Panasonic CW-XC103HU Room Air Conditioner Instruction Manual

July 30, 2024
Panasonic

Panasonic CW-XC103HU Room Air Conditioner

Panasonic-CW-XC103HU-Room-Air-Conditioner-product

Specifications

  • Model: PANASONIC CW-XC103HU
  • Order No.: RAC0209003C1 E9
  • Service Manual Models: CW-XC103HU, CW-XC118HU, CW-XC123HU, CW-XC143HU

Product Usage Instructions

Disassembly Instructions

Mechanical Parts
To disassemble the mechanical parts, follow the steps outlined in the manual for the Front Grille, Cabinet, and Control Box.

Air Handling Parts
For air handling parts like the Air Guide and Blower, Fan, and Shroud, carefully follow the disassembly instructions provided.

Electrical Parts
When dealing with electrical components such as the Overload Protector, Compressor, Capacitor, Power Cord, Thermostat, Synchronous Motor, and Motor, ensure to adhere to safety precautions and disconnect power before proceeding.

Refrigeration Cycle
Understand the components of the refrigeration cycle including the Condenser, Evaporator, and Capillary Tube for proper maintenance and troubleshooting.

Installation
Select the Best Location
Choose the optimal location for installation as per the guidelines provided in the manual.

Check of Installation
Before proceeding with installation, ensure all necessary checks are performed to guarantee proper functioning.

How to Drain
Follow the instructions on how to drain excess water efficiently from the unit.

How to Install
Installation steps are detailed in the manual including procedures for using gaskets and installation kits.

Troubleshooting Guide

Outside Dimensions
Refer to the manual for outside dimensions information to assist in installation planning.

Piping System
Understand the piping system configuration for maintenance and troubleshooting purposes.

Troubleshooting Guide
If issues arise, utilize the troubleshooting guide provided to identify and resolve common problems.

FAQ (Frequently Asked Questions)

  1. Q: Can I clean the air filters myself?
    A: Yes, you can clean the air filters by following the instructions in the manual. It is recommended to clean them regularly for optimal performance.

  2. Q: How often should I service the unit?
    A: Regular servicing is recommended at least once a year to ensure efficient operation and prolong the lifespan of the air conditioner.

WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the product or products deal with in this service information by anyone else could result in serious injury or death.
© 2002 Matsushita Electric Industrial co., Ltd. All rights reserved. Unauthorized copying and distribution is violation of law.

PREFACE
This SERVICE MANUAL provides various service information, including the mechanical and electrical parts etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.

SAFETY PRECAUTIONS

  1. When servicing the unit, set the POWER SWITCH to OFF and unplug the power cord.
  2. Observe the original lead dress.

If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit.

SPECIFICATIONS

MODELS
ITEMS| CW-XC103HU| CW-XC118HU| CW-XC123HU| CW- XC143HU
---|---|---|---|---
POWER SUPPLY| Ø, V, Hz| 1, 115, 60
COOLING CAPACITY| Btu/h.| 9,800| 11,800| 12,000| 13,800
POWER INPUT| W| 910| 1,090| 1,110| 1,280
RUNNING CURRENT| A| 8.4| 10.0| 10.2| 11.8
EER| Btu/h.W| 10.8| 10.8| 10.8| 10.8
OPERATING

CONDITION

| INDOOR| °F(°C)| DB : 80(26.7) WB : 67(19.4)
OUTDOOR| °F(°C)| DB : 95(35)  WB : 75(23.9)
REFREIGERANT (R-22) CHARGE| 490g(17.3 oz)| 500g(17.6 oz)| 500g(17.6 oz)| 530g(18.7 oz)
EVAPORATOR| 2 ROW 16 STACKS,SLIT-FIN TYPE| 2 ROW 13 STACKS,SLIT-FIN TYPE
CONDENSER| 2 ROW 18 STACKS,LOUVERED-FIN TYPE| 2 ROW 17 STACKS,LOUVERED-FIN TYPE
**** FAN| INDOOR| TURBO FAN
OUTDOOR| PROPELLER TYPE FAN WITH SLINGER-RING
FAN SPEED| FAN/COOLING| 3/3
FAN MOTOR| 6 POLES
OPERATION CONTROL| REMOTE CONTROLLER
ROOM TEMP. CONTROL| THERMISTOR
AIR DIRECTION

