Technical Specifications:

  • Operating voltage: 220 ~ 240V AC 50/60Hz

  • Rated load: 400W (Capacitive load), 800W (Resistive load)

  • Stand-by power: 0.5W

  • Sensitivity: Ceiling mounted height – 3m, Ceiling mounted
    height – 6m*, Wall mounted height – 2m

  • Hold-time: 100% / 75% / 50% / 25% / 10%

  • Daylight sensor: 2Lux / 10Lux / 25Lux / 50Lux / Disable

  • Microwave frequency: Transmitting power – 1mW Max.

  • Detection range: Ceiling mounted height – 3m, Wall mounted
    height – 1.5-2m

  • Detection angle: 3-6m (radius), 12-15m, 360° (Ceiling), 120°
    (Wall)

  • Working temperature: -20°C ~ 60°C

Product Usage Instructions:

Settings Adjustment:

  1. Sensitivity: Adjust sensitivity by selecting
    the appropriate combination on the DIP switches based on your
    application needs.

  2. Hold-time: Set the duration for which the
    light remains at full brightness after movement detection.

  3. Daylight Sensor: Choose the desired daylight
    threshold on the DIP switches. Light will activate upon movement if
    daylight sensor is disabled.

Troubleshooting:

Issue Cause Remedy
The light will not come on Incorrect light-control setting selected, Faulty

lamp, No power
supply| Adjust settings, Replace lamp, Check power supply
The lamp is always on| Continuous movement in detection zone| Check detection area setting
The lamp is on without any identifiable movement| The sensor is not mounted for reliably detecting movement| Securely mount enclosure
The lamp will not work despite movement| Movement occurred but not identified by the sensor| Reduce sensitivity, Check detection area setting

Care and Safety:

We recommend cleaning with a soft dry cloth. Avoid solvents or
abrasive cleaners that may damage the finish. Always switch off the
power supply before cleaning for safety.

FAQ:

Q: Where can I find further information about the product?

A: For additional details, please visit https://www.lighting- info.co.uk/95542

Q: What should I do if the light fitting malfunctions?

A: Refer to the troubleshooting section in the manual to
identify the cause and follow the recommended remedies
provided.

Q: How should I adjust the sensitivity of the sensor?

A: You can adjust the sensor sensitivity by selecting the
appropriate combination on the DIP switches based on your specific
requirements.

“`

Microwave Movement Sensor

This product is fitted with a microwave movement sensor. Please see below detailed operating instructions.

Technical Specifications:

Operating voltage

220 ~ 240V AC 50/60Hz

Rated load Stand-by power

400W (Capacitive load) 800W (Resistive load) 0.5W

Sensitivity Hold-time

Ceiling mounted height: 3m
Ceiling mounted
height: 6m*
Wall mounted height: 2m

100% / 75% / 50% / 25% / 10% 100% / 75% / 50% 100% / 75% / 50% / 25% / 10% 5s / 30s / 90s / 3min / 20min / 30min

Daylight sensor

2Lux / 10Lux / 25Lux / 50Lux / Disable

Microwave frequency

5.8 GHz ±75MHz

Transmitting power

1mW Max.

Ceiling mounted
Detection range height: 3m
Wall mounted height: 1.5-2m
Detection angle

3- 6m (radius ) 12-15m 3600 (Ceiling) / 1200 (Wall)

Working temperature

-200C ~ 600C

*50%, 75%, 100% detection sensitivity is workable when installed at 6m mounting height. Only 10%, 25% sensitivity is not able to detect motion signal.
Settings:

1. Sensitivity
Sensitivity can be adjusted by selecting the combination on the DIP switches for different applications.

2. Hold-time
Hold-time refers to the time period that the light remains 100% on if no more movement is detected.

3. Daylight sensor
Different daylight threshold can be preset on DIP switches. Light will always turn on upon movement if daylight sensor is disabled.

I ­100% II ­ 75% III ­ 50% IV ­ 25% V ­ 10%

123
100% 75% 50% 25% 10%

I ­ 5s II ­ 30s III ­ 90s IV ­ 3min V ­ 20min VI ­ 30min

456

5s 30s 90s 3min 20min 30min

I ­ 2Lux II ­ 10Lux III ­ 25Lux IV ­ 50Lux V ­ Disable

789

2Lux 10Lux 25Lux 50Lux

Disable*

*Disable means the daylight sensor does not work. The sensor will turn on light once motion is detected regardless of ambient light level.

Trouble shooting: Malfunction Cause Remedy
The light will not come on
The lamp is always on
The lamp is on without any identifiable movement
The lamp will not work despite movement

Cause
Incorrect light-control setting selected Faulty lamp No power supply Continuous movement in the detection zone The sensor is not mounted for reliably detecting movement
Movement occurred, but not identified by the sensor (Movement behind wall, movement of small object in immediate lamp vicinity etc.)
Rapid movements are being suppressed to minimize malfunctioning or the detection radius is too small.

Remedy
Adjust daylight threshold setting Replace lamp Check power to sensor Check detection area setting Securely mount enclosure
1. Reduce sensitivity. 2. Check the movement behind walls to avoid
facilities such as water pipe, fan, which may mis-trigger the sensor.
Check detection area setting

Care and Safety
We recommend cleaning with a soft dry cloth. Do not use solvents or abrasive cleaners as these could damage the finish. For your safety, always switch off the power supply before cleaning.

For further information, please visit https://www.lighting-info.co.uk/95542
V8 30/01/2024 UK Manufacturer: BH17 7BY EU Manufacturer: Brilliant AG, Brilliantstrasse 1, D-27442 Gnarrenburg

Instruction manual
HeroPro CCT Microwave Emergency
95542, 103940
www.saxbylighting.com

Thank you for purchasing this light fitting. Please read the instructions carefully before use to ensure safe and satisfactory operation of this product. Please retain these instructions for future reference.

Warning

Technical data

This light fitting is double insulated and does not require connection to an earth circuit.
Please read these instructions carefully before commencing any work.
This unit must be fitted by a competent and qualified electrician.
Install in accordance with the IEE Wiring regulations and current Building Regulations.
Check the pack and make sure you have all the parts listed.
To prevent electrocution switch off at the mains supply before installing or maintaining this fitting. Ensure other persons cannot restore the electrical supply without your knowledge.
If you are in any doubt, please consult a qualified electrician.

Supply Voltage:
Bulb Type:

220-240 V~, 50 Hz
95542—-18/14/9W LED (SMD) CCT, 3000/4000/6000K 900/1400/1800Lm – 143.8Lm in EM mode
103940—28/24/20W LED (SMD) CCT, 3000/4000/6000K 2000/2400/2800Lm – 190Lm in EM mode
These products contain a light source of energy efficiency class D.

Non-replaceable light source

Replaceable control gear by a professional

Conformity with all relevant UKCA Directive requirements.

This light fitting should be connected to a fused circuit. If replacing an existing fitting, make a careful note of the connections. Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your local authority or retailer for recycling advice.
Layout
Plan the desired layout of these fittings carefully, ensuring the cables will reach the distances between each light fitting. Avoid locating any cables in positions that would cause a hazard. Position cables and junction boxes (not supplied) away from areas where they may be at risk from being cut, trapped or damaged. The mains supply cable must have a minimum cross section area of 1.0mm2. Cables must be protected using suitable conduit or plastic trunking. The products can be wall or ceiling mounted. If wall mounting ensure that the power supply is at the bottom.

Conformity with all relevant EC Directive requirements.
The power supply is Double Insulated and does not require connection to an Earth circuit. Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or local store for recycling advice.
This product is not suitable for dimming.

IP65

This product is rated at IP65

IK10 This product is rated at IK10 for 95542.

IK08 This product is rated at IK08 for 103940.

Battery parameters:

Duration

3 hours (180 Minutes)

Installation
Existing fittings must be completely removed before installation of a new product. Before removing the existing fitting, carefully note the position of each set of wires. Note the switch is turned off before installation. The ceiling surface must be flat and smooth to ensure a good fit. Ensure that the screws and cable entry points are sealed to maintain the IP rating of the product. · Twist and remove the lamp cover from the product, keep safe for refitting later.
· Turn the clip to loose the LED tray in the rear casing.
· Using the rear casing as a template mark the position to drill out the fixing holes. Take care to avoid damaging any concealed wiring and pipes.
· Fix the rear casing into the position using the installation plugs and screws. · Pull the cable through the cable entry hole and seal to maintain the IP rating
and wire as detailed Wiring Diagram.

Maximum Operating Humdity Change over time Battery Specification Battery Charge Time Battery warranty Ambient Temperature

90% Approximately 1s LifePO4 3.2V 1500mAh 24 Hours 5 years 0ºC – 45ºC

· Unscrewed the battery box cover and then connect the battery DC connector together before commissioning.
· Refit the LED tray back into the rear casing and lock the clip. · Twist the lamp cover back onto the product and lock in place. · Replace fuse or circuit breaker and switch on. Your light is now ready for use.

The wattage is changeable between the diffrent wattage using the wattage switch on the driver before installation.

18W 14W 9W For the 95542 is the 18W/14W/9W selectable

28W 24W 20W For the 103940 is the 28W/24W/20W selectable

The colour is changeable between 3000/4000/6000K using the CCT switch on the driver before installation.
6000K 4000K 3000K

Choose your preferred wattage and colour before installing by wattage switch or CCT switch on the driver. Note: Befeore you change the wattage or colour, please turn off the power switch for safety.

1

2

3

4

5

6

  • Product images may vary.
    Bezels for 95542 only
    The following individual casings are available for purchase separately.
    95545 : Chrome plain 95548 : Black plain 95551 : Anthracite grey plain
    95546 : White eyelid 95549 : Black eyelid 95552 : Anthracite grey eyelid
    95547 : White grill 95550 : Black grill 95553 : Anthracite grey grill

Wiring
· This product is double insulated and must not be earthed. If there are any incoming earth cables, they must be joined together and well insulated with good quality insulation tape. This is to ensure earth continuity throughout your property.

SUPPLY

PUSH DOWN LIGHT FITTING

INSERT CABLE

· Having correctly identified the wiring from your existing light fitting, connect to the quick fit connection block in the following way, using the supplied link cables where necessary.

Non-Maintained Wiring:

The product is normally off and comes on during a power failure

MW SENSOR

LED Driver

INPUT OUTPUT

SUPPLY

LIGHT FITTING L N N L’

LN

N

NEUTRAL

L/PL

N

Emergency

SL PL Lout

Maintained (Unswitched) Wiring:

The product is on permanently and comes on

during a power failure SUPPLY

MW SENSOR
INPUT OUTPUT
LIGHT FITTING L N N L’

LED Driver
LN

N

NEUTRAL

SWITCH LIVE LINK CABLE

L/PL N

Emergency

PERMANENT LIVE

“Lout” terminal is only for connecting with OUTPUT of MW sensor, don’t for the INPUT
Maintained (Switched) Wiring: The product is used as a normal light – switch on/off, light turns on/off. Comes on during a power failure.

SUPPLY

MW SENSOR
INPUT OUTPUT
LIGHT FITTING L N N L’

LED Driver
LN

N

NEUTRAL

L/PL

N

Emergency

SL PL Lout

SL PL Lout

“Lout” terminal is only for connecting with OUTPUT of MW sensor, don’t for the INPUT

SWITCH LIVE PERMANENT LIVE

“Lout” terminal is only for connecting with OUTPUT of MW sensor, don’t for the INPUT

Sensor Used as Master Function

L

N

……

Lout

Master

Slave

Master

N

SL PL Lout

N

SL PL

N

SL PL

N

SL PL Lout

……

Emergency

LED Driver LN

LED Driver LN

LED Driver LN

Emergency

LED Driver LN

L/PL N

L/PL N

INPUT LN

OUTNPUT 0.75 1.5
NL

INPUT LN

OUTNPUT 0.75 1.5
NL

10%

30min

89

2Lux

10Lux

25Lux

50Lux

123456789

LED 95542 LED 103940

LED 95539 LED 102732

10%

30min

89 2Lux
10Lux 25Lux 50Lux

123456789

LED 95542 LED 103940

The master light LED 95542 match with the slave light LED 95539, in total link QTY is Max. 10 lamps included the master light. The master light LED 103940 match with the slave light LED 102732, in total link QTY is Max. 7 lamps included the master light.

Check that…
You have correctly identified the wires. The connections are tight. No loose strands have been left out of the connection block.