LARKIN LK-LVCM Low Velocity Center Mount Evaporator User Guide

August 19, 2024
LARKIN

LOW VELOCITY
CENTER MOUNT EVAPORATOR
Technical Guide
Including models meeting DOE minimum AWEF

LOW VELOCITY CENTER MOUNT EVAPORATORS

FEATURES & BENEFITS

CABINET
■ Low height makes it ideal for low ceiling coolers – all models are only 14.5 inches tall, allowing for maximum headroom and more product storage
■ Air moves across the ceiling in both directions providing even air distribution throughout the cooler
■ Unit designed to be mounted flush against the ceiling or suspended on rods
■ Heavy-gauge grained aluminum cabinet cleans easily and looks attractive
■ Cabinet design features improved access panels on each end for easy access to electrical and refrigerationcomponents
■ Captive stainless steel screws for easy service which prevent dropping/loss and prevent rust streaks or staining
■ Improved wire management and routing
■ Quick disconnect, waterproof plug and receptacle for each motor in all models
■ Molded fan guard is made of strong, durable, NSF and UL Sanitation rated lightweight and damage resistant plastic material
■ Liquid line solenoid wire harness is factory-installed forquick installation

COIL
■ High-efficiency aluminum fins with full collars cover mechanically expanded copper tubes
■ Coils are dehydrated and sealed at the factory
■ Electric defrost models incorporate high quality tubular heaters and a standard fixed defrost termination thermostat
■ Generous coil surface gives proper compressor balance
■ Internally enhanced tubing and fin design for higher efficiency
■ Optimized heater placement with reduced heater wattages
■ Fixed defrost termination for electric

DRAIN PAN
■ Hinged drain pan for faster, easier and safer access and serviceability
■ Tapered mounting provides proper slope for condensate drainage to one end of the unit
■ Double drain pan eliminates drain pan sweating

MOTOR
■ Motor rail is design for maximum strength and durability
■ Motors are life lubricated and thermal overload protected
■ 2 Speed EC Motors are factory-installed

CONTROL OPTIONS
■ intelliGen™ Refrigeration Controller (iRC) units come with a factory mounted controller, tested and calibrated with an electronic expansion valve, pressure transducer, temperature sensors, control board and user interface. Standard features include Door Sensor, Product Load Input and Alarm Output.
■ Optional factory or field installable intelliGen Webserver Card (iWC) enables local and remote monitoring on any phone, tablet or PC.
■ Optional factory or field installable intelliGen Integration Card (iIC) enables connectivity to BACnet and Modbus.

OTHER OPTIONS
■ Units available with stainless steel housing and drain pan
■ Air defrost units are available with various coil coatings options

OUTSTANDING FEATURES

NOMENCLATURE

PREFERRED OPTION PACKAGES

(HFC Refrigerants)

Preferred Options Package Description
B0000 Standard Base

Standard Base + indicated options below
B0200| intelliGen™ Refrigeration Controller (R-404A/R-448A/R-449A)
B0201| intelliGen™ Refrigeration Controller (R-407A/C/F)

(CO2 DX)

Package| Description (standard base model features + indicated options below)
---|---
B0500
Standard Base| Danfoss EEV (120V) with 1/4”MPT Transducer Connection
(Pressure Transducer not included)
B0501| Danfoss EEV (120V) with 1/4”MPT Transducer Connection
(Pressure Transducer not included)  + Filter Drier
B0502| Sporlan EEV (120V) with 1/4”MPT Transducer Connection
(Pressure Transducer not included)
B0503| Danfoss EEV (120V) with Danfoss Pressure Transducer
B0504| Danfoss EEV (120V) with Danfoss Pressure Transducer + Filter Drier
B0505| Danfoss EEV (120V) with CPC Pressure Transducer
B0506| Danfoss EEV (120V) with CPC Pressure Transducer + Filter Drier
B0507| Sporlan EEV (120V) with Microthermo Pressure Transducer + Filter Drier

PERFORMANCE DATA

Application Capacity: Air Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF

| R-404A/R-507A| R-448A/R-449A|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0055S6AMA| LWA050| 5,000| 1,465| 5,500| 1,612| 1| 725| 1,232
LEV0080
S6AMA| LWA075| 7,500| 2,198| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125S6AMA| LWA100| 10,000| 2,930| 11,600| 3,399| 2| 1,450| 2,464
LEV0160
S6AMA| LWA130| 13,000| 3,809| 14,300| 4,190| 2| 1,450| 2,464
LEV0180S6AMA| LWA155‡| 15,500| 4,542| 17,360| 5,086| 3| 2,175| 3,695
LEV0215
S6AMA| LWA180| 18,000| 5,274| 20,880| 6,118| 3| 2,175| 3,695
LEV0245S6AMA| LWA210| 21,000| 6,153| 23,940| 7,014| 4| 2,900| 4,927
LEV0290
S6AMA| LWA270| 27,000| 7,911| 31,860| 9,335| 4| 2,900| 4,927
LEV0360*S6AMA| LWA340| 34,000| 9,962| 40,120| 11,755| 5| 3,625| 6,159

| R-407A/R-407F| R-407C|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0055S6AMA| LWA050| 5,500| 1,612| 5,500| 1,612| 1| 725| 1,232
LEV0080
S6AMA| LWA075| 8,400| 2,461| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125S6AMA| LWA100| 11,600| 3,399| 11,600| 3,399| 2| 1,450| 2,464
LEV0160
S6AMA| LWA130| 14,300| 4,190| 14,300| 4,190| 2| 1,450| 2,464
LEV0180S6AMA| LWA155‡| 17,360| 5,086| 17,360| 5,086| 3| 2,175| 3,695
LEV0215
S6AMA| LWA180| 20,880| 6,118| 20,880| 6,118| 3| 2,175| 3,695
LEV0245S6AMA| LWA210| 23,940| 7,014| 23,940| 7,014| 4| 2,900| 4,927
LEV0290
S6AMA| LWA270| 31,860| 9,335| 31,860| 9,335| 4| 2,900| 4,927
LEV0360*S6AMA| LWA340| 40,120| 11,755| 40,120| 11,755| 5| 3,625| 6,159

Notes:
1= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov

  • = Electrical Code Designator (see Nomenclature details)
    ‡ = Number of fans increases from 2 in legacy to 3 in new model
    Net Capacity is available upon request

Application Capacity: Air Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF

| CO 2 DX|
---|---|---
Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0055C6A^A| N/A| 5,500| 1,612| 1| 725| 1,232
LEV0080
C6A^A| N/A| 8,400| 2,462| 1| 725| 1,232
---|---|---|---|---|---|---
LEV0125C6A^A| N/A| 11,600| 3,400| 2| 1,450| 2,464
LEV0160
C6A^A| N/A| 14,300| 4,191| 2| 1,450| 2,464
LEV0180C6A^A| N/A| 17,360| 5,088| 3| 2,175| 3,695
LEV0215
C6A^A| N/A| 20,880| 6,119| 3| 2,175| 3,695
LEV0245C6A^A| N/A| 23,940| 7,016| 4| 2,900| 4,927
LEV0290
C6A^A| N/A| 31,860| 9,337| 4| 2,900| 4,927
LEV0360*C6A^A| N/A| 40,120| 11,758| 5| 3,625| 6,159

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov

  • = Electrical Code Designator (see Nomenclature details)
    ‡ = Number of fans increases from 2 in legacy to 3 in new model Net Capacity is available upon request
    ± = Refrigerant Designator (see Nomenclature details)

SPECIFICATIONS

Air Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF

New Model HP 2 Speed EC Motor
115/1/60 208-230/1/60
Amps Watts MCA

MOPD
LEV0055±6AMA| 1/20| 0.8| 55| 1.1| 20| 0.4| 55| 0.6| 15
LEV0080
±6AMA| 1/20| 0.8| 55| 1.1| 20| 0.4| 55| 0.6| 15
---|---|---|---|---|---|---|---|---|---
LEV0125±6AMA| 1/20| 1.7| 110| 2.0| 20| 0.8| 110| 1.1| 15
LEV0160
±6AMA| 1/20| 1.7| 110| 2.0| 20| 0.8| 110| 1.1| 15
LEV0180±6AMA| 1/20| 2.5| 165| 2.9| 20| 1.3| 165| 1.6| 15
LEV0215
±6AMA| 1/20| 2.5| 165| 2.9| 20| 1.3| 165| 1.6| 15
LEV0245±6AMA| 1/20| 3.4| 220| 3.8| 20| 1.7| 220| 2.1| 15
LEV0290
±6AMA| 1/20| 3.4| 220| 3.8| 20| 1.7| 220| 2.1| 15
LEV0360*±6AMA| 1/20| 4.2| 275| 4.7| 20| 2.1| 275| 2.6| 15

PERFORMANCE DATA
Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF

| R-404A/R-507A| R-448A/R-449A|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0055BS6EMA| LWEE050| 5,000| 1,465| 5,500| 1,612| 1| 725| 1,232
LEV0080BS6EMA| LWEE075| 7,500| 2,198| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125BS6EMA| LWEE100| 10,000| 2,930| 11,600| 3,399| 2| 1,450| 2,464
LEV0160BS6EMA| LWEE130| 13,000| 3,809| 14,300| 4,190| 2| 1,450| 2,464
LEV0180BS6EMA| LWEE155‡| 15,500| 4,542| 17,360| 5,086| 3| 2,175| 3,695
LEV0215BS6EMA| LWEE180| 18,000| 5,274| 20,880| 6,118| 3| 2,175| 3,695
LEV0245BS6EMA| LWEE210| 21,000| 6,153| 23,940| 7,014| 4| 2,900| 4,927
LEV0290BS6EMA| LWEE270| 27,000| 7,911| 31,860| 9,335| 4| 2,900| 4,927
LEV0360BS6EMA| LWEE340| 34,000| 9,962| 40,120| 11,755| 5| 3,625| 6,159
| R-407A/R-407F| R-407C|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0055BS6EMA| LWEE050| 5,500| 1,612| 5,500| 1,612| 1| 725| 1,232
LEV0080BS6EMA| LWEE075| 8,400| 2,461| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125BS6EMA| LWEE100| 11,600| 3,399| 11,600| 3,399| 2| 1,450| 2,464
LEV0160BS6EMA| LWEE130| 14,300| 4,190| 14,300| 4,190| 2| 1,450| 2,464
LEV0180BS6EMA| LWEE155‡| 17,360| 5,086| 17,360| 5,086| 3| 2,175| 3,695
LEV0215BS6EMA| LWEE180| 20,880| 6,118| 20,880| 6,118| 3| 2,175| 3,695
LEV0245BS6EMA| LWEE210| 23,940| 7,014| 23,940| 7,014| 4| 2,900| 4,927
LEV0290BS6EMA| LWEE270| 31,860| 9,335| 31,860| 9,335| 4| 2,900| 4,927
LEV0360BS6EMA| LWEE340| 40,120| 11,755| 40,120| 11,755| 5| 3,625| 6,159

Notes:
1= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov

  • = Electrical Code Designator (see Nomenclature details)
    ‡ = Number of fans increases from 2 in legacy to 3 in new model
    Net Capacity is available upon request

PERFORMANCE DATA
Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF

| CO 2 DX|
---|---|---
Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0055C6E^A| N/A| 5,500| 1,612| 1| 725| 1,232
LEV0080
C6E^A| N/A| 8,400| 2,462| 1| 725| 1,232
---|---|---|---|---|---|---
LEV0125C6E^A| N/A| 11,600| 3,400| 2| 1,450| 2,464
LEV0160
C6E^A| N/A| 14,300| 4,191| 2| 1,450| 2,464
LEV0180C6E^A| N/A| 17,360| 5,088| 3| 2,175| 3,695
LEV0215
C6E^A| N/A| 20,880| 6,119| 3| 2,175| 3,695
LEV0245C6E^A| N/A| 23,940| 7,016| 4| 2,900| 4,927
LEV0290
C6E^A| N/A| 31,860| 9,337| 4| 2,900| 4,927
LEV0360*C6E^A| N/A| 40,120| 11,758| 5| 3,625| 6,159

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov

  • = Electrical Code Designator (see Nomenclature details)
    ‡ = Number of fans increases from 2 in legacy to 3 in new model
    Net Capacity is available upon request
    ± = Refrigerant Designator (see Nomenclature details)

SPECIFICATIONS
Electric Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF

New Model|

HP

| 2 Speed EC Motor| Defrost Heaters
---|---|---|---
208-230/1/60
Amps| Watts| MCA| MOPD| Watts| Total Amps
LEV0055B±6EMA| 1/20| 0.4| 55| 0.6| 15| 1,600| 7.0
LEV0080B±6EMA| 1/20| 0.4| 55| 0.6| 15| 1,600| 7.0
---|---|---|---|---|---|---|---
LEV0125B±6EMA| 1/20| 0.8| 55| 1.1| 15| 2,800| 12.2
LEV0160B±6EMA| 1/20| 0.8| 110| 1.1| 15| 2,800| 12.2
LEV0180B±6EMA| 1/20| 1.3| 110| 1.1| 15| 4,000| 17.0
LEV0215B±6EMA| 1/20| 1.3| 165| 1.6| 15| 4,000| 17.4
LEV0245B±6EMA| 1/20| 1.7| 165| 2.1| 15| 5,200| 22.6
LEV0290B±6EMA| 1/20| 1.7| 220| 2.1| 15| 5,200| 22.6
LEV0360B±6EMA| 1/20| 2.1| 220| 2.6| 15| 7,000| 30.4

Notes:

  • = Electrical Code Designator (see Nomenclature details)
    ± = Refrigerant Designator (see Nomenclature details)

PERFORMANCE DATA
Selection Capacity: Medium Temperature Hot Gas Defrost- 60 Hz
Please consult AWEF table on page 20 to confirm model meets DOE minimum AWEF

| R-404A/R-507A| R-448A/R-449A|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0080S6HMA| NA| 7,500| 2,198| 8,400| 2,461| 1| 725| 1,232
LEV0125
S6HMA| LWG100| 10,000| 2,930| 11,600| 3,399| 2| 1,450| 2,464
LEV0160S6HMA| LWG130| 13,000| 3,809| 14,300| 4,190| 2| 1,450| 2,464
LEV0180
S6HMA| LWG155‡| 15,500| 4,542| 17,360| 5,086| 3| 2,175| 3,695
LEV0215S6HMA| LWG180| 18,000| 5,274| 20,880| 6,118| 3| 2,175| 3,695
LEV0245
S6HMA| LWG210| 21,000| 6,153| 23,940| 7,014| 4| 2,900| 4,927
LEV0290S6HMA| LWG270| 27,000| 7,911| 31,860| 9,335| 4| 2,900| 4,927
LEV0360
S6HMA| LWG340| 34,000| 9,962| 40,120| 11,755| 5| 3,625| 6,159
| R-407A/R-407F| R-407C|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of Fans| CFM| m 3 H
LEV0080S6HMA| NA| 8,400| 2,461| 8,400| 2,461| 1| 725| 1,232
LEV0125
S6HMA| LWG100| 11,600| 3,399| 11,600| 3,399| 2| 1,450| 2,464
LEV0160S6HMA| LWG130| 14,300| 4,190| 14,300| 4,190| 2| 1,450| 2,464
LEV0180
S6HMA| LWG155‡| 17,360| 5,086| 17,360| 5,086| 3| 2,175| 3,695
LEV0215S6HMA| LWG180| 20,880| 6,118| 20,880| 6,118| 3| 2,175| 3,695
LEV0245
S6HMA| LWG210| 23,940| 7,014| 23,940| 7,014| 4| 2,900| 4,927
LEV0290S6HMA| LWG270| 31,860| 9,335| 31,860| 9,335| 4| 2,900| 4,927
LEV0360
S6HMA| LWG340| 40,120| 11,755| 40,120| 11,755| 5| 3,625| 6,159

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov

  • = Electrical Code Designator (see Nomenclature details)
    ‡ = Number of fans increases from 2 in legacy to 3 in new model
    Net Capacity is available upon request

SPECIFICATIONS
Hot Gas Defrost- 60 Hz
Please consult AWEF table on page 20 to confirm model meets DOE minimum AWEF

| 2-Speed EC Motor| Drain Pan Heaters
---|---|---
115/1/60| Watts| 115/1/60
New Model| HP| Amps| Watts| MCA| MOPD| Total Amps
LEV0080S6HMA| 1/20| 0.8| 55| 1.1| 20| 200| 1.7
LEV0125
S6HMA| 1/20| 1.7| 110| 2.0| 20| 350| 3
LEV0160S6HMA| 1/20| 1.7| 110| 2.0| 20| 350| 3
LEV0180
S6HMA| 1/20| 2.5| 165| 2.9| 20| 500| 4
LEV0215S6HMA| 1/20| 2.5| 165| 2.9| 20| 500| 4
LEV0245
S6HMA| 1/20| 3.4| 220| 3.8| 20| 650| 6
LEV0290S6HMA| 1/20| 3.4| 220| 3.8| 20| 650| 6
LEV0360
S6HMA| 1/20| 4.2| 275| 4.7| 20| 875| 8
| 2-Speed EC Motor| Drain Pan Heaters
---|---|---
208-230/1/60| Watts| 208-230/1/60
New Model| HP| Amps| Watts| MCA| MOPD| Total Amps
LEV0080S6HMA| 1/20| 0.4| 55| 0.6| 15| 200| 0.9
LEV0125
S6HMA| 1/20| 0.8| 110| 1.1| 15| 350| 1.5
LEV0160S6HMA| 1/20| 0.8| 110| 1.1| 15| 350| 1.5
LEV0180
S6HMA| 1/20| 1.3| 165| 1.6| 15| 500| 2.2
LEV0215S6HMA| 1/20| 1.3| 165| 1.6| 15| 500| 2.2
LEV0245
S6HMA| 1/20| 1.7| 220| 2.1| 15| 650| 2.8
LEV0290S6HMA| 1/20| 1.7| 220| 2.1| 15| 650| 2.8
LEV0360
S6HMA| 1/20| 2.1| 275| 2.6| 15| 875| 3.8

Notes:

  • = Electrical Code Designator (see Nomenclature details)

PHYSICAL DATA
Air Defrost (R-404A/R-507A, R-448A/R-449A, R-407A/R-407F, R-407C)

| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet OD| Suction OD| Equalizer OD| Drain MPT| lb| kg
LEV0055S6AMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 84| 38
LEV0080
S6AMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 84| 38
LEV0125S6AMA| 2| 1/2| 1 – 3/8| 1/4| 3/4| 117| 53
LEV0160
S6AMA| 2| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 164| 74
LEV0180S6AMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 179| 81
LEV0215
S6AMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 192| 87
LEV0245S6AMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 232| 105
LEV0290
S6AMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 240| 109
LEV0360*S6AMA| 5| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 291| 132

Air Defrost (CO2 DX)

| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet 2| Suction OD 2| Drain MPT| lb| kg
LEV0055C6AMA| 1| 3/8| 3/8| 3/4| 84| 38
LEV0080
C6AMA| 1| 3/8| 3/8| 3/4| 84| 38
LEV0125C6AMA| 2| 3/8| 3/8| 3/4| 117| 53
LEV0160
C6AMA| 2| 3/8| 3/8| 3/4| 164| 74
LEV0180C6AMA| 3| 3/8| 3/8| 3/4| 179| 81
LEV0215
C6AMA| 3| 3/8| 3/8| 3/4| 192| 87
LEV0245C6AMA| 4| 3/8| 1/2| 3/4| 232| 105
LEV0290
C6AMA| 4| 3/8| 1/2| 3/4| 240| 109
LEV0360*C6AMA| 5| 1/2| 1/2| 3/4| 291| 132

Notes:

  • = Electrical Code Designator (see Nomenclature details)
    All connections are in “2 = Connection sizes may vary, if TD is lesser or greater than 10⁰F

PHYSICAL DATA
Electric Defrost (R-404A/R-507A, R-448A/R-449A, R-407A/R-407F, R-407C) 507A

| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet OD| Suction OD| Equalizer OD| Drain MPT| lb| kg
LEV0055BS6EMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 90| 41
LEV0080BS6EMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 90| 41
LEV0125BS6EMA| 2| 1/2| 1 – 3/8| 1/4| 3/4| 124| 56
LEV0160BS6EMA| 2| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 180| 82
LEV0180BS6EMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 185| 84
LEV0215BS6EMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 189| 86
LEV0245BS6EMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 244| 111
LEV0290BS6EMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 250| 113
LEV0360BS6EMA| 5| 1 – 3/8| 1 – 3/8| 1/4| 3/4| 300| 136

Electric Defrost (CO2 DX)

| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet 2| Suction 2| Drain MPT| lb| kg
LEV0055C6EMA| 1| 3/8| 3/8| 3/4| 90| 41
LEV0080
C6EMA| 1| 3/8| 3/8| 3/4| 90| 41
LEV0125C6EMA| 2| 3/8| 3/8| 3/4| 124| 56
LEV0160
C6EMA| 2| 3/8| 3/8| 3/4| 180| 82
LEV0180C6EMA| 3| 3/8| 3/8| 3/4| 185| 84
LEV0215
C6EMA| 3| 3/8| 3/8| 3/4| 189| 86
LEV0245C6EMA| 4| 3/8| 1/2| 3/4| 244| 111
LEV0290
C6EMA| 4| 3/8| 1/2| 3/4| 250| 113
LEV0360*C6EMA| 5| 3/8| 1/2| 3/4| 300| 136

Hot Gas Defrost

| | | | | | Approx. Net Weight
---|---|---|---|---|---|---
Model| No. of Fans| Coil Inlet OD| Suction OD| Equalizer OD| Drain MPT| Side Port OD| lb| kg
LEV0080S6HMA| 1| 3/8| 1 – 3/8| 1/4| 3/4| 0.5| 90| 41
LEV0125
S6HMA| 2| 1/2| 1 – 3/8| 1/4| 3/4| 0.5| 148| 67
LEV0160S6HMA| 2| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 176| 80
LEV0180
S6HMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 209| 95
LEV0215S6HMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 222| 101
LEV0245
S6HMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 268| 122
LEV0290S6HMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 274| 124
LEV0360
S6HMA| 5| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.875| 324| 147

Notes:

  • = Electrical Code Designator (see Nomenclature details)
    All connections are in “2 = Connection sizes may vary, if TD is lesser or greater than 10⁰F

DIMENSIONAL DRAWINGS

DIMENSIONAL DATA
Air Defrost

Model| No. of Fans| L| A| B| C| D| E
---|---|---|---|---|---|---|---
Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)
LEV0055±6AMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0080
±6AMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0125±6AMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0160
±6AMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0180±6AMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0215
±6AMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0245±6AMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0290
±6AMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0360*±6AMA| 5| 119 1/2 (3035)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| 22 (559)

Electric Defrost

Model| No. of Fans| L| A| B| C| D| E
---|---|---|---|---|---|---|---
Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)
LEV0055B±6EMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0080B±6EMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0125B±6EMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0160B±6EMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0180B±6EMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0215B±6EMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0245B±6EMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0290B±6EMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0360B±6EMA| 5| 119 1/2 (3035)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| 22 (559)

Hot Gas Defrost

Model| No. of Fans| L| A| B| C| D| E
---|---|---|---|---|---|---|---
Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)
LEV0080S6HMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0125
S6HMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0160S6HMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0180
S6HMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| –| –| –
LEV0215S6HMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0245
S6HMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0290S6HMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0360
S6HMA| 5| 119 1/2 (3035)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| 22 (559)

Notes:

  • = Electrical Code Designator (see Nomenclature details)

DOE Rated AWEF
AWEF DATA
Air Defrost

FPI Model Cooler
R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F

CO 2 DX
AWEF| AWEF| AWEF| AWEF| AWEF
6| LEV0055±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0080
±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0125±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0160
±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0180±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0215
±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0245±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0290
±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0360*±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0

Electric Defrost

FPI Model Cooler
R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F

CO 2 DX
AWEF| AWEF| AWEF| AWEF| AWEF
6| LEV0055B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0080B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0125B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0160B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0180B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0215B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0245B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0290B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0360B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0

Notes:

  • = Electrical Code Designator (see Nomenclature details)
    ± = Refrigerant Designator (see Nomenclature details

DOE Rated AWEF
AWEF DATA
Hot Gas Defrost

FPI Model Cooler
R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F
AWEF AWEF AWEF
6 LEV0080*S6HMA 9.0
6 LEV0125*S6HMA 9.0
6 LEV0160*S6HMA 9.0
6 LEV0180*S6HMA 9.0
6 LEV0215*S6HMA 9.0
6 LEV0245*S6HMA 9.0
6 LEV0290*S6HMA 9.0
6 LEV0360*S6HMA 9.0

Notes:

  • = Electrical Code Designator (see Nomenclature details)

HOT GAS REVERSE CYCLE KITS

(Hot Gas Models Only)
The hot gas defrost Low Velocity Center Mount units may be field piped for hot gas defrost using the optional bypass kit.
When compressor vapor, in reverse cycle defrosting, is directed back into the evaporator at the suction connection, it flows through the defrosting coil, heating the finned surface and melting frost.
As heat is transferred to the coil fins, hot refrigerant gas condenses to a liquid state. The refrigerant then exits the coil at the distributor side port, passes around the expansion valve through the bypass check valve and flows into the liquid refrigerant line.
Kits include one check valve and piping for liquid bypass around expansion valve and instructions for field installation.

| TXV Bypass Kits
---|---
Models Used On| TXV Type| Bypass Kit Assy
LEV0125| EG, EGSE| 50747611
LEV0125| SBF| 50747612
LEV0125| SQE| 50747613
LEV0125| BBI| 50747614
LEV0160 to LEV0290| SBF, SQE| 50747511
LEV0160 to LEV0290| BBI| 50747512
LEV0160 to LEV0290| EG,EGSE| 50747513
LEV0160 to LEV0245| EGSE-1-ZP, EGSE-2-ZP| 50747515
LEV0360| SBF, SQE| 50747311
LEV0360| BBI| 50747312
LEV0360| EG| 50747313
LEV0290| EBF| 50747411

REPLACEMENT PARTS

Cabinet Components

Part # Description No. of Fans
40420101 Drain Pan – Stucco 1
40420201 Drain Pan – Stucco 2
40420301 Drain Pan – Stucco 3
40420401 Drain Pan – Stucco 4
40420501 Drain Pan – Stucco 5
40420102 Drain Pan – White 1
40420202 Drain Pan – White 2
40420302 Drain Pan – White 3
40420402 Drain Pan – White 4
40420502 Drain Pan – White 5

Electrical Components

Part # Description
22597101 Terminal Board – Air Defrost
22597701 Terminal Board – Electric & Hot Gas Defrost
22598201 2SP RELAY 24V
22598202 2SP RELAY 120V
22598203 2SP RELAY 240V
5521R Defrost Termination
4267W Defrost Termination/Fan Delay Thermostat

Motor/Fan Blade/Fan Guards

Part # Description
25329001S Motor 115/1/60 – 2 Speed EC
25329101S Motor 208-230/1/60 – 2 Speed EC
5110E Fan Blade
23106201 Fan Guard – Plastic
5055F Fan Guard – Metal
41417501 Motor Mount Plate

Electric Defrost

Part # Description No. of Fans
4548B Coil Heater 1
4549B Coil Heater 2
4544B Coil Heater 3
4545B Coil Heater 4
4546B Coil Heater 5

STANDARD NOZZLE SELECTION
Air Defrost

Medium Temperature (25°F SST)

Model| No. of Fans| Distributor Tube (in.)| No. of Circuits| Nozzle Selections
OD| Length| R-404A/R-507A| R-448A/R-449A| R-407A/R-407F| R-407C
LEV0055S6AMA| 1| 3/16| 24| 4| L – 1/3| L – 1/2| L – 1/3| L – 1/3
LEV0080
S6AMA| 1| 3/16| 24| 4| L – 1/2| L – 3/4| L – 1/2| L – 1/2
LEV0125S6AMA| 2| 3/16| 24| 6| L – 3/4| L – 1| L – 3/4| L – 3/4
LEV0160
S6AMA| 2| 3/16| 24| 12| E – 1| E – 1 1/2| E – 3/4| E – 3/4
LEV0180S6AMA| 3| 3/16| 24| 10| E – 1| E – 1 1/2| E – 1| E – 1
LEV0215
S6AMA| 3| 3/16| 24| 12| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0245S6AMA| 4| 3/16| 24| 10| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0290
S6AMA| 4| 3/16| 24| 12| E – 2| E – 2 1/2| E – 2| E – 2
LEV0360*S6AMA| 5| 3/16| 24| 20| C – 2 1/2| C – 3| C – 2 1/2| C – 2 1/2

Electric Defrost

Medium Temperature (25°F SST)

Model| No. of Fans| Distributor Tube (in.)| No. of Circuits| Nozzle Selections
OD| Length| R-404A/R-507A| R-448A/R-449A| R-407A/R-407F| R-407C
LEV0055BS6EMA| 1| 3/16| 24| 4| L – 1/3| L – 1/2| L – 1/3| L – 1/3
LEV0080BS6EMA| 1| 3/16| 24| 4| L – 1/2| L – 3/4| L – 1/2| L – 1/2
LEV0125BS6EMA| 2| 3/16| 24| 6| L – 3/4| L – 1| L – 3/4| L – 3/4
LEV0160BS6EMA| 2| 3/16| 24| 12| E – 1| E – 1 1/2| E – 3/4| E – 3/4
LEV0180BS6EMA| 3| 3/16| 24| 10| E – 1| E – 1 1/2| E – 1| E – 1
LEV0215BS6EMA| 3| 3/16| 24| 12| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0245BS6EMA| 4| 3/16| 24| 10| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0290BS6EMA| 4| 3/16| 24| 12| E – 2| E – 2 1/2| E – 2| E – 2
LEV0360BS6EMA| 5| 3/16| 24| 20| C – 2 1/2| C – 3| C – 2 1/2| C – 2 1/2

Hot Gas Defrost

Medium Temperature (25°F SST)

Model| No. of Fans| Distributor Tube (in.)| No. of Circuits| Nozzle Selections
OD| Length| R-404A/R-507A| R-448A/R-449A| R-407A/R-407F| R-407C
LEV0080S6HMA| 1| 3/16| 24| 4| L – 1/2| L – 3/4| L – 1/2| L – 1/2
LEV0125
S6HMA| 1| 3/16| 24| 4| L – 3/4| L – 1| L – 3/4| L – 3/4
LEV0160S6HMA| 2| 3/16| 24| 6| E – 1| E – 1 1/2| E – 3/4| E – 3/4
LEV0180
S6HMA| 2| 3/16| 24| 12| E – 1| E – 1 1/2| E – 1| E – 1
LEV0215S6HMA| 3| 3/16| 24| 10| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0245
S6HMA| 3| 3/16| 24| 12| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0290S6HMA| 4| 3/16| 24| 10| E – 2| E – 2 1/2| E – 2| E – 2
LEV0360
S6HMA| 4| 3/16| 24| 12| C – 2 1/2| C – 3| C – 2 1/2| C – 2 1/2

Notes:

  • = Electrical Code Designator (see Nomenclature details)

2175 West Park Place Blvd.
Stone Mountain, GA 30087
Phone: 800.537.7775 · Fax: 770.465.5900
heatcraftrpd.com
Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice.
LK-LVCM-0124 | Version 008
©2024 Heatcraft Refrigeration Products LLC