LARKIN LK-LVCM Low Velocity Center Mount Evaporator User Guide
- August 19, 2024
- LARKIN
Table of Contents
LOW VELOCITY
CENTER MOUNT EVAPORATOR
Technical Guide
Including models meeting DOE minimum AWEF
LOW VELOCITY CENTER MOUNT EVAPORATORS
FEATURES & BENEFITS
CABINET
■ Low height makes it ideal for low ceiling coolers – all models are only 14.5
inches tall, allowing for maximum headroom and more product storage
■ Air moves across the ceiling in both directions providing even air
distribution throughout the cooler
■ Unit designed to be mounted flush against the ceiling or suspended on rods
■ Heavy-gauge grained aluminum cabinet cleans easily and looks attractive
■ Cabinet design features improved access panels on each end for easy access
to electrical and refrigerationcomponents
■ Captive stainless steel screws for easy service which prevent dropping/loss
and prevent rust streaks or staining
■ Improved wire management and routing
■ Quick disconnect, waterproof plug and receptacle for each motor in all
models
■ Molded fan guard is made of strong, durable, NSF and UL Sanitation rated
lightweight and damage resistant plastic material
■ Liquid line solenoid wire harness is factory-installed forquick installation
COIL
■ High-efficiency aluminum fins with full collars cover mechanically expanded
copper tubes
■ Coils are dehydrated and sealed at the factory
■ Electric defrost models incorporate high quality tubular heaters and a
standard fixed defrost termination thermostat
■ Generous coil surface gives proper compressor balance
■ Internally enhanced tubing and fin design for higher efficiency
■ Optimized heater placement with reduced heater wattages
■ Fixed defrost termination for electric
DRAIN PAN
■ Hinged drain pan for faster, easier and safer access and serviceability
■ Tapered mounting provides proper slope for condensate drainage to one end of
the unit
■ Double drain pan eliminates drain pan sweating
MOTOR
■ Motor rail is design for maximum strength and durability
■ Motors are life lubricated and thermal overload protected
■ 2 Speed EC Motors are factory-installed
CONTROL OPTIONS
■ intelliGen™ Refrigeration Controller (iRC) units come with a factory mounted
controller, tested and calibrated with an electronic expansion valve, pressure
transducer, temperature sensors, control board and user interface. Standard
features include Door Sensor, Product Load Input and Alarm Output.
■ Optional factory or field installable intelliGen Webserver Card (iWC)
enables local and remote monitoring on any phone, tablet or PC.
■ Optional factory or field installable intelliGen Integration Card (iIC)
enables connectivity to BACnet and Modbus.
OTHER OPTIONS
■ Units available with stainless steel housing and drain pan
■ Air defrost units are available with various coil coatings options
OUTSTANDING FEATURES
NOMENCLATURE
PREFERRED OPTION PACKAGES
(HFC Refrigerants)
Preferred Options | Package Description |
---|---|
B0000 | Standard Base |
Standard Base + indicated options below
B0200| intelliGen™ Refrigeration Controller (R-404A/R-448A/R-449A)
B0201| intelliGen™ Refrigeration Controller (R-407A/C/F)
(CO2 DX)
Package| Description (standard base model features + indicated options
below)
---|---
B0500
Standard Base| Danfoss EEV (120V) with 1/4”MPT Transducer Connection
(Pressure Transducer not included)
B0501| Danfoss EEV (120V) with 1/4”MPT Transducer Connection
(Pressure Transducer not included) + Filter Drier
B0502| Sporlan EEV (120V) with 1/4”MPT Transducer Connection
(Pressure Transducer not included)
B0503| Danfoss EEV (120V) with Danfoss Pressure Transducer
B0504| Danfoss EEV (120V) with Danfoss Pressure Transducer + Filter Drier
B0505| Danfoss EEV (120V) with CPC Pressure Transducer
B0506| Danfoss EEV (120V) with CPC Pressure Transducer + Filter Drier
B0507| Sporlan EEV (120V) with Microthermo Pressure Transducer + Filter Drier
PERFORMANCE DATA
Application Capacity: Air Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF
| R-404A/R-507A| R-448A/R-449A|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan
Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of
Fans| CFM| m 3 H
LEV0055S6AMA| LWA050| 5,000| 1,465| 5,500| 1,612| 1| 725| 1,232
LEV0080S6AMA| LWA075| 7,500| 2,198| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125S6AMA| LWA100| 10,000| 2,930| 11,600| 3,399| 2| 1,450| 2,464
LEV0160S6AMA| LWA130| 13,000| 3,809| 14,300| 4,190| 2| 1,450| 2,464
LEV0180S6AMA| LWA155‡| 15,500| 4,542| 17,360| 5,086| 3| 2,175| 3,695
LEV0215S6AMA| LWA180| 18,000| 5,274| 20,880| 6,118| 3| 2,175| 3,695
LEV0245S6AMA| LWA210| 21,000| 6,153| 23,940| 7,014| 4| 2,900| 4,927
LEV0290S6AMA| LWA270| 27,000| 7,911| 31,860| 9,335| 4| 2,900| 4,927
LEV0360*S6AMA| LWA340| 34,000| 9,962| 40,120| 11,755| 5| 3,625| 6,159
| R-407A/R-407F| R-407C|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan
Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of
Fans| CFM| m 3 H
LEV0055S6AMA| LWA050| 5,500| 1,612| 5,500| 1,612| 1| 725| 1,232
LEV0080S6AMA| LWA075| 8,400| 2,461| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125S6AMA| LWA100| 11,600| 3,399| 11,600| 3,399| 2| 1,450| 2,464
LEV0160S6AMA| LWA130| 14,300| 4,190| 14,300| 4,190| 2| 1,450| 2,464
LEV0180S6AMA| LWA155‡| 17,360| 5,086| 17,360| 5,086| 3| 2,175| 3,695
LEV0215S6AMA| LWA180| 20,880| 6,118| 20,880| 6,118| 3| 2,175| 3,695
LEV0245S6AMA| LWA210| 23,940| 7,014| 23,940| 7,014| 4| 2,900| 4,927
LEV0290S6AMA| LWA270| 31,860| 9,335| 31,860| 9,335| 4| 2,900| 4,927
LEV0360*S6AMA| LWA340| 40,120| 11,755| 40,120| 11,755| 5| 3,625| 6,159
Notes:
1= Capacities shown are Application Capacities reflecting nominal operation at
10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy
Factor) standard, the Net Capacity is determined by the AHRI 1250 test method.
DOE will publish this compliance data at
www.regulations.doe.gov
- = Electrical Code Designator (see Nomenclature details)
‡ = Number of fans increases from 2 in legacy to 3 in new model
Net Capacity is available upon request
Application Capacity: Air Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF
| CO 2 DX|
---|---|---
Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST
New Model| BTUH| Watts| No. of Fans| CFM| m
3 H
LEV0055C6A^A| N/A| 5,500| 1,612| 1| 725| 1,232
LEV0080C6A^A| N/A| 8,400| 2,462| 1| 725| 1,232
---|---|---|---|---|---|---
LEV0125C6A^A| N/A| 11,600| 3,400| 2| 1,450| 2,464
LEV0160C6A^A| N/A| 14,300| 4,191| 2| 1,450| 2,464
LEV0180C6A^A| N/A| 17,360| 5,088| 3| 2,175| 3,695
LEV0215C6A^A| N/A| 20,880| 6,119| 3| 2,175| 3,695
LEV0245C6A^A| N/A| 23,940| 7,016| 4| 2,900| 4,927
LEV0290C6A^A| N/A| 31,860| 9,337| 4| 2,900| 4,927
LEV0360*C6A^A| N/A| 40,120| 11,758| 5| 3,625| 6,159
Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation
at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy
Factor) standard, the Net Capacity is determined by the AHRI 1250 test method.
DOE will publish this compliance data at
www.regulations.doe.gov
- = Electrical Code Designator (see Nomenclature details)
‡ = Number of fans increases from 2 in legacy to 3 in new model Net Capacity is available upon request
± = Refrigerant Designator (see Nomenclature details)
SPECIFICATIONS
Air Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF
New Model | HP | 2 Speed EC Motor |
---|---|---|
115/1/60 | 208-230/1/60 | |
Amps | Watts | MCA |
MOPD
LEV0055±6AMA| 1/20| 0.8| 55| 1.1| 20| 0.4| 55| 0.6| 15
LEV0080±6AMA| 1/20| 0.8| 55| 1.1| 20| 0.4| 55| 0.6| 15
---|---|---|---|---|---|---|---|---|---
LEV0125±6AMA| 1/20| 1.7| 110| 2.0| 20| 0.8| 110| 1.1| 15
LEV0160±6AMA| 1/20| 1.7| 110| 2.0| 20| 0.8| 110| 1.1| 15
LEV0180±6AMA| 1/20| 2.5| 165| 2.9| 20| 1.3| 165| 1.6| 15
LEV0215±6AMA| 1/20| 2.5| 165| 2.9| 20| 1.3| 165| 1.6| 15
LEV0245±6AMA| 1/20| 3.4| 220| 3.8| 20| 1.7| 220| 2.1| 15
LEV0290±6AMA| 1/20| 3.4| 220| 3.8| 20| 1.7| 220| 2.1| 15
LEV0360*±6AMA| 1/20| 4.2| 275| 4.7| 20| 2.1| 275| 2.6| 15
PERFORMANCE DATA
Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF
| R-404A/R-507A| R-448A/R-449A|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan
Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of
Fans| CFM| m 3 H
LEV0055BS6EMA| LWEE050| 5,000| 1,465| 5,500| 1,612| 1| 725| 1,232
LEV0080BS6EMA| LWEE075| 7,500| 2,198| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125BS6EMA| LWEE100| 10,000| 2,930| 11,600| 3,399| 2| 1,450| 2,464
LEV0160BS6EMA| LWEE130| 13,000| 3,809| 14,300| 4,190| 2| 1,450| 2,464
LEV0180BS6EMA| LWEE155‡| 15,500| 4,542| 17,360| 5,086| 3| 2,175| 3,695
LEV0215BS6EMA| LWEE180| 18,000| 5,274| 20,880| 6,118| 3| 2,175| 3,695
LEV0245BS6EMA| LWEE210| 21,000| 6,153| 23,940| 7,014| 4| 2,900| 4,927
LEV0290BS6EMA| LWEE270| 27,000| 7,911| 31,860| 9,335| 4| 2,900| 4,927
LEV0360BS6EMA| LWEE340| 34,000| 9,962| 40,120| 11,755| 5| 3,625| 6,159
| R-407A/R-407F| R-407C|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan
Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of
Fans| CFM| m 3 H
LEV0055BS6EMA| LWEE050| 5,500| 1,612| 5,500| 1,612| 1| 725| 1,232
LEV0080BS6EMA| LWEE075| 8,400| 2,461| 8,400| 2,461| 1| 725| 1,232
---|---|---|---|---|---|---|---|---
LEV0125BS6EMA| LWEE100| 11,600| 3,399| 11,600| 3,399| 2| 1,450| 2,464
LEV0160BS6EMA| LWEE130| 14,300| 4,190| 14,300| 4,190| 2| 1,450| 2,464
LEV0180BS6EMA| LWEE155‡| 17,360| 5,086| 17,360| 5,086| 3| 2,175| 3,695
LEV0215BS6EMA| LWEE180| 20,880| 6,118| 20,880| 6,118| 3| 2,175| 3,695
LEV0245BS6EMA| LWEE210| 23,940| 7,014| 23,940| 7,014| 4| 2,900| 4,927
LEV0290BS6EMA| LWEE270| 31,860| 9,335| 31,860| 9,335| 4| 2,900| 4,927
LEV0360BS6EMA| LWEE340| 40,120| 11,755| 40,120| 11,755| 5| 3,625| 6,159
Notes:
1= Capacities shown are Application Capacities reflecting nominal operation at
10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy
Factor) standard, the Net Capacity is determined by the AHRI 1250 test method.
DOE will publish this compliance data at
www.regulations.doe.gov
- = Electrical Code Designator (see Nomenclature details)
‡ = Number of fans increases from 2 in legacy to 3 in new model
Net Capacity is available upon request
PERFORMANCE DATA
Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF
| CO 2 DX|
---|---|---
Application Capacity 1| Fan Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST
New Model| BTUH| Watts| No. of Fans| CFM| m
3 H
LEV0055C6E^A| N/A| 5,500| 1,612| 1| 725| 1,232
LEV0080C6E^A| N/A| 8,400| 2,462| 1| 725| 1,232
---|---|---|---|---|---|---
LEV0125C6E^A| N/A| 11,600| 3,400| 2| 1,450| 2,464
LEV0160C6E^A| N/A| 14,300| 4,191| 2| 1,450| 2,464
LEV0180C6E^A| N/A| 17,360| 5,088| 3| 2,175| 3,695
LEV0215C6E^A| N/A| 20,880| 6,119| 3| 2,175| 3,695
LEV0245C6E^A| N/A| 23,940| 7,016| 4| 2,900| 4,927
LEV0290C6E^A| N/A| 31,860| 9,337| 4| 2,900| 4,927
LEV0360*C6E^A| N/A| 40,120| 11,758| 5| 3,625| 6,159
Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation
at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy
Factor) standard, the Net Capacity is determined by the AHRI 1250 test method.
DOE will publish this compliance data at
www.regulations.doe.gov
- = Electrical Code Designator (see Nomenclature details)
‡ = Number of fans increases from 2 in legacy to 3 in new model
Net Capacity is available upon request
± = Refrigerant Designator (see Nomenclature details)
SPECIFICATIONS
Electric Defrost- 60 Hz
Please consult AWEF table on page 19 to confirm model meets DOE minimum AWEF
New Model|
HP
| 2 Speed EC Motor| Defrost Heaters
---|---|---|---
208-230/1/60
Amps| Watts| MCA| MOPD| Watts| Total Amps
LEV0055B±6EMA| 1/20| 0.4| 55| 0.6| 15| 1,600| 7.0
LEV0080B±6EMA| 1/20| 0.4| 55| 0.6| 15| 1,600| 7.0
---|---|---|---|---|---|---|---
LEV0125B±6EMA| 1/20| 0.8| 55| 1.1| 15| 2,800| 12.2
LEV0160B±6EMA| 1/20| 0.8| 110| 1.1| 15| 2,800| 12.2
LEV0180B±6EMA| 1/20| 1.3| 110| 1.1| 15| 4,000| 17.0
LEV0215B±6EMA| 1/20| 1.3| 165| 1.6| 15| 4,000| 17.4
LEV0245B±6EMA| 1/20| 1.7| 165| 2.1| 15| 5,200| 22.6
LEV0290B±6EMA| 1/20| 1.7| 220| 2.1| 15| 5,200| 22.6
LEV0360B±6EMA| 1/20| 2.1| 220| 2.6| 15| 7,000| 30.4
Notes:
- = Electrical Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)
PERFORMANCE DATA
Selection Capacity: Medium Temperature Hot Gas Defrost- 60 Hz
Please consult AWEF table on page 20 to confirm model meets DOE minimum AWEF
| R-404A/R-507A| R-448A/R-449A|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan
Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of
Fans| CFM| m 3 H
LEV0080S6HMA| NA| 7,500| 2,198| 8,400| 2,461| 1| 725| 1,232
LEV0125S6HMA| LWG100| 10,000| 2,930| 11,600| 3,399| 2| 1,450| 2,464
LEV0160S6HMA| LWG130| 13,000| 3,809| 14,300| 4,190| 2| 1,450| 2,464
LEV0180S6HMA| LWG155‡| 15,500| 4,542| 17,360| 5,086| 3| 2,175| 3,695
LEV0215S6HMA| LWG180| 18,000| 5,274| 20,880| 6,118| 3| 2,175| 3,695
LEV0245S6HMA| LWG210| 21,000| 6,153| 23,940| 7,014| 4| 2,900| 4,927
LEV0290S6HMA| LWG270| 27,000| 7,911| 31,860| 9,335| 4| 2,900| 4,927
LEV0360S6HMA| LWG340| 34,000| 9,962| 40,120| 11,755| 5| 3,625| 6,159
| R-407A/R-407F| R-407C|
---|---|---|---
Application Capacity 1| Application Capacity 1| Fan
Data
| Legacy Model| 10°F TD/25°F SST| 6°C TD/4°C
SST| 10°F TD/25°F SST| 6°C TD/4°C SST
New Model| BTUH| Watts| BTUH| Watts| No. of
Fans| CFM| m 3 H
LEV0080S6HMA| NA| 8,400| 2,461| 8,400| 2,461| 1| 725| 1,232
LEV0125S6HMA| LWG100| 11,600| 3,399| 11,600| 3,399| 2| 1,450| 2,464
LEV0160S6HMA| LWG130| 14,300| 4,190| 14,300| 4,190| 2| 1,450| 2,464
LEV0180S6HMA| LWG155‡| 17,360| 5,086| 17,360| 5,086| 3| 2,175| 3,695
LEV0215S6HMA| LWG180| 20,880| 6,118| 20,880| 6,118| 3| 2,175| 3,695
LEV0245S6HMA| LWG210| 23,940| 7,014| 23,940| 7,014| 4| 2,900| 4,927
LEV0290S6HMA| LWG270| 31,860| 9,335| 31,860| 9,335| 4| 2,900| 4,927
LEV0360S6HMA| LWG340| 40,120| 11,755| 40,120| 11,755| 5| 3,625| 6,159
Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation
at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy
Factor) standard, the Net Capacity is determined by the AHRI 1250 test method.
DOE will publish this compliance data at
www.regulations.doe.gov
- = Electrical Code Designator (see Nomenclature details)
‡ = Number of fans increases from 2 in legacy to 3 in new model
Net Capacity is available upon request
SPECIFICATIONS
Hot Gas Defrost- 60 Hz
Please consult AWEF table on page 20 to confirm model meets DOE minimum AWEF
| 2-Speed EC Motor| Drain Pan Heaters
---|---|---
115/1/60| Watts| 115/1/60
New Model| HP| Amps| Watts| MCA| MOPD|
Total Amps
LEV0080S6HMA| 1/20| 0.8| 55| 1.1| 20| 200| 1.7
LEV0125S6HMA| 1/20| 1.7| 110| 2.0| 20| 350| 3
LEV0160S6HMA| 1/20| 1.7| 110| 2.0| 20| 350| 3
LEV0180S6HMA| 1/20| 2.5| 165| 2.9| 20| 500| 4
LEV0215S6HMA| 1/20| 2.5| 165| 2.9| 20| 500| 4
LEV0245S6HMA| 1/20| 3.4| 220| 3.8| 20| 650| 6
LEV0290S6HMA| 1/20| 3.4| 220| 3.8| 20| 650| 6
LEV0360S6HMA| 1/20| 4.2| 275| 4.7| 20| 875| 8
| 2-Speed EC Motor| Drain Pan Heaters
---|---|---
208-230/1/60| Watts| 208-230/1/60
New Model| HP| Amps| Watts| MCA| MOPD|
Total Amps
LEV0080S6HMA| 1/20| 0.4| 55| 0.6| 15| 200| 0.9
LEV0125S6HMA| 1/20| 0.8| 110| 1.1| 15| 350| 1.5
LEV0160S6HMA| 1/20| 0.8| 110| 1.1| 15| 350| 1.5
LEV0180S6HMA| 1/20| 1.3| 165| 1.6| 15| 500| 2.2
LEV0215S6HMA| 1/20| 1.3| 165| 1.6| 15| 500| 2.2
LEV0245S6HMA| 1/20| 1.7| 220| 2.1| 15| 650| 2.8
LEV0290S6HMA| 1/20| 1.7| 220| 2.1| 15| 650| 2.8
LEV0360S6HMA| 1/20| 2.1| 275| 2.6| 15| 875| 3.8
Notes:
- = Electrical Code Designator (see Nomenclature details)
PHYSICAL DATA
Air Defrost (R-404A/R-507A, R-448A/R-449A, R-407A/R-407F, R-407C)
| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet OD| Suction OD|
Equalizer OD| Drain MPT| lb| kg
LEV0055S6AMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 84| 38
LEV0080S6AMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 84| 38
LEV0125S6AMA| 2| 1/2| 1 – 3/8| 1/4| 3/4| 117| 53
LEV0160S6AMA| 2| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 164| 74
LEV0180S6AMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 179| 81
LEV0215S6AMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 192| 87
LEV0245S6AMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 232| 105
LEV0290S6AMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 240| 109
LEV0360*S6AMA| 5| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 291| 132
Air Defrost (CO2 DX)
| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet 2| Suction OD 2| Drain
MPT| lb| kg
LEV0055C6AMA| 1| 3/8| 3/8| 3/4| 84| 38
LEV0080C6AMA| 1| 3/8| 3/8| 3/4| 84| 38
LEV0125C6AMA| 2| 3/8| 3/8| 3/4| 117| 53
LEV0160C6AMA| 2| 3/8| 3/8| 3/4| 164| 74
LEV0180C6AMA| 3| 3/8| 3/8| 3/4| 179| 81
LEV0215C6AMA| 3| 3/8| 3/8| 3/4| 192| 87
LEV0245C6AMA| 4| 3/8| 1/2| 3/4| 232| 105
LEV0290C6AMA| 4| 3/8| 1/2| 3/4| 240| 109
LEV0360*C6AMA| 5| 1/2| 1/2| 3/4| 291| 132
Notes:
- = Electrical Code Designator (see Nomenclature details)
All connections are in “2 = Connection sizes may vary, if TD is lesser or greater than 10⁰F
PHYSICAL DATA
Electric Defrost (R-404A/R-507A, R-448A/R-449A, R-407A/R-407F, R-407C) 507A
| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet OD| Suction OD|
Equalizer OD| Drain MPT| lb| kg
LEV0055BS6EMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 90| 41
LEV0080BS6EMA| 1| 1/2| 1 – 3/8| 1/4| 3/4| 90| 41
LEV0125BS6EMA| 2| 1/2| 1 – 3/8| 1/4| 3/4| 124| 56
LEV0160BS6EMA| 2| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 180| 82
LEV0180BS6EMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 185| 84
LEV0215BS6EMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 189| 86
LEV0245BS6EMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 244| 111
LEV0290BS6EMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 250| 113
LEV0360BS6EMA| 5| 1 – 3/8| 1 – 3/8| 1/4| 3/4| 300| 136
Electric Defrost (CO2 DX)
| | | | | Approx. Net Weight
---|---|---|---|---|---
Model| No. of Fans| Coil Inlet 2| Suction 2| Drain
MPT| lb| kg
LEV0055C6EMA| 1| 3/8| 3/8| 3/4| 90| 41
LEV0080C6EMA| 1| 3/8| 3/8| 3/4| 90| 41
LEV0125C6EMA| 2| 3/8| 3/8| 3/4| 124| 56
LEV0160C6EMA| 2| 3/8| 3/8| 3/4| 180| 82
LEV0180C6EMA| 3| 3/8| 3/8| 3/4| 185| 84
LEV0215C6EMA| 3| 3/8| 3/8| 3/4| 189| 86
LEV0245C6EMA| 4| 3/8| 1/2| 3/4| 244| 111
LEV0290C6EMA| 4| 3/8| 1/2| 3/4| 250| 113
LEV0360*C6EMA| 5| 3/8| 1/2| 3/4| 300| 136
Hot Gas Defrost
| | | | | | Approx. Net Weight
---|---|---|---|---|---|---
Model| No. of Fans| Coil Inlet OD| Suction OD|
Equalizer OD| Drain MPT| Side Port OD| lb| kg
LEV0080S6HMA| 1| 3/8| 1 – 3/8| 1/4| 3/4| 0.5| 90| 41
LEV0125S6HMA| 2| 1/2| 1 – 3/8| 1/4| 3/4| 0.5| 148| 67
LEV0160S6HMA| 2| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 176| 80
LEV0180S6HMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 209| 95
LEV0215S6HMA| 3| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 222| 101
LEV0245S6HMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 268| 122
LEV0290S6HMA| 4| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.625| 274| 124
LEV0360S6HMA| 5| 1 – 1/8| 1 – 3/8| 1/4| 3/4| 0.875| 324| 147
Notes:
- = Electrical Code Designator (see Nomenclature details)
All connections are in “2 = Connection sizes may vary, if TD is lesser or greater than 10⁰F
DIMENSIONAL DRAWINGS
DIMENSIONAL DATA
Air Defrost
Model| No. of Fans| L| A| B| C| D|
E
---|---|---|---|---|---|---|---
Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)|
Inches (mm)| Inches (mm)
LEV0055±6AMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0080±6AMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0125±6AMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0160±6AMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0180±6AMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0215±6AMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0245±6AMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0290±6AMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0360*±6AMA| 5| 119 1/2 (3035)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| 22
(559)
Electric Defrost
Model| No. of Fans| L| A| B| C| D|
E
---|---|---|---|---|---|---|---
Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)|
Inches (mm)| Inches (mm)
LEV0055B±6EMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0080B±6EMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0125B±6EMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0160B±6EMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0180B±6EMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0215B±6EMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0245B±6EMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0290B±6EMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0360B±6EMA| 5| 119 1/2 (3035)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| 22
(559)
Hot Gas Defrost
Model| No. of Fans| L| A| B| C| D|
E
---|---|---|---|---|---|---|---
Inches (mm)| Inches (mm)| Inches (mm)| Inches (mm)|
Inches (mm)| Inches (mm)
LEV0080S6HMA| 1| 31 1/2 (800)| 22 (559)| –| –| –| –
LEV0125S6HMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0160S6HMA| 2| 53 1/2 (1359)| 22 (559)| 22 (559)| –| –| –
LEV0180S6HMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| –| –| –
LEV0215S6HMA| 3| 75 1/2 (1918)| 22 (559)| 22 (559)| 22 (559)| –| –
LEV0245S6HMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0290S6HMA| 4| 97 1/2 (2477)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| –
LEV0360S6HMA| 5| 119 1/2 (3035)| 22 (559)| 22 (559)| 22 (559)| 22 (559)| 22
(559)
Notes:
- = Electrical Code Designator (see Nomenclature details)
DOE Rated AWEF
AWEF DATA
Air Defrost
FPI | Model | Cooler |
---|---|---|
R-404A/ R-507A | R-448A/ R-449A | R-407A/ R-407F |
CO 2 DX
AWEF| AWEF| AWEF| AWEF| AWEF
6| LEV0055±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0080±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0125±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0160±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0180±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0215±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0245±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0290±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0360*±6AMA| 9.0| 9.0| 9.0| 9.0| 9.0
Electric Defrost
FPI | Model | Cooler |
---|---|---|
R-404A/ R-507A | R-448A/ R-449A | R-407A/ R-407F |
CO 2 DX
AWEF| AWEF| AWEF| AWEF| AWEF
6| LEV0055B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0080B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0125B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0160B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0180B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0215B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0245B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0290B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
6| LEV0360B±6EMA| 9.0| 9.0| 9.0| 9.0| 9.0
Notes:
- = Electrical Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details
DOE Rated AWEF
AWEF DATA
Hot Gas Defrost
FPI | Model | Cooler |
---|---|---|
R-404A/ R-507A | R-448A/ R-449A | R-407A/ R-407F |
AWEF | AWEF | AWEF |
6 | LEV0080*S6HMA | 9.0 |
6 | LEV0125*S6HMA | 9.0 |
6 | LEV0160*S6HMA | 9.0 |
6 | LEV0180*S6HMA | 9.0 |
6 | LEV0215*S6HMA | 9.0 |
6 | LEV0245*S6HMA | 9.0 |
6 | LEV0290*S6HMA | 9.0 |
6 | LEV0360*S6HMA | 9.0 |
Notes:
- = Electrical Code Designator (see Nomenclature details)
HOT GAS REVERSE CYCLE KITS
(Hot Gas Models Only)
The hot gas defrost Low Velocity Center Mount units may be field piped for hot
gas defrost using the optional bypass kit.
When compressor vapor, in reverse cycle defrosting, is directed back into the
evaporator at the suction connection, it flows through the defrosting coil,
heating the finned surface and melting frost.
As heat is transferred to the coil fins, hot refrigerant gas condenses to a
liquid state. The refrigerant then exits the coil at the distributor side
port, passes around the expansion valve through the bypass check valve and
flows into the liquid refrigerant line.
Kits include one check valve and piping for liquid bypass around expansion
valve and instructions for field installation.
| TXV Bypass Kits
---|---
Models Used On| TXV Type| Bypass Kit Assy
LEV0125| EG, EGSE| 50747611
LEV0125| SBF| 50747612
LEV0125| SQE| 50747613
LEV0125| BBI| 50747614
LEV0160 to LEV0290| SBF, SQE| 50747511
LEV0160 to LEV0290| BBI| 50747512
LEV0160 to LEV0290| EG,EGSE| 50747513
LEV0160 to LEV0245| EGSE-1-ZP, EGSE-2-ZP| 50747515
LEV0360| SBF, SQE| 50747311
LEV0360| BBI| 50747312
LEV0360| EG| 50747313
LEV0290| EBF| 50747411
REPLACEMENT PARTS
Cabinet Components
Part # | Description | No. of Fans |
---|---|---|
40420101 | Drain Pan – Stucco | 1 |
40420201 | Drain Pan – Stucco | 2 |
40420301 | Drain Pan – Stucco | 3 |
40420401 | Drain Pan – Stucco | 4 |
40420501 | Drain Pan – Stucco | 5 |
40420102 | Drain Pan – White | 1 |
40420202 | Drain Pan – White | 2 |
40420302 | Drain Pan – White | 3 |
40420402 | Drain Pan – White | 4 |
40420502 | Drain Pan – White | 5 |
Electrical Components
Part # | Description |
---|---|
22597101 | Terminal Board – Air Defrost |
22597701 | Terminal Board – Electric & Hot Gas Defrost |
22598201 | 2SP RELAY 24V |
22598202 | 2SP RELAY 120V |
22598203 | 2SP RELAY 240V |
5521R | Defrost Termination |
4267W | Defrost Termination/Fan Delay Thermostat |
Motor/Fan Blade/Fan Guards
Part # | Description |
---|---|
25329001S | Motor 115/1/60 – 2 Speed EC |
25329101S | Motor 208-230/1/60 – 2 Speed EC |
5110E | Fan Blade |
23106201 | Fan Guard – Plastic |
5055F | Fan Guard – Metal |
41417501 | Motor Mount Plate |
Electric Defrost
Part # | Description | No. of Fans |
---|---|---|
4548B | Coil Heater | 1 |
4549B | Coil Heater | 2 |
4544B | Coil Heater | 3 |
4545B | Coil Heater | 4 |
4546B | Coil Heater | 5 |
STANDARD NOZZLE SELECTION
Air Defrost
Medium Temperature (25°F SST)
Model| No. of Fans| Distributor Tube (in.)| No. of
Circuits| Nozzle Selections
OD| Length| R-404A/R-507A| R-448A/R-449A|
R-407A/R-407F| R-407C
LEV0055S6AMA| 1| 3/16| 24| 4| L – 1/3| L – 1/2| L – 1/3| L – 1/3
LEV0080S6AMA| 1| 3/16| 24| 4| L – 1/2| L – 3/4| L – 1/2| L – 1/2
LEV0125S6AMA| 2| 3/16| 24| 6| L – 3/4| L – 1| L – 3/4| L – 3/4
LEV0160S6AMA| 2| 3/16| 24| 12| E – 1| E – 1 1/2| E – 3/4| E – 3/4
LEV0180S6AMA| 3| 3/16| 24| 10| E – 1| E – 1 1/2| E – 1| E – 1
LEV0215S6AMA| 3| 3/16| 24| 12| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0245S6AMA| 4| 3/16| 24| 10| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0290S6AMA| 4| 3/16| 24| 12| E – 2| E – 2 1/2| E – 2| E – 2
LEV0360*S6AMA| 5| 3/16| 24| 20| C – 2 1/2| C – 3| C – 2 1/2| C – 2 1/2
Electric Defrost
Medium Temperature (25°F SST)
Model| No. of Fans| Distributor Tube (in.)| No. of
Circuits| Nozzle Selections
OD| Length| R-404A/R-507A| R-448A/R-449A|
R-407A/R-407F| R-407C
LEV0055BS6EMA| 1| 3/16| 24| 4| L – 1/3| L – 1/2| L – 1/3| L – 1/3
LEV0080BS6EMA| 1| 3/16| 24| 4| L – 1/2| L – 3/4| L – 1/2| L – 1/2
LEV0125BS6EMA| 2| 3/16| 24| 6| L – 3/4| L – 1| L – 3/4| L – 3/4
LEV0160BS6EMA| 2| 3/16| 24| 12| E – 1| E – 1 1/2| E – 3/4| E – 3/4
LEV0180BS6EMA| 3| 3/16| 24| 10| E – 1| E – 1 1/2| E – 1| E – 1
LEV0215BS6EMA| 3| 3/16| 24| 12| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0245BS6EMA| 4| 3/16| 24| 10| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0290BS6EMA| 4| 3/16| 24| 12| E – 2| E – 2 1/2| E – 2| E – 2
LEV0360BS6EMA| 5| 3/16| 24| 20| C – 2 1/2| C – 3| C – 2 1/2| C – 2 1/2
Hot Gas Defrost
Medium Temperature (25°F SST)
Model| No. of Fans| Distributor Tube (in.)| No. of
Circuits| Nozzle Selections
OD| Length| R-404A/R-507A| R-448A/R-449A|
R-407A/R-407F| R-407C
LEV0080S6HMA| 1| 3/16| 24| 4| L – 1/2| L – 3/4| L – 1/2| L – 1/2
LEV0125S6HMA| 1| 3/16| 24| 4| L – 3/4| L – 1| L – 3/4| L – 3/4
LEV0160S6HMA| 2| 3/16| 24| 6| E – 1| E – 1 1/2| E – 3/4| E – 3/4
LEV0180S6HMA| 2| 3/16| 24| 12| E – 1| E – 1 1/2| E – 1| E – 1
LEV0215S6HMA| 3| 3/16| 24| 10| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0245S6HMA| 3| 3/16| 24| 12| E – 1 1/2| E – 2| E – 1 1/2| E – 1 1/2
LEV0290S6HMA| 4| 3/16| 24| 10| E – 2| E – 2 1/2| E – 2| E – 2
LEV0360S6HMA| 4| 3/16| 24| 12| C – 2 1/2| C – 3| C – 2 1/2| C – 2 1/2
Notes:
- = Electrical Code Designator (see Nomenclature details)
2175 West Park Place Blvd.
Stone Mountain, GA 30087
Phone: 800.537.7775 · Fax: 770.465.5900
heatcraftrpd.com
Since product improvement is a continuing effort, we reserve the right to make
changes in specifications without notice.
LK-LVCM-0124 | Version 008
©2024 Heatcraft Refrigeration Products LLC
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>