B-TEC XT Series Matko Wireless Transceivers Instruction Manual
- June 3, 2024
- B-TEC
Table of Contents
Matko Wireless Installation Manual
XT Series:
XT100, XT200,
XT300, XT400
Instruction Manual
Product Comparison
| XT100T| XT200T| XT300T| XT400T
---|---|---|---|---
Line of Sight Distance| Up to 1 mile| Up to 1 mile| Up to 1 mile| Up to 1 Mile
Baud Rate
1200
2400
4800
9600
19200| 9600 (Fixed)| ▲
▲
▲
▲
▲| ▲
▲
▲
▲
▲| ▲
▲
▲
▲
▲
Protocol
RS232
20 ma Current Loop
RS422/485| ▲| ▲
▲
▲| ▲
▲
▲| ▲
▲
▲
Approvals
US (FCC)
Canada (IC)
Europe (ETSI)| ▲| ▲| ▲
▲
▲| ▲
▲
▲
Network ID’s| 1| 2| 16| 16
TTL Line Passing| 0| 0| 0| 4(Transceiver)/2(Receiver)
Configuration| Fixed| In Field| In Field| In Field
Enclosure| NEMA 4
1P65| NEMA 4
1P65| NEMA 4
1P65| NEMA 4
1P65
Wiring Diagram
| Indicator| Pin| Display
---|---|---|---
Indicators with Active 20 mA Output| +20 mA
-20 mA| 6
5| CL (+)
CL (-)
Indicators with Passive 20 mA Output| +20 mA
-20 mA| 1
2
5
6| +9 VDC
GND -JUMP
CL (-) -JUMP
CL (+)
Indicators with RS232 Output| GND
TXD| 2
3| GND
232 RXD
Indicators with RS422 Output| TX 422A (+)
TX 422B (-)| 7
8| RX 422A
RX 422B
Figure 1 – Wiring Diagram
Compatibility:
All Matko XT Series transceivers and receivers are compatible with each other.
An XT300 Transceiver can talk to an XT100 Receiver; however, the units must
have been configured to the same ID (XT100 only works on ID 0)
Power:
The XT Series transceivers can operate with any voltage source from 7.5 VDC to
12 VDC. This includes running power directly off of an SBL Series remote VCC
and GND.
Install Notes:
-Mount all units in a direct line of sight with each other with all antennas on the same plane (all pointed straight up or straight down).
Configuration
All units must be on the same ID to communicate with each other. XT100 units
are fixed on ID 0. XT200 units are selectable between ID 0 and 1. XT300/400
units have IDs 0 through 15 available.
- Set the ID DIP switch to the desired ID
- Set the baud rate DIP switch to match the serial device connected to the XT unit. XT100 units are fixed at 9600 baud RS232.
- Press the CONFIG button on the transceiver to save the DIP switch settings. The three green configuration LEDs will illuminate as setup progresses. When all three LEDs light up Configuration is complete. *
• If there is a problem with configuration the red CONFIG LED will blink every 5 seconds up to 6 times as internal communication is re-established. The red CONFIG LED will then blink several times rapidly. Wait a minimum of 5 seconds before pressing CONFIG again.
- It may take up to 30 seconds after configuration before a link is established with other units and data is transmitted between units.
When the transceiver has been properly configured and properly wired according to figure 1 the corresponding green LED (RS232, CLOOP, or RS422) will blink with each data transmission. This LED will blink regardless of whether the receiver side has been properly configured or even powered on. The red RX LED will blink on the receiver side with each data burst received from the matching transceiver. Ideally with each green blink on the transceiver side there will be a corresponding red blink on the receiver side. If the receiver side is infrequent the signal is not reliably getting from one unit to the other.
Reposition antennas for direct line of sight as much as is feasible.
XT400 IO (Input Output) Setup
The XT400 transceiver has the ability to pass up to 4 input lines to one or
more XT400 Transceivers set for outputs. You may not have more than one unit
set for input on the same system as the two units would conflict with each
other. Each transceiver can either be an input device or an output. You cannot
mix input and output on the same device.
In addition to setting the DIP switches as mentioned above the unit will also
need to have the removable jumper placed in the correct spot as well as two 8
pin chips.
-For input lines, place the jumper on input and make sure the two MCT6 chips are inserted into the sockets to the right, labeled “IN”
-For output lines, place the jumper on output and make sure the two MCT6 chips are inserted into the sockets to the left, labeled “OUT”
*Input and output are only in reference to the digital lines. Serial data is bidirectional regardless of jumper settings.
Example Installations
Case 1
Typical Setup: Indicator to remote using two XT300 Transceivers
Case 2
Networked Indicators
Case 3
An Indicator to two remote displays with built in receivers
Case 4
Indicator with a closed contact switch to a SBL-4SG-XT400
Case 5
Indicator with a remote zero/print switch near the Display
Case 6
A switch remotely controlling an AC Relay for a traffic light
*You can reverse the logic by connecting the coils of the AC relay to IO 0 and +5 VDC instead of ground
Repeater
If the transceivers/receivers are working but you cannot get the needed range
for the job site you can try to add an extra transceiver to system as a
repeater unit. Mount the unit roughly in the middle of the distance with line
of site to both ends. You will need power at this location. Add a jumper wire
from 232 RXD to 232 TXD. Any signal that can make it to this transceiver will
then be transmitted back out. The original transmitting unit will have the
data echoed back to it, so this will not work for bidirectional communication.
Troubleshooting
Before you call, please see if any of the below problems/solutions match your
conditions.
The Red PWR LED doesn’t come on
Verify the power supply is turned on and putting out 7.5 to 12 volts DC and
that the wires are securely screwed into the terminals.
No LEDs are blinking on the unit connected to the indicator
Make sure the indicator’s port is enabled for continuous output and that the
unit is wired according to the wiring diagram. The indicator’s transmit should
be wired into the XT units receive terminals. The corresponding LEDs should
blink with every signal regardless of the DIP settings or even if the signal
is good or not.
No LEDs are blinking on the unit connected to the remote display Make sure
there is an LED blinking on the side connected to the indicator first. If that
side does not blink the receiving side will not blink. If the indicator side
is blinking, then make sure both units are set to the same ID and reconfigure
both sides by pressing the CONFIG button on each side. Try unplugging one unit
and plugging it back in to have the wireless units re-establish the network.
If the remote display end still does not blink, then the problem may be
distance/obstacle related. Try bringing both sides into an office and see if
they communicate over a short distance. If they do, then reposition the units
for better line of site or add a repeater to the system.
The RX LED blinks on the remote display side of my XT transceiver, but the
remote shows “NoData” The problem is probably with the wiring. Make sure you
are coming out a transmit on the XT unit and going into a receive on the
remote display. Try changing to a different transmit port if you have any unit
other than the XT100T.
All other models have RS232, current loop and RS422 as options. You do not
have to use the same loop on the remote display side as you use on the
indicator side.
The RX LED is blinking on the remote display side, but the remote is blank or
shows random numbers.
Verify the baud rate is correct and press the configure button on both ends.
Reset the remote display to factory defaults by holding the LEFT and RIGHT
buttons during countdown. After the unit starts to count down for the second
time let go and the remote should display the correct baud rate. If still
blank, try shift data over to the left or
right.
The system is reliable except when weight is on the scale
Make sure that when a truck pulls on a scale it does not come between the two
antennas. A truck acts as a solid metal wall blocking the signal
The system sometimes works and sometimes does not.
Make sure nothing has changed at the site such as trees growing into the line
of sight or gravel piles growing to block the signal. If you are at the far
edge of the maximum usable range then many things can degrade the signal
including, temperature, humidity, to large equipment being run nearby. In
general, make sure both antennas are pointing straight up and down, are as
high above the earth as is reasonably possible and have a clear line of sight
to each other. Other than that you may need a repeater added to the system to
extend the range *If you are still unable to get the unit working after going
through this list, please call our tech support at 844-CAL-BTEK
(844-225-2835)
Mounting Dimensions
XT100T, XT200T, XT300T
There are (4) holes 0.156” diameter with spacing of 4.7” wide x 2.4” tall
A second option is to use (2) mounting holes 4.7” wide with a maximum diameter
of .175”
XT400T
There are (4) holes 0.156” diameter with spacing of 6.75” wide x 2.4” tall A
second option is to use (2) mounting holes 6.75” wide with a maximum diameter
of .175”
Manual Revision
v.2.3
Reworded all configuration procedures. Added wiring diagrams and
troubleshooting pages. Added XT400 diagram
Replacement Part Numbers
Part Number | Description |
---|---|
841-500053 | 2.4 GHz antenna for all XT Series models |
Discontinued | XT100 Series receiver mounted internally to an SBL Series Remote |
Display.
Fixed at 9600 Baud rate and 1 System ID
841-500028| XT200 Series receiver mounted internally to an SBL Series Remote
Display.
Selectable Baud Rate and 2 System IDs
Discontinued| XT300 Series receiver mounted internally to an SBL Series Remote
Display.
Selectable Baud Rate and 16 System IDs
Discontinued| XT300 Series receiver mounted internally to an SBL Series Remote
Display.
Selectable Baud Rate and 16 System IDs. 2 Digital output
841-500024| XT100 Series Transmitter/Receiver in a NEMA 4 case.
Fixed at 9600 Baud rate and 1 System ID
841-500027| XT200 Series Transmitter/Receiver in a NEMA 4 case.
Selectable Baud Rate and 2 System IDs
Discontinued| XT300 Series Transmitter/Receiver in a NEMA 4 case.
Selectable Baud Rate and 16 System IDs
Discontinued| XT300 Series Transmitter/Receiver in a NEMA 4 case.
Selectable Baud Rate and 16 System IDs. 4 Digital inputs or 4 digital outputs.
841-500054| 9 Volt DC power supply for all XT Series Transceivers
*Any serial devices can be connected using XT Series Wireless transceivers. PCs can be connected to printers or multiple indicators can be networked together… B-TEK remotes are not required for a wireless system.
RF Exposure
WARNING: To satisfy FCC RF exposure requirements for mobile transmitting
devices, a separation distance of 20 cm or more should be maintained between
the antenna of this device and persons during device operation. To ensure
compliance, operations at closer than this distance is not recommended. The
antenna used for this transmitter must not be co-located in conjunction with
any other antenna or transmitter. The preceding statement must be included as
a CAUTION statement in OEM product manuals in order to alert users of FCC RF
Exposure compliance.
Wireless Manual v.2.3