CONTROL

| VERTICAL| MANUAL
HORIZONTAL| AUTO| MANUAL| AUTO
CONSTRUCTION| SLIDE IN-OUT CHASSIS
*** PROTECTOR| COMPRESSOR| OVERLOAD PROTECTOR
FAN MOTOR| INTERNAL THERMAL PROTECTOR
POWER CORD| 3 WIRE WITH GROUNDING
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN SYSTEM| DRAIN PIPE OR SPLASHED BY FAN SLINGER
NET WEIGHT| lbs(kg)| 95(43)| 100(45)| 115(52)
DIMENSION(W
HD)| inch(mm)| 23 5/814 31/3222 5/16 (600380*567)

  • DB:Dry Bulb
    **WB:Wet Bulb
    The specifications will be changed without notice for further improvement.

**FEATURES

**

VENTILATION
The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions. When fresh air is necessary in the room, set the ventilation lever to the OPEN position.
The damper is opened and room air is drawn out.

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(2\)

NOTE: Before using the ventilation feature, and prior to installing the front grille, pull down part until level with part .

CW-XC118HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(3\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(4\)

Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner.

  1. OPERATION BUTTON
    To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again.
    This button takes priority over any other buttons. When you first turn it on, the air conditioner is on the High cool mode and the temp. at 72°F (22°C).

  2. OPERATION MODE SELECTION BUTTON
    Every time you push this button, it will toggle between COOL and FAN.

  3. FAN SPEED SELECTION BUTTON
    Every time you push this button, it is set as follows.
    [High(F3) → Low(F1) → Med(F2) → High(F3) →…]

  4. ROOM TEMPERATURE SETTING BUTTON
    This button can automatically control the temperature of theroom.Thetemperaturecanbesetwithin arangeof 60°F to 86°F by 1°F (16°C to 30°C by 1°C).
    Select the lower number for lower temperature of the room.

  5. ON/OFF TIMER BUTTON
    You can set the time when the unit will turn on or turn off automatically by pressing the timer button. If the unit is operating, this button controls the time it will be turned off. If the unit is off state, this button controls the time it will start. Every time you push this button, the remaining time will be set as follows.

    • Stopping operation
    • (1Hour → 2Hours → 3Hours → 4Hours → 5Hours → 6Hours → 7Hours → 8Hours → 9Hours → 10Hours → 11Hours → 12Hours → 0Hour → 1Hour → 2Hours →… )
    • The Setting Temperature will be raised by 2°F(1°C) 30min. later and by 2°F(1°C) after another 30 min.
    • Starting operation
    • (1Hour → 2Hours → 3Hours → 4Hours → 5Hours → 6Hours → 7Hours → 8Hours → 9Hours → 10Hours → 11Hours → 12Hours → 0Hour → 1Hour → 2Hours → … )
  6. REMOTE CONTROL SIGNAL RECEIVER

CW-XC103HU, CW-XC123HU, CW-XC143HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(5\)

Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner.

  1. OPERATION BUTTON
    To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again.
    This button takes priority over any other buttons. When you first turn it on, the air conditioner is on the High cool mode and the temp. at 72°F(22°C).

  2. OPERATION MODE SELECTION BUTTON
    Every time you push this button, it will toggle between COOL, FAN.

  3. ROOM TEMPERATURE SETTING BUTTON
    This button can automatically control the temperature of the room. The temperature can be set within a range of 60°Fto 86°Fby1°F(16°Cto30°Cby1°C).
    Select the lower number for lower temperature of the room.

  4. FAN SPEED SELECTION BUTTON
    Every time you push this button, it is set as follows.
    [High(F3) → Low(F1) → Med(F2) → High(F3) →…]

  5. ON/OFF TIMER BUTTON
    You can set the time when the unit will turn on or turn off automatically by pressing the timer button. If the unit is operating, this button controls the time it will be turned off. If the unit is off state, this button controls the time it will start. Every time you push this button, the remaining time will be set as follows.

    • Stopping operation
      (1Hour → 2Hours → 3Hours → 4Hours → 5Hours → 6Hours → 7Hours → 8Hours → 9Hours → 10Hours → 11Hours → 12Hours → 0Hour → 1Hour → 2Hours →… )
      The Setting Temperature will be raised by 2°F(1˚C) 30min. later and by 2°F(1˚C) after another 30 min.

