kopp PRCD-S pro Mobile Personal Protection Devices Instruction Manual

August 25, 2024
Kopp

kopp PRCD-S pro Mobile Personal Protection Devices

Specifications

  • Product Name: PRCD-S pro / PRCD-S / PRCD-K / PRCD
  • Type: Mobile personal protection devices
  • Rated Voltage: 230 VAC, 50 Hz
  • Rated Current: Not specified in the provided text
  • Switching Power: Not specified in the provided text
  • Fault Current Type: Not specified in the provided text

Product Usage Instructions

Regulations and Safety Recommendations
Ensure to comply with accident prevention regulations and recommendations provided in the manual for safe current consumption.

Functions and Features
The product offers various functions, including detection of smooth DC residual currents, self-monitoring, fault-free switching with gloves, and undervoltage release.

PRCD-S Pro
The latest generation mobile residual current protective device that detects smooth DC residual currents over 6 mA reliably. It allows fault-free switching with gloves and triggers switching off electrical consumers in case of undervoltage.

PRCD-S
A cost-effective alternative to PRCD-S pro, proven through years of use. Available in various configurations for construction and installation sites.

PRCD-K:
Designed for specialized use.

PRCD at a Glance

  • Operation on: Outlet / building wiring
  • Based on: DIN VDE 0661, DIN 14660, DGUV Information 203-006
  • Number of Poles: Not specified in the provided text

FAQ

  • Q: What is the main function of the PRCD-S pro?
    A: The main function of the PRCD-S pro is to detect smooth DC residual currents over 6 mA reliably and provide fault-free switching even with gloves.

  • Q: How does the PRCD-S ensure safety during operation?
    A: The PRCD-S triggers switching off electrical consumers in case of undervoltage, ensuring safety during operation.

Heinrich Kopp GmbH – a leading producer of electrical installation materials.
With the development and production of mobile personal protection devices, innovative smart home solutions and a broad range of switch programmes with high design standards, Kopp offers a large product portfolio for electrical installations in the specialist trade and DIY sector. A large share of our products are manufactured at our own production facility in Germany. In addition, the company manufactures customised solutions for industrial customers. Kopp is part of the strong Alfanar Group, an internationally active group with a high level of expertise in the area of electrical engineering.

Regulations

Accident prevention regulations describe the technical prerequisites to be applied and give recommendations in order to ensure safe current consumption from existing connection points at installation and operation sites.

Based on DGUV information 203-006, it is required to use e.g. a mobile residual current protective device (pursuant to DIN VDE 0661), which fulfills the following functions, when connecting electrical equipment to external outlets:

  • Rated differential current IΔn ≤ 30 mA
  • Switches all poles, including the protective conductor
  • Undervoltage release
  • No automatic restart after the voltage returns

As well as the following functions:

  • Must be impossible to switch on if the protective conductor is interrupted or energized
  • Must switch off if voltage is detected on the protective conductor or if the protective conductor is interrupted during operation
  • Must not switch off the protective conductor if external voltage is detected on the protective conductor.

DGUV regulation 49 and GUV-I 8651 describe tools and protective measures used for firefighting.
The generators of the fire department should be primarily used. In order to increase the level of protection, we recommend employing additional protective measures, such as a mobile residual current protective device.
If a different connection point is necessary in exceptional cases, it may only be connected by means of a safety switch (differential current protective device with residual current, protective conductor breakage, protective conductor voltage, and external voltage monitoring).

PRCD-S pro: Latest generation mobile residual current protective device

In addition to the characteristics required in DGUV information 203-006, the PRCD-S pro offers:

  • It can only be switched on when the resistance of the protective conductor is < 1 kΩ

  • Detection of smooth DC residual currents > 6 mA*

  • Fault-free switching even with gloves

  • Clear display of the device status and possible errors by means of integrated LEDs

  • (depending on device type)

Detection of smooth DC residual currents

Electrical consumers and equipment could create smooth DC residual currents. If these are then connected to a circuit with a type A residual current- operated circuit breaker, these smooth DC residual currents can lead to a malfunction of the residual current-operated circuit breaker.
PRCD-S pro detects smooth DC residual currents > 6 mA reliably! *

PRCD-S pro

Self-monitoring device

  • Function test of the residual current circuit every time the device is connected to the outlet and every 2 operating hours
  • Relay point test every time the device is switched on/off
  • Monitoring of the resistance of the protective conductor
  • Status of devive and error signalling by LED

Fault-free switching with gloves
Thanks to the latest electronics, the PRCD-S pro does not care whether or not a user wears gloves or not. It is always possible to switch the device on without a fault under any and all operating conditions. Even with gloves.

Undervoltage release
If the voltage decreases during operation, the device triggers switching off the electrical consumers. The device does not switch on again automatically. It is necessary to switch it on again manually.

PRCD-S: Proven through years of use

Compared to PRCD-S pro, PRCD-S is an cost-effective alternative mobile protective device for construction and installation sites.

PRCD-S is available in various configurations:

  • Intermediate device for the user’s wiring with degrees of protection IP55 and IP68
  • Extension with safety plug and safety connector
  • Integrated in cable drum

PRCD-K: For specialized use
DGUV information 203-032 requires suitable protective measures before connecting two or more electrical devices to a generator. PRCD-K meets these requirements and serves to increase the level of protection.

PRCD at a glance

__Operation on| PRCD-S pro PRCD-S
---|---
Outlet / building wiring| Outlet / building wiring
Based on|

  • DIN VDE 0661
  • DIN 14660
  • DGUV Information 203-006

|

  • DIN VDE 0661
  • DGUV Information 203-006

Number of poles| 3| 3
Rated voltage| 230 VAC, 50 Hz|

  • 110 VAC, 60 Hz
  • 230 VAC, 50 Hz
  • Depending upon version

Rated current| 16 A| 230 VAC, 50 Hz
Switching power| 3 600 W| je nach Ausführung
Type of residual current| A + Detection of smooth DC residual currents

Depending upon version

| A
Rated residual current|

  • 10 mA
  • 30 mA
  • 30 mA + 6 mA DC
  • Depending upon version

|

  • 10 mA
  • 30 mA
  • Depending upon version

Switching technology| Relay| Mechanical
Degree of protection| IP44 IP55

Depending upon version

| IP44 IP55 IP68

Depending upon version

Temperature range for operation| -25 … +45 °C| -25 … +45 °C
Undervoltage release| |
PE-detection| |
Self-monitoring device (switching contacts, residual current circuit)| | (only manually with test button)
Determination of PE quality ( < 1 kΩ)|
|
Detection of smooth DC residual currents| Depending upon version|

Fault-free switching with gloves| |

Increase in protection level for generators and when using submersible pumps| Outlet / building wiring, and generators, primarily in Germany| Outlet / building wiring, and generators, primarily outside of Germany
---|---|---
DIN VDE 0661

DGUV Information 203-032

| DIN VDE 0661

DGUV Information 203-032

| DIN VDE 0661

DGUV Information 203-032

3| 3| 2
230 VAC, 50 Hz| 230 VAC, 50 Hz| 230 VAC, 50 Hz
16 A| 16 A| 16 A
3 600 W| 3 600 W| 3 600 W
A| A| A
30 mA| 30 mA| 30 mA
Mechanisch

Mechanical

| Mechanisch

Mechanical

| Mechanisch

Mechanical

IP55 IP68

Je nach Ausführung

Depending upon version

| IP55| IP55
-25 … +45 °C| -25 … +45 °C| -25 … +45 °C
| |
| |
(only manually with test button)| (only manually with test button)| (only manually with test button)
| |
| | _
(not applicable)| (not applicable)                      (not applicable)_

Behaviour in case of failure

Cannot be switched on.

With breakage during operation: Interruption of L, N, and PE.

| Cannot be switched on.

With breakage during operation: Interruption of L, N, and PE.

| Cannot be switched on.

With breakage during operation: Interruption of L and N.

| !| Can be switched on. Secondary accidents possible.
---|---|---|---|---
!| Can be switched on. Secondary accidents possible.| !| Can be switched on. Secondary accidents possible.| !| Can be switched on. Secondary accidents possible.| !| Can be switched on. Secondary accidents possible.
Cannot be switched on.

With breakage during operation: Interruption of L, N, and PE.

| Cannot be switched on.
With breakage during operation: Interruption of L, N, and PE.| Cannot be switched on. With breakage during operation: Interruption of L and N.| Can be switched on. Mortal danger!
Cannot be switched on.| Cannot be switched on.| |
| | Cannot be switched on. Mortal danger!| Can be switched on. Mortal danger!
Cannot be switched on.

With breakage during operation: Interruption of L, N, and PE.

| Cannot be switched on.

With breakage during operation: Interruption of L, N, and PE.

| Cannot be switched on.

With breakage during operation: Interruption of L and N.

| Can be switched on. Function not affected.
Interruption of L and N, PE.| Interruption of L and N, PE.| Interruption of L and N.| Interruption of L and N.
!| | !| Can be switched on. Secondary accidents possible.| |
| | |
| Can be switched on.| Can be switched on.| Can be switched on.
| Secondary accidents possible.| Mortal danger!| Mortal danger!
| | |
Consumer is energized. Mortal danger!| Consumer is energized. Mortal danger!| No interruption.

RCD (MCB) of the external circuit triggers.

| No interruption.

RCD (MCB) of the external circuit triggers.

| | |
Can be switched on. Function not affected.| Can be switched on. Function not affected.| Can be switched on. Function not affected.| Can be switched on. Function not affected.

PRCD-S pro

PRCD-S

PRCD-K


PRCD-2P / PRCD-3P

Periodic inspection

The mobile protective devices (PRCD-S pro, PRCD-S, PRCD-K, etc.) must be subjected to routine periodic inspections. DIN VDE 0701 and DIN VDE 0702 describe the procedure and DGUV 203-006 describes the inspection periods to be followed, among other things. Measuring instrument manufacturers offer suitable measuring instruments for mobile protective devices.
On its homepage, Heinrich Kopp GmbH provides an information sheet for periodic inspection that can be downloaded for each device type.

More information: www.kopp.eu

Heinrich Kopp GmbH
Alzenauer Straße 68
63796 Kahl/Main
DEUTSCHLAND
Tel.: +49 6188 40-0
Fax: +49 6188 40-369
E-Mail: info@kopp.eu
www.kopp.eu

Clever sein.
Kopp einschalten.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals