nVent RTD-200 Temperature Sensor for Ambient Sensing Owner’s Manual
- August 7, 2024
- nVent
Table of Contents
RAYCHEM
RTD-200
RTD Temperature Sensor
for Ambient Sensing
Installation Instructions
RTD-200 Temperature Sensor for Ambient Sensing
APPROVALS
Approvals associated with control device, however not to be used in Div. 1 areas.
DESCRIPTION
The nVent RAYCHEM RTD-200 is a three-wire platinum RTD (resistance-
temperature-detector) typically used with electronic control systems that
require accurate ambient temperature sensing. The RTD-200 comes with a 1/2”
NPT fitting that installs to the appropriate conduit box. This allows mounting
of the RTD in a typical ambient location. This also allows for splicing of RTD
extension wire back to the controller.
Tools required
- None
Additional materials required
- None
KIT CONTENTS
Item | Qty | Description |
---|---|---|
A | 1 | RTD temperature sensor with 1/2-in NPT fitting |
SPECIFICATIONS
Sensor
Housing| 316 stainless steel
Dimensions| 3 in (7.6 mm) length 1/4 in (6 mm) diameter
Accuracy| ±0.3°F (0.2°C)
Range| –100°F to 300°F (–73°C to 149°C)
Resistance| 100 ohms +/– .25 ohm at 0°C
X=0.00385 ohms/ohm/°C
Extension Wires
Wire size (each of 3)| 22 AWG
Note: The length of RTD extension wires is determined by the wire gauge
used.
To reduce the likelihood that electrical noise will affect temperature
measurement, keep RTD extension wires as short as possible. Use shielded
instrument cable such as nVent RAYCHEM MONI-RTD-WIRE (22 AWG, PVC insulation,
–30°F to 140°F, –20°C to 60°C) or Belden 83553 (22 AWG, FEP insulation, –95°F
to 395°F, –70°C to 200°C).
Wire dielectric strength| 600 volts
Length| 6 ft (1.8 m)
Outer jacket| Fluoropolymer
Maximum exposure
temperature| 300°F (149°C)
Sensor fitting| 1/2-in NPT with sealing washer and nut
WARNING:
This component is an electrical device. It must be installed correctly to
ensure proper operation and to prevent shock or fire. Read these important
warnings and carefully follow all the installation instructions. Component
approvals and performance are based on the use of specified parts only. Do not
use substitute parts or vinyl electrical tape to make connections.
INSTALLATION
The RTD-200 can be terminated directly at the controller using the supplied
1/2 in NPT fitting. In this configuration, no additional extension wire is
required.
RTD wired directly to controller
(Distance from sensor bulb to controller must be less than 4 ft)
Note: RTD should be placed in a typical ambient location. RTD wired
with splice box
Note: RTD should be placed in a typical ambient location.
RTD-200 WIRING
Electrical Schematic of RTD
Connect the wires as shown.
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com| Europe, Middle
East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com| Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nVent.com| Latin
America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com
---|---|---|---
©2024 nVent. All nVent marks and logos are owned or licensed by nVent Services
GmbH or its affiliates. All other trademarks are the property of their
respective owners.
nVent reserves the right to change specifications without notice.
RAYCHEM-IM-H56998-RTD200-EN-2401
nVent.com/RAYCHEM
PN P000000095