Simpson GIMA400 Digital Power Meters User Manual

June 3, 2024
Simpson

Simpson GIMA400 Digital Power Meters

Safety

The GIMA400 is intended for connection to dangerous voltages giving a risk of electric shock. Refer to the safety/installation instructions in the GIMA400 Installation Guide before connecting the communications.

WARNING

The meter contains no user serviceable parts. Installation and commissioning should only be carried out by qualified personnel

For further Information contact the manufacturer:
Address: Simpson Electric Company 520 Simpson Avenue Lac Du Flambeau, WI. (USA)
Web : www.simpsonelectric.com
Email: SimpsonSupport@simpsonelectric.com

Programming

Meters fitted with the Modbus option have two additional stages in the front panel programming menu.

To enter programming mode:

  • Hold and together for 5 Seconds.
  • Press repeatedly until the required setup page is displayed.

Simpson-GIMA400-Digital-Power-Meters-fig- \(3\)

For full information on entering and using programming mode refer to the latest “GIMA400

Connection

Cable Selection

A dedicated, screened twisted pair cable is required to provide basic RS485 connection. A second twisted pair may be used for 0V connection if required. The cable should be chosen to suit the data rate and maximum length to be installed. The EIA RS-485-A standard provides curves that relate cable length to data rate for 24 AWG screened, twisted pair, telephone cable with a shunt capacitance of 50pf/m. For baud rates up to 19,200 the standard suggests a maximum length of 1200m for this type of cable. If other types of cable are to be used it is recommended that the cable supplier is consulted as to the suitability for use with RS485 to 19,200 baud.

Signal 0V and Cable Shield

  • A signal 0V termination is provided on each meter. Although RS485 does not strictly require a signal 0V, it is recommended this is connected as shown in the diagram below. This creates a known reference for the isolated RS485 system thereby reducing potential common-mode errors in the meter’s RS485 driver circuit.
  • A cable shield is used to attenuate noise picked up from external sources. This should be continuous, and cover as much of the signal pairs as possible. It is recommended that the shield should be connected to ground at the host (PC) only. The cable shield should not be used as the 0V connection.

Terminating Resistors

In order to minimise signal errors due to noise over long cable lengths, terminating resistors may be fitted. These match the RS485 device impedance to that of the cable. Two 120 resistors, one at the host port terminals and the other at the most remote meter terminals are recommended for this purpose.

Connection To Meters

The bus wires should be taken to meters at each location for termination, using the meter terminals as a loop in-out connection. 3-Pairs of terminals, internally shorted, are provided for convenience. The use of spurs should be avoided wherever possible.

Basic ConnectionSimpson-GIMA400-Digital-Power-Meters-fig-
\(4\)

Protocol

Modbus Commands

The GIMA400 meter supports the following standard Modbus commands

Command Function Broadcast
03 Read Multiple Holding Registers No
04 Read Multiple Input Registers No
06 Preset a Single Register Yes
08 (SF=00) Sub Function 00 only (Loop Back) No
16 Preset Multiple Registers Yes

Exception Responses

If the meter receives a Modbus command, with no errors and a valid address, it will attempt to handle the query and provide an appropriate response. If the meter cannot handle the query a standard Modbus exception response is sent (except broadcast queries). An exception response is characterised by its function byte which has 80H added to that sent in the query. The following exceptions codes are supported:

Code Function
1 Preset data is out of range for parameter
2 Function cannot access requested register address

Modbus Data Tables

Using The Tables

For convenience, meter data is organised in tables of like information with the same format. An entire table may be read with a single Modbus command 3 (Holding Registers). For compatibility with the Modbus standard each register contains a single data Word (16 bits). Data in the meter is stored as:

Unsigned Integer (U-INT)

16-bit data in the range 0 to 65,535. This is used for parameters such as CT prim as this can never be negative.

Signed Integer (S-INT)

16-bit data in the range –32,768 to +32,767. This is used for parameters such as instantaneous kW, which may have a negative value indicating export power.

