Danfoss ETS 800P Manifold ETS Electric Expansion Valve Installation Guide

July 22, 2024
Danfoss

Danfoss ETS 800P Manifold ETS Electric Expansion Valve

Product Specifications

  • Product Name: Electric Expansion Valve, Manifold ETS Type ETS 800P ETS 1000P
  • Compatible Refrigerants: R134a, R404A, R407A, R407C, R407F, R407H, R410A, R417A, R422A, R422B, R422D, R438A, R442A, R448A, R449A, R449B, R450A, R452A, R463A, R507A, R513A, R513B, R515A, R515B, R1234ze(E)
  • Nominal Voltage: 12 V DC
  • Recommended Current: 400 mA at 200 pps

Product Usage Instructions

  1. Identify the components: Coils A and B, Screws X and T30.
  2. Assemble the coils on their respective positions – A1 and A2 for Coil A, B1 and B2 for Coil B.
  3. Secure the coils in place using Screws X and T30.

Safety Instructions

For R1234ze(E) refrigerant:

  • Evaluate ignition risk by ISO5149/EN378 and IEC60335-2-40 standards.
  • Avoid using the valve outside of specified temperature limits.
  • Do not unplug the valve when energized.
  • Install the valve in an appropriate enclosure to protect it from moisture, dust, dirt, and impact.
  • In regions where safety standards are not well-defined, seek third-party approval for systems with flammable refrigerants.

AQ

  • Q: What are the recommended refrigerants for this electric expansion valve?
  • A: The valve is compatible with a range of refrigerants including R134a, R404A, R407C, and more. Refer to the product manual for the complete list.
  • Q: What is the nominal voltage of the valve?
  • A: The nominal voltage is 12 V DC.
  • Q: Can the valve be used outside of specified temperature limits?
  • A: It is not recommended to use the valve outside of the stated temperature limits to ensure proper functionality and safety.

Compatible refrigerants

  • R134a, R404A, R407A, R407C, R407F, R407H,
  • R410A, R417A, R422A, R422B, R422D, R438A,
  • R442A, R448A, R449A, R449B, R450A,
  • R452A, R463A, R507A, R513A, R513B, R515A,
  • R515B, R1234ze(E)

NOTE: For more details, please check the datasheet.

Inlet fluid temperature

  • Min. -40 °C / -40 °F
  • Max. 70 °C / 158 °F

Max. working pressure

  • MWP = 37 bar / 536 psig

Stepper motor type

  • Bipolar

Allowable ambient temperature

  • Min. -40 °C / -40 °F
  • Max. 70 °C / 158 °F

Total number of steps

  • ETS 800P 3810 full steps
  • ETS 1000P 4999 full steps

Nominal voltage

  • 12 V DC

Resistance

  • 52.4 Ohm ±10% @ 25 OC

Phase current

  • Recommended: 400 mA at 200 pps

Flow Direction

ETS 800P / 1000P

Application

Mounting

Danfoss-ETS-800P-Manifold-ETS-Electric-Expansion-Valve-
FIG-3

Brazing

Danfoss-ETS-800P-Manifold-ETS-Electric-Expansion-Valve-
FIG-4

  • N2 gas from the opposite side of the soldering point.

Electrical connections

ETS 800P / 1000P

Danfoss-ETS-800P-Manifold-ETS-Electric-Expansion-Valve-
FIG-5

Disassembling

Danfoss-ETS-800P-Manifold-ETS-Electric-Expansion-Valve-
FIG-6

Assembling

Danfoss-ETS-800P-Manifold-ETS-Electric-Expansion-Valve-
FIG-7Danfoss-ETS-800P-Manifold-
ETS-Electric-Expansion-Valve-FIG-8

Warning

  • Do not connect directly to AC/DC power source. Connect the valve to the appropriate controller/driver only. Do not operate the valve while assembling or disassembling

Special note for R1234ze(E)

Ignition risk is evaluated in accordance to ISO5149/EN378 and IEC60335-2-40.

  • Do not use a valve outside of the stated temperature limits.
  • Do not unplug when energized
  • Must be installed in a suitable end-use enclosure to protect the valve electrical plug against moisture, dust, dirt and impact.
  • For countries where safety standards are not an indispensable part of the safety system, Danfoss recommends the installer to get a third-party approval of the system containing flammable refrigerant.

Danfoss-ETS-800P-Manifold-ETS-Electric-Expansion-Valve-
FIG-9

Any information, including, but not limited to information on the selection of the product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals catalogs descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to the form, fit, or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals