ACIQ 24-EHPB Series Next Gen Heat Pump System User Guide
- September 10, 2024
- ACiQ
Table of Contents
- 24-EHPB Series Next Gen Heat Pump System
- Specifications
- Product Usage Instructions
- Connecting the Thermostat
- Proper Communication Setup
- Photo Examples
- Q: What type of wire should I use for communication between
- Q: Why is grounding the shielded wire important?
- Q: How far should I keep the communication wire from line
24-EHPB Series Next Gen Heat Pump System
“`html
Specifications
- Model: ACiQ Next Gen Ducted Heat Pump System
- Available Models: ACiQ-24, ACiQ-36, ACiQ-48, ACiQ-60
- Features: Variable speed, inverter-driven heat pump condenser,
smart air handler with variable speed blower
Product Usage Instructions
Connecting the Thermostat
To connect the thermostat to your ACiQ system, follow these
steps:
-
Refer to the installation manual for detailed
instructions. -
Identify the type of thermostat you have (communicating
controller, 24V thermostat, or 3rd party 24V thermostat). -
Based on your thermostat type, follow the wiring diagrams
provided in the manual to make the proper connections between the
indoor and outdoor units. -
Ensure that the communication wire used is 18/2 AWG shielded
cable and grounded at only one end. -
Insert a battery into the thermostat to ensure it turns
on.
Proper Communication Setup
For efficient communication between units, follow these
guidelines:
-
Use the specified communication wire to avoid errors.
-
Ground the shielded wire at only one end to prevent
communication errors. -
Keep the communication wire at least 18 inches away from any
line voltage wires. -
Run the communication wire perpendicular to power lines, not
along with them, for optimal performance.
Photo Examples
Refer to the photos in the manual for visual guidance on proper
installation and wiring setup.
FAQ
Q: What type of wire should I use for communication between
units?
A: Use 18/2 AWG shielded cable for communication. Using the
specified wire is crucial to avoid communication errors.
Q: Why is grounding the shielded wire important?
A: Grounding the shield at only one end prevents communication
errors. Do not ground the shield at both ends.
Q: How far should I keep the communication wire from line
voltage wires?
A: The communication wire should be run a minimum of 18 inches
away from any line voltage wires to prevent communication
errors.
“`
2024 V1
Quick Start Guide
ACiQ Next Gen Ducted Heat Pump System
ACiQ-24-AHB/ACiQ-24-HPB ACiQ-36-AHB/ACiQ-36-HPC ACiQ-48-AHB/ACiQ-48-HPB ACiQ-60-AHB/ACiQ-60-HPB
ACiQ-24-AHB/ACiQ-24-EHPB ACiQ-36-AHB/ACiQ-36-EHPB ACiQ-48-AHB/ACiQ-48-EHPB ACiQ-60-AHB/ACiQ-60-EHPB
Thank you for purchasing a Next Gen Heat Pump system from ACiQ! This system
gives you the benefits of a variable speed, inverter driven heat pump
condenser, combined with a smart air handler with a variable speed blower.
This Quick Start Guide covers how to connect the thermostat to your system and
ensure proper communication. It is not meant to replace the entire
installation manual. Please reference install manual for in depth
instructions.
ACiQTM Wiring Diagrams and Connections
The wiring diagrams below and on the following pages show the proper wiring and DIP switch settings (for indoor and outdoor units) depending upon your application and the type of thermostat used (standard wired controller or 24V thermostat).
SCENARIO
CONTROLLER
SCENARIO 1 (RECOMMENDED)
ACIQ COMMUNICATING CONTROLLER (STANDARD)
INDOOR UNIT
AIR HANDLER
CONNECTION BETWEEN INDOOR &
OUTDOOR UNITS
RS485: S1/S2
OUTDOOR UNIT
AHU DIP SWITCH
SW1-1
SW1-4
ODU DIP SWITCH
S1-2
STANDARD OUTDOOR UNIT
OFF (Default)
OFF (Default)
OFF (Default)
SCENARIO 2
ACIQ T755 24V THERMOSTAT
AIR HANDLER
RS485: S1/S2
STANDARD OUTDOOR UNIT
ON
OFF (Default)
OFF (Default)
SCENARIO 3
3RD PARTY 24V THERMOSTAT
AIR HANDLER
24V: R/C/B/Y1/Y2/G/W
STANDARD OUTDOOR UNIT
ON
ON
ON
WARNING In ALL wiring scenarios, be sure to turn off the circuit breaker and pull the disconnect before wiring. Incorrect wiring can cause an electrical short and destroy the main circuits boards!
SCENARIO 1: INCLUDED RS485 COMMUNICATING CONTROLLER THERMOSTAT
(Standard and Recommended Installation)
Please note that using the provided communicating thermostat will provide
maximum efficiency. But when using this thermostat the unit will prioritize
efficiency over comfort. The system will maintain a comfortable temperature
but may run longer than some people desire. For conventional control over the
unit see option #2.
ACIQ COMMUNICATING CONTROLLER
INDOOR AHU
OUTDOOR ODU
HA / HB
Interchangeable with optional 20 ft long 4-wire communicating harness. Connects to the S-485 port.
NON-POLARITY RS485 COMMUNICATION
S1 / S2
18/2 AWG shielded wire must be used & grounded on ONLY one side
Gen2 Outdoor Board: Note the cover on BOTH rows of terminal screws. Lift the
covers to access the screws.
ACiQTM Wiring Diagrams and Connections
SCENARIO 1 Continued: INCLUDED RS485 COMMUNICATING CONTROLLER THERMOSTAT
(Standard and Recommended Installation)
IMPORTANT NOTES
Communication wire connected to S1 & S2 MUST be 18/2 AWG shielded cable.
Failure to use specified wire can result in communication errors.
The shielded ground must be grounded at one end ONLY. DO NOT ground the shield
at both ends. Failure to follow this procedure can result in communication
errors.
Communication wire must be run a minimum of 18″ away from any line voltage
wires. Failure to follow this procedure can result in communication errors.
Always try to run the communication wire perpendicular to power lines and NOT
along with them.
Ensure battery is inserted in the thermostat and wiring is connected. Without
battery, the thermostat will not turn on.
Photo Examples
Indoor Air Handler Circuit Boards
Data Transfer Board
Main Board (Side Facing)
ACIQ Provided Thermostat
Ensure battery is inserted here. Without battery thermostat will not turn on.
HA & HB wiring terminals
ENC2 Aux Heat
Lockout S3
ENC2 Compressor
Lockout
S4
SW1
SW2 SW3 HA / HB SW4 S-485
18/2 Shielded Cable
Shield Ground Gen1 Outdoor Board (Discontinued)
Gen2 Outdoor Unit Circuit Board
Terminal Block (Left)
Communication Board (Right)
Upper terminal screws shown Lower terminal screws under the label
Terminal screws under the labels
Common Wiring Connections, Continued
SCENARIO 2: OPTIONAL 24v ACIQ (T755) THERMOSTAT
This option shows how to wire the 24 volt ACiQ thermostat to the air handler.
This method prioritizes comfort over efficiency. Please note for this method
to work DIP switch SW1-1 needs to be turned ON. This method also uses S1 & S2
to communicate between the air handler and the condenser (no 24 volt wire is
run outside) only 18/2 shielded wire is run outside. For additional thermostat
wiring options, see page 5.
24v THERMOSTAT ACIQ T755
INDOOR AHU
OUTDOOR ODU
24v S1 / S2
NON-POLARITY RS485 COMMUNICATION
Verify outdoor unit is receiving 208/240 volts to L1 & L2 as well. L1 & L2 are on a separate terminal block.
IMPORTANT!
24 Volts AC must NEVER be connected to S1 & S2. Doing so will cause
irreversible damage to the outdoor communication board.
Common Wiring Connections, Continued
SCENARIO 3: OPTIONAL THIRD-PARTY 24v THERMOSTAT (ECOBEE, NEST, ETC)
This option shows how to wire any 24 volt thermostat to the air handler
without communication. This method also prioritizes comfort over efficiency.
Please note for this method to work DIP switch SW1-1 needs to be turned ON.
This method also uses 24v wiring to communicate between the air handler and
the condenser using regular thermostat cable. For thermostat wiring options,
see page 6.
24v THERMOSTAT
INDOOR AHU
OUTDOOR ODU
24v
XX
X
X
24v
24V NON-COMMUNICATING
IMPORTANT!
24 Volts AC must NEVER be connected to S1 & S2. Doing so will cause
irreversible damage to the outdoor communication board.
Wiring Diagrams and Connections Without Communication
Scenario 3 24v Connection Method C (36k to 60k Units Only): The following
wiring diagrams are suitable for the AHU and outdoor condenser when used ith a
24v thermostat without communication.
NOTE: This equipment uses B functionality. The terminal is energized for
heating functionality. Please ensure thermostat is setup for B functionality.
Air Handler DIP Switch Guide
2023 V1.2
Function Settings
Thermostat Wiring Method
SW1-1
OFF
RS-485 Communication. Used For ACiQ Communicating Thermostat.
ON
Used For 24 Volt Thermostats.
Cold Air Prevention – Defrost
SW1-2
OFF
Cold Air Prevention Activated – Fan Stops
ON
No Cold Air Prevention – Fan Continues To Operate
System Type
SW1-3
OFF
Heat Pump
ON
Cooling Only
Indoor & Outdoor Unit Wiring Method
SW1-4
OFF
S1 & S2 (DC Communication / Only Applies To ACiQ Condenser)
ON
24 Volt Wires (No True Communication / Applies To All Condensers)
Default AHU DIP Switch Settings Shown Below
SW2-1
OFF
ON
SW2-2
OFF
ON
SW2-3
OFF
ON
SW2-4
OFF
ON
Heat Settings Auxiliary Heat Activation Differential
4 °F Gap Between T1 & Ts Sensors 2 °F Gap Between T1 & Ts Sensors Auxiliary
Heat Activation Delay
None Yes Auxiliary Heat Activation Delay Time 15 Minute Delay (For Electric
Heat) 30 Minute Delay (For Electric Heat) Heat Source Lock Outs In This
Position Electric Heat Lockout Can Be Set Via ENC2 In This Position Compressor
Lockout Can Be Set Via ENC2
Delay between 1st stage & 2nd stage electric heat is time based, not
temperature based.
T1 Sensor = Return Air Temp (Room Temp), Ts = Set point
SW2-3 only works if SW2-2 is turned ON.
This sets maximum temperature, anything over this setting locks out. This sets
minimum temperature, anything under this setting locks out.
ENC2 Dial Referenced In SW2-4. 16 Digits To Select From (0-9, A-F). Lock Out
Range = -4 S3 °F to 46 °F. 0 = No Lock Out, 1 = -4 °F Lock Out, F = 46 °F Lock
Out. Each Digit Increases
Temperature By 3.6 °F. Chart Provides Temperature Rounded To Nearest Whole
Number.
1 = -4 °F 2 = 0 °F 3 = 3 °F 4 = 7 °F
5 = 10 °F 6 = 14 °F 7 = 18 °F 8 = 21 °F
9 = 25 °F D = 39 °F A = 28 °F E = 43 °F B = 32 °F F = 46 °F C = 37 °F
SW3-1
OFF
ON
SW3-2
OFF
ON
SW3-3
OFF
ON
Heat Settings Cont. Ramping Up Algorithm Delay
1.5 Hours (Efficiency) 0.5 Hours (Comfort) Y/Y2 Temperature Differential
Adjustment
3.6 °F (Efficiency) 1.8 °F (Comfort) W2 Temperature Differential Activation 6
°F (Efficiency) 4 °F (Comfort)
This sets the maximum continuous runtime allowed before the system
automatically stages up capacity. Only applies if 24 volt
thermostat is being used.
If using 24 volt thermostat this sets compressor speed instead. ON = slower,
OFF = Faster.
This DIP switch only works if using the provided communicating ACiQ
thermostat. Otherwise delay is time based.
Electric Heat Nominal CFM Adjustment
SW4
Available settings are 000/001/010/011. Each digit corresponds with an
individual switch position.
OFF = 0, ON = 1. For example [SW4-1 OFF, SW4-2 ON, SW4 -3 OFF] = 010
S4-1
OFF
ON
S4-2
OFF
ON
Heat Settings Cont. Aux Heat Control W1 & W2 Controlled Separately W1 & W2 Not
Controlled Separately
Dehumidify Control DH Terminal Available To Be Used DH Terminal Deactivated
General Notes If selected 24 volt thermostat has an E/AUX option and it is
used
to activate heat, all delays will be bypassed.
When auxiliary heat is energized the fan will run in Turbo Mode.
IMPORTANT: In order for changes to take effect power must be OFF BEFORE DIP switch changes.
Default setting is OFF except S4.
Please note if using the provided ACiQ thermostat DIP Switch Settings will not
need to be adjusted. DIP Switch settings should only be adjusted by a
professional HVAC service technician. Please note in this quick start guide
the specific DIP Switches that need adjusted will be shown to ensure accurate
operation for the chosen set up. For Option 1 nothing needs to be done. For
Option 2 please refer to the DIP Switch diagram that shows the correct
position of the DIP Switches.