Long Integer (LONG)

32-bit data in the range 0 to 4,294,967,295. This is used for parameters such as kWh, which may have large values. Each LONG requires two consecutive Modbus data words. Standard software often handles long integer reads, however, a LONG may be calculated from the individual data words as:

Energy Registers

Data Address| Modbus Register| Data| Access
---|---|---|---
512| 40513| eScale High Word| Read Only
513| 40514| eScale Low Word
514| 40515| kWh High Word| Read/Write
515| 40516| kWh Low Word
516| 40517| kVAh High Word| Read/Write
517| 40518| kVAh Low Word
518| 40519| kvarh Inductive High Word| Read/Write
519| 40520| kvarh Inductive Low Word
520| 40521| kvarh Capacitive High Word| Read/Write
521| 40522| kvarh Capacitive Low Word
522| 40523| Import kvarh High Word| Read/Write
523| 40524| Import kvarh Low Word
524| 40525| Export kWh High Word| Read/Write
525| 40526| Export kWh Low Word
526| 40527| Export kvarh High Word| Read/Write
527| 40528| Export kvarh Low Word
528| 40529| Hours Run High Word| Read/Write
529| 40530| Hours Run Low Word

Energy registers are stored as long integer representations of the number displayed on the meter
without decimal point or scaling. For example if the meter displays 123456.78kWh, the Holding Registers 40515-40516 will contain the long integer 12345678. This number may be scaled in Wh or kWh, using eScale as:

  • Wh = Holding Reg[40516] x 10(eScale-3)
  • kWh = Holding Reg[40516] x 10(eScale-6)

The eScale constant is set, along with the kWh register resolution and scaling, by the CT primary and nominal voltage programmed settings. The display scaling and eScale therefore remain constant once a meter is installed and commissioned. A read of eScale High Word always returns zero.

Example:

If the meter displays 1234567.8 kWh then eScale would be 5 and the Holding Registers 40515- 40516 would contain 12345678.

The host would calculate the scaled energy reading as:

12345678 x 10(5-3) = 12345678 x 100 = 1,234,567,800 Wh or 12345678 x 10(5-6) = 12345678 x 0.1 = 1,234,567.8 kWh

The host programmer could take two approaches to interpreting the data from the meter:

  • Enter a fixed scaling factor (x100 for Wh or x0.1 for kWh in above example). This would be set for each meter in the system based on its display after commissioning.
  • Use the transmitted eScale constant, as shown above, to automatically position the decimal point in the interpreted result.

Instantaneous Meter Values

Data Address| Modbus Register| Data| Scaling
---|---|---|---
2816| 42817| System kW| Kp
2817| 42818| System kVA| Kp
2818| 42819| System kvar| Kp
2819| 42820| System PF| 1000 = 1.000
2820| 42821| Frequency| 500 = 50.0
2821| 42822| Phase 1 Volts| Kvp
2822| 42823| Phase 1 Amps| Ki
2823| 42824| Phase 1 kW| Kp
2824| 42825| Phase 2 Volts| Kvp
2825| 42826| Phase 2 Amps| Ki
2826| 42827| Phase 2 kW| Kp
2827| 42828| Phase 3 Volts| Kvp
2828| 42829| Phase 3 Amps| Ki
2829| 42830| Phase 3 kW| Kp
2830| 42831| Phase 1 PF| 1000 = 1.000
2831| 42832| Phase 2 PF| 1000 = 1.000
2832| 42833| Phase 3 PF| 1000 = 1.000
2833| 42834| Ph1-Ph2 Volts| Kvl
2834| 42835| Ph2-Ph3 Volts| Kvl
2835| 42836| Ph3-Ph1 Volts| Kvl
2836| 42837| Neutral Current| Ki
2837| 42838| Amps Scale Ki| –
2838| 42839| Phase Volts Scale Kvp| –
2839| 42840| Line Volts Scale Kvl| –
2840| 42841| Power Scale Kp| –

Note: All registers in this table have read only access.