    • Starting operation
      (1Hour → 2Hours → 3Hours → 4Hours → 5Hours → 6Hours → 7Hours → 8Hours → 9Hours → 10Hours → 11Hours → 12Hours → 0Hour → 1Hour → 2Hours → … )

  6. AIR SWING BUTTON
    This button can automatically control the air flow direction.

  7. ECONOMY BUTTON
    If you push this button, the fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and check the room air temperature to determine if cooling is necessary.

  8. REMOTE CONTROL SIGNAL RECEIVER

DISASSEMBLY INSTRUCTIONS

  • Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.

MECHANICAL PARTS
FRONT GRILLE

  1. Open the lnlet grille upward .
  2. Remove the screw which fastens the front grille.
  3. Pull the front grille from the right side.
  4. Remove the front grille.
  5. Re-install the component by referring to the removal procedure, above.(See Figure 1)

CABINET

  1. After disassembling the FRONT GRILLE, remove the 2 screws which fasten the cabinet at both sides.
  2. Remove the 2 screws which fasten the cabinet at back.
  3. Pull the base pan forward. (See Figure 2)
  4. Remove the cabinet.
  5. Re-install the component by referring to the removal procedure, above.

CONTROL BOX

  1. Remove the front grille. (Refer to section 2.1.1)
  2. Remove the cabinet. (Refer to section 2.1.2)
  3. Remove the 2 screws which fasten the control box cover.
  4. Remove two housings which connect compressor wire and motor wire in the control box.
  5. Discharge the capacitor by placing a 20,000 ohmresistor across the capacitor terminals.
  6. Remove the 2 screws which fasten the control box.
  7. Pull the control box forward completely.
  8. Re-install the components by referring to the removal procedure, above. (See Figure 3)
    (Refer to the circuit diagram found on pages 34~37 in this manual and on the control box.)

AIR HANDLING PARTS
AIR GUIDE AND BLOWER

  1. Remove the front grille. (Refer to section 2.1.1)
  2. Remove the cabinet. (Refer to section 2.1.2)
  3. Remove the control box. (Refer to section 2.1.3)
  4. Remove the 4 screws which fasten the brace.
  5. Remove the brace.
  6. Remove the 2 screws which fasten the evaporator.
  7. Move the evaporator forward and pulling it upward slightly. (See Figure 4)Panasonic-CW-XC103HU-Room-Air-Conditioner-\(9\)
  8. Move the evaporator to the left carefully.
  9. Pull out the hook of orifice by pushing the tabs and remove it. (See Figure 5)
  10. Remove the clamp with a hand plier which secures the blower.
  11. Remove the blower.
  12. Remove the 4 screws which fasten the air guide from the barrier.
  13. Move the air guide backward, pulling out from the base pan.
  14. Re-install the components by referring to the removal procedure, above.

FAN

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the brace (Refer to section 2.2.1)
  3. Remove the 4 screws which fasten the condenser.
  4. Move the condenser to the left carefully.
  5. Remove the clamp which secures the fan.
  6. Remove the fan. (See Figure 7)
  7. Re-install by referring to the removal procedure.

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(12\)

SHROUD

  1. Remove the fan. (Refer to section 2.2.2)
  2. Remove the screw which fastens the shroud.
  3. Remove the shroud. (See Figure 8)
  4. Re-install the component by referring to the removal procedure, above.

ELECTRICAL PARTS
OVERLOAD PROTECTOR

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the nut which fastens the terminal cover.
  3. Remove the terminal cover. (See Figure 9)
  4. Remove all the leads from the overload protector.
  5. Remove the overload protector.
  6. Re-install the component by referring to the removal procedure, above.

COMPRESSOR

  1. Remove the cabinet. (Refer to section 2.1.2)

  2. Discharge the refrigerant system using a FreonTM Recovery System.
    If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

  3. Remove the overload protector. (Refer to section 2.3.1)

  4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.

  5. Remove the 3 nuts and the 3 washers which fasten the compressor.

  6. Remove the compressor. (See Figure 10)

  7. Re-install the components by referring to the removal procedure, above.

CAPACITOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Remove the knobs and the screw which fasten control panel from control box.
  3. Remove the screw which located in the front.
  4. Open the bottom side of control box.
  5. Remove the screw and the clamp which fastens the capacitor.
  6. Disconnect all the leads of capacitor terminals.
  7. Re-install the components by referring to the removal procedure, above. (See Figure 11)

POWER CORD

  1. Remove the control box. (Refer to section 2.1.3)

  2. Open the control box. (Refer to section 2.3.3)

  3. Disconnect the grounding screw from the control box.

  4. Disconnect the 2 receptacles.

  5. Remove a screw which fastens the clip cord.
    (See Figure 12)Panasonic-CW-XC103HU-Room-Air-
Conditioner-\(17\)

  6. Remove the power cord.

  7. Re-install the component by referring to the above removal procedure, above.
    (Use only one ground-marked hole for ground connection.)

  8. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord which has the same specification marked on the supply cord attached at the unit.)

THERMISTOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Open the control box. (Refer to section 2.3.3)
  3. Disconnet the thermistor terminals from main P.W.B assembly.
  4. Remove the thermistor.
  5. Re-install the components by refereing to the above removal procedure. (See Figure 13)

SYNCHRONOUS MOTOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Unfold the control box. (Refer to section 2.3.3)
  3. Remove the crankshaft.
  4. Disconnect all the leads of the synchronous motor.
  5. Remove the 2 screws which fasten the synchronous motor. (See Fig. 14)
  6. Re-install the components by referring to the removal procedure, above.

MOTOR

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the evaporator. (Refer to section 2.2.1)
  3. Remove the orifice. (Refer to section 2.2.1)
  4. Remove the blower. (Refer to section 2.2.1)
  5. Remove the fan. (Refer to section 2.2.2)
  6. Remove the control box cover and disconnect 5 or 4 wires of motor housing. (Refer to section 2.1.3)
  7. Remove the 2 or 4 screws which fasten the motor from the mount motor. (See Figure 14)
  8. Remove the motor.
  9. Re-install the components by referring to the removal procedure, above.(See Figure 14)

REFRIGERATING CYCLE

CAUTION
Discharge the refrigerant system using a FreonTM Recovery System.
If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

CONDENSER

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the 4 screws which fasten the brace.(Refer to section 2.2.1)
  3. Remove the 5 screws which fasten the condenser and shroud.
  4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
  5. Remove the condenser.
  6. Re-install the component by referring to notes.
    (See Figure 15)

EVAPORATOR

  1. Remove the cabinet. (Refer to section 2.1.2)

  2. Remove the 2 screws which fasten the evaporator.

  3. Move the evaporator sideways carefully.
    (Refer to section 2.2.1)

  4. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections.

  5. Remove the evaporator.

  6. Re-install the component by referring to notes.
    (See Figure 16)

CAPILLARY TUBE

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.(See caution above)
  3. Remove the capillary tube.
  4. Re-install the component by referring to notes.

NOTES
Replacement of the refrigeration cycle.

  1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System.
    If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

  2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

  3. Solder service valves into the pinch-off tube ports, leaving the valves open.

  4. Solder the pinch-off tubes with Service valves.

  5. Evacuate as follows.

  6. Connect the vacuum pump, as illustrated figure 18A.

  7. Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.
    CAUTION
    If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

  8. Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vaccum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

  9. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 18B.
    Open valve C.
    Discharge the line at the manifold connection.

  10. The system is now ready for final charging.

  11. Recharge as follows :

  12. Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

  13. Connect the charging cylinder as shown in figure 18B.
    With valve C open, discharge the hose at the manifold connection.

  14. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

  15. If more charge is required, the high-side will not take it. Close valve A.

  16. With the unit running, open valve B and add the balance of the charge.

  * Do not add the liquid refrigerant to the Low-side.
  * Watch the Low-side gauge; allow pressure to rise to 0.2 Mpa.
  * Turn off valve B and allow pressure to drop.
  * Repeat steps b. and c. until the balance of the charge is in the system.
6. When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(23\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(24\)

INSTALLATION

SELECT THE BEST LOCATION

  1. To prevent vibration and noise, make sure the unit is installed securely and firmly.

  2. Install the unit where the sunlight does not shine directly on the unit.

  3. The outside of the cabinet must extend outward for at least 30.48cm(12″) and there should be no obstacles, such as a fence or wall, within 50.8cm(20″) from the back of the cabinet because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner. CAUTION
    All side louvers of the cabinet must remain exposed to the outside of the structure.

  4. Install the unit a little slanted so the back is slightly lower than the front (about 12.7mm(1/2″)). This will help force condensed water to the outside.

  5. Install the unit from the bottom about 76.2cm(30″)~152.4cm(60″) above the floor level.

CHECK OF INSTALLATION
The setting conditions must be checked prior to initial starting.
The undermentioned items are especially important checking points when the installation is finished.

  1. Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.
  2. Connect to a single-outlet 15A circuit. (or 20A circuit for Electric Heater Model)
  3. To avoid vibration or noise, make sure the air conditioner is installed securely.
  4. Avoid placing furniture or draperies in front of the air inlet and outlet.

HOW TO DRAIN
(When using drain pipe)
The air conditioner must be installed horizontally or tilted slightly to the outside for proper water drainage.
On exceptionally hot and humid days the air conditioner may overflow conclensed water.
If the air conditioner is used in hot and a high humidity zone, exchange the 1 HOLE RUBBER for the 2 DRAIN PIPE.(See figure 19, figure 20.)

HOW TO INSTALL

WHEN USING GASKET

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(61\)

  1. WINDOW (WIDTH-A, HEIGHT-B)
  2. GASKET
  3. WALL
  4. DETAILS 5.1 x 30 ROUND HEAD WOOD SCREWS
A B C D E F H I
625mm (245/8″) 392mm (157/16″) 280mm (111/32″) 30mm (11/16″) 0~25mm
(0~1″) OVER 420mm (OVER 1617/32″) 5~10mm (3/16″~3/8″) -5~5mm (-3/16″~3/16″)

WHEN USING INSTALLATION KITS
A. WINDOW REQUIREMENTS
This unit is designed for installation in standard double hung windows with actual opening widths from 68.58cm(27″) to 99.09cm(39″).
The top and bottom window sash must open sufficiently to allow a clear vertical opening of 16″ from the bottom of the upper sash to the window stool.

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(29\)

INSTALLATION KITS CONTENTS

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(30\)

NO. NAME OF PARTS Q’TY
1 FRAME CURTAIN 2
2 SILL SUPPORT 2
3 BOLT 2
4 NUT 2
5 SCREW(TYPE A) (10mm(2/5″)) 16
6 SCREW(TYPE B)       D5.1mm(0.2″) 16mm(0.63″) 3
7 SCREW(TYPE C)          D4.1mm(0.17″)
16mm(0.63″) 5
8 FOAM-STRIP 1
9 FOAM-PE (600mm x 25mm x 2mm) 1
10 FRAME GUIDE 2
11 WINDOW LOCKING BRACKET 1
12 FOAM-PE (920mm x 30mm x 2mm) 1
13 DRAIN PIPE 1

SUGGESTED TOOL REQUIREMENTS
SCREWDRIVER(+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL

PREPARATION OF CHASSIS

  1. Remove the screws which fasten the cabinet at both sides and at the back.
  2. Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.Panasonic-CW-XC103HU-Room-Air-Conditioner-\(31\)
  3. Remove EPS Material.
  4. Cut the window sash seal to the proper length. Peel off the backing and attach the foam-pe  12 to the underside of the window sash.
  5. Remove the backing from the top upper guide Foam PE 9 and attach it to the bottom of the upper guide.
  6. Attach the upper guide onto the top of the cabinet with 3 type A screws.Panasonic-CW-XC103HU-Room-Air-Conditioner-\(32\)
  7. Insert the frame guides 10  into the bottom of the cabinet.
  8. Insert the Frame Curtain  1 into the upper guide and frame guides 10 .
  9. Fasten the curtains to the unit with 4 Type A screws at the both sides.

CABINET INSTALLATION

  1. Open the window. Mark a line on center of the window stool(or desired air conditioner location). Carefully place the cabinet on the window stool and align the center mark on the bottom front with the center line marked in the window stool.

  2. Pull the bottom window sash down behind the upper guide until it meets.Panasonic-CW-XC103HU-Room-Air-Conditioner-\(33\) NOTE:
    Do not pull the window sash down so tightly that the movement of Frame Curtain is restricted.

  3. Panasonic-CW-XC103HU-Room-Air-Conditioner-\(34\)Loosely assemble the sill support using the parts in Figure 23.

  4. Select the position that will place the sill support near the outer most point on sill (See Figure 23)
    NOTE: Be careful when you install the cabinet (frame guides 10 are broken easily).

  5. Attach the sill support to the cabinet track hole in relation to the selected position using 2 Type A screws in each support (See Figure 24).

  6. The cabinet should be installed with a very slight tilt(about 12.7mm 1/2″) downward toward the outside (See Figure 25).
    Adjust the bolt and the nut of sill support for balancing the cabinet.

  7. Attach the cabinet to the window stool by driving the screws 6 (Type B: Length sixteen millimeters and below.) through the front angle into window stool 16mm (5/8″).

  8. Pull each Frame curtain properly to each window sash track, and repeat step 2.

  9. Attach each Frame curtain to the window sash by using screws (Type C).(See Figure 26)

  10. Slide the unit into the cabinet.(See Fig. 27)
    CAUTION: For security purpose, reinstall screws(Type A) at the cabinet’s sides.Panasonic-CW-XC103HU-Room-Air-Conditioner-\(38\)

  11. Cut the foam-strip to the proper length and insert between the upper and lower window sash.(See Fig. 28)Panasonic-CW-XC103HU-Room-Air-Conditioner-\(39\)

  12. Attach the window locking bracket with a type C screw. (See Fig. 29)

  13. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place.(See Fig. 30)

  14. Lift the inlet grille and secure it with a type A screw through the front grille.(See Fig. 31)Panasonic-CW-XC103HU-Room-Air-Conditioner-\(40\)

TROUBLESHOOTING GUIDE

OUTSIDE DIMENSIONS

unit: mm(inch)

PIPING SYSTEM

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(43\)

Figure 33 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(44\)

TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two kinds.
The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(45\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(46\)

ELECTRICAL PARTS TROUBLESHOOTING GUIDE: CW-XC103HU, CW-XC118HU, CW-XC123HU, CW-XC143HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(47\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(48\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(49\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(50\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(51\)

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(52\)

COMPLAINT CAUSE REMEDY
Fan motor will not run. No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to rotary switch. If none, check power supply

cord. Replace cord if circuit is open.
Wire disconnected or connection loose| Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Capacitor (Discharge capacitor before testing.)| Test capacitor.
Replace if not within ±10% of manufacturer’s rating. Replace if shorted, open, or damaged.
Will not rotate| Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.
Units using slinger ring for condenser fan must have 1/4 to 5/16 inch clearance to the base. If it hits the base, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Fan motor runs intermittently| Revolves on overload.| Check voltage. If not within limits, call an electrician.
Test capacitor.
Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
Fan motor noise.| Fan| If cracked, out of balance, or partially missing, replace it.
Blower| If cracked, out of balance, or partially missing, replace it.
Loose clamper| Tighten it.
Worn bearings| If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
Compressor will not run, but fan motor runs.| Voltage| Check voltage.
If not within limits, call an electrician.
Wiring| Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
Rotary| Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
Compressor will not run, but fan motor runs.| Thermostat| Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit.
Check continuity of the thermostat. Replace thermostat if circuit is open.
---|---|---
Capacitor (Discharge capacitor before servicing.)| Check the capacitor.
Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.
Compressor| Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Overload| Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Compressor cycles on overload.| Voltage| Check the voltage.
If not within limits, call an electrician.
Overload| Check overload, if externally mounted.
Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
Compressor cycles on overload.| Fan motor| If not running, determine the cause. Replace if required.
Condenser air flow restriction| Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush.
Clean the interior base before reassembling.
Condenser fins (damaged)| If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to overload. Straighten the fins or replace the coil.
Compressor cycles on overload.| Capacitor| Test capacitor.
Wiring| Check the terminals. If loose, repair or replace.
Refrigerating system| Check the system for a restriction.
Insufficient cooling or heating| Air filter| If restricted, clean of replace.
Exhaust damper door| Close if open.
Unit undersized| Determine if the unit is properly sized for the area to be cooled.
Excessive noise| Blower or fan| Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts.
Copper tubing| Remove the cabinet carefully and rearrange tubing not to contact cabinet, compressor, shroud, and barrier.

SCHEMATIC DIAGRAM

CIRCUIT DIAGRAM

  • MODEL : CW-XC103HU, CW-XC123H, UCW-XC143HU, CW-XC118HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(53\)

LOCATION NO. DESCRIPTION Q’TY PER SET
1 POWER CORD ASSY 1
2 MOTOR ASSY 1
3 COMPRESSOR 1
4 MAIN P.W.B ASSY 1
5 DISPLAY P.W.B ASSY 1
6 THERMISTOR 1
7 CAPACITOR 1
8 CONNECTOR ASSY 1
9 OVERLOAD PROTECTOR 1
10 MOTOR ASSY, SYNC. 1

ELECTRONIC CONTROL DEVICE

  • MODEL: CW-XC118HU, CW-XC103HU, CW-XC123HU, CW-XC143HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(54\)

SYNC MOTOR : CW-XC103HU, CW-XC123HU, CW-XC143HU only.

COMPONENTS LOCATION(FOR MAIN P.C.B ASM)

  • MODEL: CW-XC118HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(55\)

  • MODEL: CW-XC103HU, CW-XC123HU, CW-XC143HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(56\)

COMPONENTS LOCATION(FOR DISPLAY P.C.B ASM)

  • MODEL: CW-XC118HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(57\)

  • MODEL: CW-XC103HU, CW-XC123HU, CW-XC143HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(58\)

EXPLODED VIEW

  • MODEL: CW-XC1118HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(59\)

  • MODEL: CW-XC103HU, CW-XC123HU, CW-XC143HU

Panasonic-CW-XC103HU-Room-Air-Conditioner-\(60\)

REPLACEMENT PARTS LIST

R : Recommendable parts.

LOCATION NO . DESCRIPTION PART NO. REMARK
CW- XC103HU CW- XC118HU CW- XC123HU CW-

XC143HU
A| FRONT GRILLE ASS’Y| CW353110188A| CW353110188B| CW353110188A| CW353110188A| R
1| GRILLE, FRONT| CW353010136A| CW353010136B| CW353010136A| CW353010136A|
2| INLET, GRILLE| CW353010137A| CW353010137B| CW353010137A| CW353010137A|
3| AIR FILTER ASS’Y| CW5231R1152M| CW5231R1152M| CW5231R1152M| CW5231R1152M|
4| HORIZONTAL LOUVER| CW4758R2196G| CW4758R2196B| CW4758R2196G| CW4758R2196G|
5| VERTICAL LOUVER| –| CW4758R3307C| –| –|
B| COMP&ACCESSORY ASS’Y| | | | |
1| ANTI-VIBRATION BUSH| CW4830R4335A| CW4830R4335A| CW4830R4335A| CW4H00982E|
2| COMPRESSOR| CW2520KAC2JA| CW2520KQC2AA| CW2520KQC2AA| CW2520KRC2AA| R
3| GASKET| CW4986-L001G| CW4986-L001G| CW4986-L001G| CW4986-L001G|
4| OVERLOAD PROTECTOR| CW6750-L031A| CW6750-L067A| CW6750-L067A| CW6750-L029A| R
5| TERMINAL COVER| CW3550-L006A| CW3550-L006A| CW3550-L006A| CW3550-L006A|
6| BASE PAN WELD ASS’Y| CW304120012R| CW304120012R| CW304120012R| CW304120012N|
7| BARRIER, SINGLE| CW479020022A| CW479020022A| CW479020022A| CW479020022A|
8| SCROLL| CW307220001A| CW307220001A| CW307220001A| CW307220001A|
9| AIR GUIDE ASSEMBLY| CW523910006D| CW523910006E| CW523910006D| CW523910006F|
10| CABINET ASS’Y| CW3091R2286F| CW3091R2286Z| CW3091R2286Z| CW3091R2286Y|
11| DAMPER, VENTILATION| CW4900R7024B| CW4900R7024B| CW4900R7024B| CW4900R7024B|
12| MOUNT, MOTOR| CW496020005A| CW496020005A| CW496020005A| CW4960R6165A|
13| MOTOR ASSEMBLY, SINGLE| CW468120073E| CW468120073B| CW468120073B| CW468120009Z| R
14| SHROUD| CW4998R1496A| CW4998R1496A| CW4998R1496A| CW499810004A|
15| FAN, TURBO| CW590020030A| CW590020030A| CW590020030A| CW590020029A| R
16| FAN, AXIAL| CW590010009B| CW590010009B| CW590010009B| CW5900R1173A| R
17| CLAMP, SPRING| CWL00027| CWL00027| CWL00027| CWL00027|
18| ORIFICE| CW494810005A| CW494810005A| CW494810005A| CW494810005A|
19| BRACE| CW480010001A| CW480010001A| CW480010001A| CW480010001A|
20| EVAPORATOR ASSEMBLY, FIRST| CW5421R6086B| CW5421R2912C| CW5421R2912C| CW5421R6086B|
21| CONDENSER ASSEMBLY, FIRST| CW5403R2921A| CW5403R2921A| CW5403R2921A| CW540320042M|
22| VERTICAL LOUVER| CW4758R2888B| –| CW4758R2888B| CW4758R2888B|
23| REMOTE CONTROLLER ASSEMBLY| CW671190018A| CW671190018C| CW671190018A| CW671190018A| R
24| OPERATING INSTRUCTION| CW382820046E| CW382820046E| CW382820046E| CW382820046E|
25| INSTALLATION KIT| CW312710015G| CW312710015G| CW312710015G| CW312710015G| R
26| UPPER GUIDE| CW4974R3262E| CW4974R3262E| CW4974R3262E| CW4974R3262E|
LOCATION NO .| DESCRIPTION| PART NO.| REMARK
---|---|---|---
CW- XC103HU| CW- XC118HU| CW- XC123HU| CW- XC143HU
C| CONTROL BOX ASSEMBLY| CW499520104Y| CW499520104Z| CW499520104X| CW499520104X|
1| CONTROL BOX , SINGLE| CW4994R1221B| CW4994R1221A| CW4994R1221B| CW4994R1221B|
2| CONTROL PANEL| CW372010003B| CW372010003A| CW372010003B| CW372010003B|
3| ESCUTCHEON| CW383120031Y| CW383120031Z| CW383120031Y| CW383120031Y|
4| CAPACITOR| CW6120R2194F| CW0CZZ20001N| CW0CZZ20001N| CW0CZZ20001N| R
5| POWER CORD ASS’Y| CW2H00677R| CW2H00677S| CW2H00677S| CW2H00677S| R
6| THERMISTOR| CW632320003D| CW632320003D| CW632320003D| CW632320003D| R
7| COVER| CW3550R7032A| CW3550R7032A| CW3550R7032A| CW3550R7032A|
8| MAIN PWB ASS’Y| CW687110070J| CW687110070K| CW687110070J| CW687110070J| R
9| DISPLAY PWB ASS’Y| CW687120195Q| CW687120195P| CW687120195Q| CW687120195Q| R
10| MOTOR ASS’Y, SYNC.| CW2H01102D| –| CW2H01102D| CW2H01102D| R
11| CABLE, FLAT| CW685090001H| CW685090001H| CW685090001H| CW685090001H|
D| PIPE| | | | |
1| TUBE ASSEMBLY, SUCTION INDOOR| CW5211R6081A| CW5211R2926A| CW5211R2926A| CW5211R6081G|
2| TUBE ASSEMBLY, DISCHARGE SINGLE| CW5211R2930A| CW5211R2930A| CW5211R2930A| CW521120805B|
3| TUBE, EVAPORATOR| CW5210R7062A| CW5210R7090B| CW5210R7090B| CW5210R7062A|
4| TUBE, EVAPORATOR| CW5210R7063A| CW5210R4373B| CW5210R4373B| CW5210R7063A|
5| TUBE ASSEMBLY, CONNECTOR| CW5211R7059W| CW5211R7059W| CW5211R7059W| CW5211R7059W|
6| TUBE, CAPILLARY BEND| CW5425R7133T| CW521120598E| CW521120598E| CW521120598D|
7| DRIER ASSEMBLY| CW585130001F| CW585130001F| CW585130001F| CW585130001F|

January, 2004 Printed in Korea

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals