THORN 96403687z02 Champion LED Installation Guide
- August 21, 2024
- THORN
Table of Contents
THORN 96403687z02 Champion LED
Product Specifications
- Type: Champion LED
- Class: I
- Length max: 200m
- Electrical Connections: DALI, RDM-DMX
- Recommended Cable: HO7RNF 5G 1.5mm2
- Voltage Input Range: 200-440Vac
Product Usage Instructions
-
Positioning and Installation
The luminaire with clear optic should be positioned at a distance of 3m to avoid prolonged staring into the luminaire. Secure the product with a retaining cable attached to the fork using the specified mounting hardware (1xM20 or 2xM14 with extra large washer, not provided). -
Electrical Connection – DALI
Connect the electrical cables according to the specified pinout for DALI connections. Ensure proper grounding and make sure to follow the recommended cable type for DALI connections. -
Electrical Connection – RDM-DMX
For RDM-DMX connections, follow the pinout and wiring instructions provided in the manual. Observe the signaling LED indications on the gear box to monitor faults and status. -
Gear Box Mounting
Mount the gear box horizontally or vertically as recommended, avoiding forbidden positions. Follow the drilling recommendations for secure mounting of the gear box.
Frequently Asked Questions (FAQ)
-
Q: What should I do if the luminaire is not turning on?
A: Check the electrical connections, ensure proper grounding, and verify power input according to specifications. -
Q: How can I troubleshoot signaling LED indications?
A: Refer to the fault description table in the manual to identify and address any reported issues based on the pulse signals. -
Q: Can I extend the cable length beyond 200m?
A: It is not recommended to exceed the maximum cable length specified to maintain optimal performance and safety.
CHAMPION LED
Installation instructions
GEAR BOX 264L / 200-440Vac models
V in
Nominal
| Inrush Current Data| # Drivers for each Circuit Breaker
---|---|---
I peak
(A)
| Half Value Time (µs)| Type B
10A
| Type B
16A
| Type B 20A| Type B 25A| Type C 10A| Type C 16A| Type C
20A
| Type C
25A
| Type D
10A
| Type D
16A
| Type D 20A| Type D 25A
230Vac| 29| 2000| 1| 1| 2| 2| 1| 2| 3| 4| 1| 2| 3| 4
400Vac| 50| 2000| 0| 1| 1| 1| 1| 1| 2| 3| 2| 3| 4| 5
V in
Nominal
| Inrush Current Data| # Drivers for each Circuit Breaker
---|---|---
I peak
(A)
| Half Value Time (µs)| Type B 32A| Type B
40A
| Type B
50A
| Type B
63A
| Type C
32A
| Type C 40A| Type C 50A| Type C 63A| Type D 32A| Type D
40A
| Type D
50A
| Type D
63A
230Vac| 29| 2000| 4| 6| 7| 9| 5| 6| 8| 10| 5| 6| 8| 10
400Vac| 50| 2000| 2| 3| 4| 5| 5| 7| 9| 11| 8| 10| 13| 17
- Replace any cracked protective shield.
- Class II luminaires must be installed so that exposed metal work of the luminaire is not in contact with any part of the electrical installation connected to a protective conductor.
WARNING: Class I luminaires must be earthed.
- This luminaire operates at mains voltage which must be switched off before intervention in control gear.
- Any modification to this luminaire is forbidden.
- Lighted objects nearer than the minimal distance in the is forbidden.
Thorn Lighting is constantly developing and improving its products. The right
is reserved to change specifications without prior notification or public
announcement.