10 (ºC or ºF).
159
40160 VFD temperature loop deadband x 10 (ºC or ºF).
160
40161
VFD temperature loop proportional band x 10 (ºC or ºF).
161
40162 VFD temperature loop integral time.
162
40163 Voltage required for closing the 6-way valve.
163
40164
Minimum output voltage required for cooling for the 6way valve.
164
40165
Minimum output voltage required for heating for the 6-way valve.
165
40166 6-way valve size selection in inches.
166
40167 Signal type for Analog output 1.
Data Type
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 1
Unsigned
Scale 10
Unsigned
Scale 10
Signed
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 1
Unsigned
Scale 100
Unsigned
Scale 100
Unsigned
Scale 100
Unsigned Unsigned
Range
Unit: Pascals, Range: 100 to Register Maximum pressure value range [40135],
Value/1 (e.g. 200Pa = 200) Unit: Pascals, Range: 200 to 20000, Value/1 (e.g.
200Pa = 200)
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: Pascals, Range:
100 to Register Maximum pressure value range [40135], Value/1 (e.g. 200Pa =
200) Unit: Pascals, Range: 0 to 100, Value x 1 (e.g. 20Pa = 20)
Unit: Pascals, Range: 100 to 500, Value x 1 (e.g. 250Pa = 250)
Unit: Seconds, Range: 0 to 250 seconds, Value x 1 (e.g. 50 secs = 50)
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20)
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: depends on system
unit, Range: 10ºC to 40ºC or 50ºF to 104ºF, Value x 10 (e.g. 30°C = 300 or
60ºF = 600) Unit: depends on system unit, Range: 0ºC to 5ºC or 0ºF to 9ºF,
Value x 10 (e.g. 2°C = 20 or 4ºF = 40) Unit: depends on system unit, Range:
0.5ºC to 5ºC or 1ºF to 9ºF, Value x 10 (e.g. 2°C= 20 or 4ºF = 40) Unit:
Seconds, Range: 0 to 250 seconds, Value x 1 (e.g. 50 secs = 50)
Unit: V, Range: 0 to 11 V, Value x 100 (e.g. 2V = 200)
Unit: V, Range: 0 to 11 V, Value x 100 (e.g. 2V = 200)
Unit: V, Range: 0 to 11 V, Value x 100 (e.g. 2V = 200) 1 = 1/2, 2 = 3/4, 3 = 1
1 = Analog, 2 = On-Off, 3 = Pulsing
Writable
RO W RO W W W W RO RO W W W W W W W W W
www.neptronic.com
Page | 18
Protocol Register
Base
Index
Description
167
40168 Signal type for Analog output 2.
168
40169 Signal type for Analog output 3.
169
40170 Signal type for Analog output 4.
170
40171 Signal type for Binary output 1.
171
40172 Signal type for Binary output 2.
172
40173 Signal type for Binary output 3.
173
40174 Signal type for Binary output 4.
174
40175 Signal type for Binary output 5.
175
40176 Signal type for Binary output 6.
176
40177 Signal type for Binary output 7.
177
40178 PIR Relay sensor.
178
40179 Floating output motor timing for BO1/BO2.
179
40180 Floating output motor timing for BO3/BO7.
180
40181 Reserved
181
40182 Floating output value for BO1/BO2.
182
40183 Floating output value for BO3/BO7.
183
40184 Reserved
184
40185 Value for Pulse output 1.
185
40186 Value for Pulse output 2.
186
40187 Value for Pulse output 3.
187
40188 Value for Pulse output 4.
188
40189 Value for Pulse output 5.
189
40190 Value for Pulse output 6.
www.neptronic.com
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned Unsigned
Unsigned Unsigned Unsigned Unsigned
Scale 1
Unsigned
Scale 1
1 = Analog, 2 = On-Off, 3 = Pulsing 1 = Analog, 2 = On-Off, 3 = Pulsing 1 =
Analog, 2 = On-Off, 3 = Pulsing 1 = Pulsing, 2 = On-Off, 3 = Floating 1 =
Pulsing, 2 = On-Off 1 = Pulsing, 2 = On-Off, 3 = Floating 1 = Pulsing, 2 = On-
Off 1 = Pulsing, 2 = On-Off 1 = Pulsing, 2 = On-Off 1 = Pulsing, 2 = On-Off 0
= Relay was not activated, 1 = Relay was activated
Unit: Seconds, Range: 15 to 250 seconds, Value x 1 (e.g. 20 secs = 20)
Unit: Seconds, Range: 15 to 250 seconds, Value x 1 (e.g. 20 secs = 20)
Unsigned
Scale 10
Unsigned
Scale 10
Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20)
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unsigned
Scale 10
Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 1 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20) Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20)
Writable W W W W W W W W W W W W W
W W
W W W W W W
Page | 19
Protocol Register
Base
Index
Description
190
40191 Value for Pulse output 7.
191
40192 Delta temperature between inlet and outlet.
192
40193 Delta temperature set point.
193
194 195 196 197 to 198 199
200
201
40194 Light intensity sensor value.
40195 Light intensity sensor maximum range.
40196 Reserved
40197 VOC sensor value.
40198 to 40199
Reserved
40200 User backlight or contrast intensity.
40201 Occupancy backlight or contrast intensity.
40202 Unoccupancy backlight or contrast intensity.
Universal Wall-Mount Controller
Modbus Communication Module User Guide
Data Type
Range
Unsigned
Scale 10
Signed
Scale 100
Signed
Scale 100
Unsigned
Scale 1
Unsigned
Scale 1
Unit: %, Range: 0% to 100%, Value x 10 (e.g. 2% = 20)
Unit: depends on system unit, Range: -12°C to 12°C or 10.4°F to 53.6°F Value x
100 (e.g. 8°C = 800 or 6ºF = 600) Unit: depends on system unit, Range: -12°C
to 12°C or 10.4°F to 53.6°F Value x 100 (e.g. 8°C = 800 or 6ºF = 600) Unit:
Luxes, Range: 0 to 16000 Luxes, Value x 1 (e.g. 20 Luxes = 20)
Unit: Luxes, Range: 1000 to 16000 Luxes, Value x 1 (e.g. 20 Luxes = 20)
Unsigned
Scale 1
Unit: PPB, Range: 0 to 30000 PPB, Value x 1 (e.g. 20 PPB= 20)
Writable W W W RO W
RO
Unsigned Unit: %, Range: 0% to 100%, Value x 1 (e.g. 30% = 30)
W
Scale 1
Unsigned Unit: %, Range: 0% to 100%, Value x 1 (e.g. 30% = 30)
W
Scale 1
Unsigned Unit: %, Range: 0% to 100%, Value x 1 (e.g. 30% = 30)
W
Scale 1
www.neptronic.com
Page | 20
Notes
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada neptronic.com
Toll free in North America:
1-800-361-2308 Tel.:
514-333-1433 Fax:
514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)
References
- Neptronic | Home - Humidifier Distributor & HVAC Products
- Neptronic | Home - Humidifier Distributor & HVAC Products
- Neptronic | Home - Humidifier Distributor & HVAC Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>