Instantaneous readings are provided as signed integer values with no decimal point or legend (e.g. kW or MW). Scaling factors are provided to enable conversion of the raw data to real numbers inbasic unit form (amps, volts, watts, VA, or var). These scaling factors are constant values calculated as a function of CT and PT Primary programming. To convert raw data to real numbers

  • R = I x 10(K-3)

Where:

  • I = Integer number
  • K = Relevant Scaling Factor
  • R = Real number result

Example:

  • If the meter is programmed with CT Primary=50Amps and PT Primary=415V:
  • LCD values would be scaled as: 50.00A, 240.0V, 415.7VLL and 36.00kW.
  • Scaling factors would be: I Scale=1, Kvp=2, Kvl=2, Kp=4.
  • Integer Values would be transmitted as: 5000, 2400, 4157 and 3600
  • Amps would be calculated as 5000 x 10(1-3) = 5000/100 = 50.00A
  • Phase Volts would be calculated as 2400 x 10(2-3) = 2400/10 = 240.0V
  • Line Volts would be calculated as 4157 x 10(2-3) = 4157/10 = 415.7V
  • 3-Ph Power would be calculated as 3600 x 10(4-3) = 3600×10 = 36000W

Additional Instantaneous Values

Data Address| Modbus Register| Data| Scaling
---|---|---|---
3072| 43073| Phase 1 kVA| Kp
3073| 43074| Phase 2 kVA| Kp
3074| 43075| Phase 3 kVA| Kp
3075| 43076| Phase 1 kvar| Kp
3076| 43077| Phase 2 kvar| Kp
3077| 43078| Phase 3 kvar| Kp

Note : All values in this table are Signed Integers with read only access.

Peak Hold Values

Data Address| Modbus Register| Data| Scaling
---|---|---|---
3328| 43329| Peak Hold Ph1 Amps| Ki
3329| 43330| Peak Hold Ph2 Amps| Ki
3330| 43331| Peak Hold Ph3 Amps| Ki
3331| 43332| Peak Hold Ph1 Volts| Kvp
3332| 43333| Peak Hold Ph2 Volts| Kvp
3333| 43334| Peak Hold Ph3 Volts| Kvp
3334| 43335| Peak Hold kW Demand| Kp + 1
3335| 43336| KW Demand Period| 1-60 Minutes
3336| 43337| KW Demand| Kp + 1
3337| 43338| KVA Demand| Kp + 1
3338| 43339| Peak Hold kVA Demand| Kp + 1
3339| 43340| Kvar Demand| Kp + 1
3340| 43341| Peak Hold kvar Demand| Kp + 1

Note: All values in this table are Signed Integers(amps & Volts parameters) and unsigned integers ( power demands) with read/write access except 43337, 43338 and 43340 which have read only access.

Meter Setup

Data Address| Modbus Register| Data| Scaling
---|---|---|---
3584| 43585| CT Primary| 10 – 25,000 Amps
3585| 43586| Nominal Volts| 10 – 55,000 Volts
3586| 43587| Pulse 1 Rate| 1-1000 Counts/Pulse
3587| 43588| Pulse 2 Rate (= Pulse 1 Rate)| 1-1000 Counts/Pulse
3588| 43589| Baud| 96 = 9600baud etc
3589| 43590| Modbus ID| 0 – 247
3590| 43591| Meter Model| Cube400 = 400
3591| 43592| Meter Type| Basic Cube400 = 1
3592| 43593| Firmware Version| Eg. 0x14 = 1.04
3593| 43594| Current Demand Period| 1 = 10Sec, 2=20Sec etc
3594| 43595| Pulse ON Time| 1 = 100ms, 2=200ms etc
3595| 43596| Security Code| 0 – 9999
3596| 43597| Hours Run Limit| 0–9999kW (scaled as LCD)
3597| 43598| PT Scaling Factor| 1 – 10

Note: All values in this table are unsigned Integers with read/write access except 43591-43593 which are read only.
The overall PT Primary is calculated as: Nominal Volts X PT scaling factor

Peak Hold Current/Voltage Demand

Data Address| Modbus Register| Data| Scaling
---|---|---|---
3840| 43841| Peak Ph1 Amps Demand| Ki
3841| 43842| Peak Ph2 Amps Demand| Ki
3842| 43843| Peak Ph3 Amps Demand| Ki
3843| 43844| Peak Ph1 Volts Demand| Kvp
3844| 43845| Peak Ph2 Volts Demand| Kvp
3845| 43846| Peak Ph3 Volts Demand| Kvp

Note: All values in this table are Unsigned Integers with read/write access.

Current/Voltage Demand

Data Address| Modbus Register| Data| Scaling
---|---|---|---
4096| 44097| Ph1 Amps Demand| Ki
4097| 44098| Ph2 Amps Demand| Ki
4098| 44099| Ph3 Amps Demand| Ki
4099| 44100| Ph1 Volts Demand| Kvp
4100| 44101| Ph2 Volts Demand| Kvp
4101| 44102| Ph3 Volts Demand| Kvp

Note: All values in this table are Unsigned Integers with read only access

Total Harmonic Distortion Values

Data Address| Modbus Register| Data| Scaling
---|---|---|---
4352| 44353| V1 % THD| 1000 = 100%
4353| 44354| V2 % THD| 1000 = 100%
4354| 44355| V3 % THD| 1000 = 100%
4355| 44356| I1 % THD| 1000 = 100%
4356| 44357| I2 % THD| 1000 = 100%
4357| 44358| I3 % THD| 1000 = 100%

Note: All values in this table are Unsigned Integers with read only access.

Power Demand Values

Data Address| Modbus Register| Data| Scaling
---|---|---|---
4608| 44609| kW Demand| Kp + 1
4609| 44610| kVA Demand| Kp + 1
4610| 44611| Kvar Demand| Kp + 1
4611| 44612| Peak Hold kW Demand| Kp + 1
4612| 44613| Peak Hold kVA Demand| Kp + 1
4613| 44614| Peak Hold kvar Demand| Kp + 1

Note: All values in this table are signed Integers. Demand values have read only access while peak hold values have read/write access

Amalgamated Data Table

Data Address Modbus Register Data Scaling
7680 47681 KWh High Word Ke
7681 47682 KWh Low Word
7682 47683 KVAh High Word Ke
7683 47684 KVAh Low Word
7684 47685 Kvarh High Word Ke
7685 47686 Kvarh Low Word
7686 47687 Export kWh High Word Ke
7687 47688 Export kWh Low Word
7688 47689 Phase 1 Amps __

Ki

7689| 47690| Phase 2 Amps
7690| 47691| Phase 3 Amps
7691| 47692| Phase 1 Volts| __

Kvp

7692| 47693| Phase 2 Volts
7693| 47694| Phase 3 Volts
7694| 47695| Ph1-Ph2 Volts| __

Kvl

7695| 47696| Ph2-Ph3 Volts
7696| 47697| Ph3-Ph1 Volts
7697| 47698| Frequency| 500 = 50.0
7698| 47699| Phase 1 PF| __

1000 = 1.000

7699| 47700| Phase 2 PF
7700| 47701| Phase 3 PF
7701| 47702| System PF
7702| 47703| Phase 1 kW| __

Kp

7703| 47704| Phase 2 kW
7704| 47705| Phase 3 kW
7705| 47706| System kW
7706| 47707| Phase 1 kVA| __

Kp

7707| 47708| Phase 2 kVA
7708| 47709| Phase 3 kVA
7709| 47710| System kVA
7710| 47711| Phase 1 kvar| __

Kp

7711| 47712| Phase 2 kvar
7712| 47713| Phase 3 kvar
7713| 47714| System kvar
7714| 47715| Ph1 Amps Demand| __

Ki

7715| 47716| Ph2 Amps Demand
7716| 47717| Ph3 Amps Demand
7717| 47718| Ph1 Volts Demand| __

Kvp

7718| 47719| Ph2 Volts Demand
7719| 47720| Ph3 Volts Demand
7720| 47721| Peak Ph1 Amps| __

Ki

7721| 47722| Peak Ph2 Amps
7722| 47723| Peak Ph3 Amps
7723| 47724| Peak Ph1 Volts| __

Kvp

7724| 47725| Peak Ph2 Volts
7725| 47726| Peak Ph3 Volts
7726| 47727| kW Demand| __

Kp + 1

7727| 47728| kVA Demand
7728| 47729| kvar Demand
7729| 47730| Peak Hold kW Demand| __

Kp + 1

7730| 47731| Peak Hold kVA Demand
7731| 47732| Peak Hold kvar Demand
7732| 47733| Neutral Current| Ki
7733| 47734| Amps Scale Ki| –
7734| 47735| Phase Volts Scale Kvp| –
7735| 47736| Line Volts Scale Kvl| –
7736| 47737| Power Scale Kp| –
7737| 47738| Energy Scale Ke| –

Note: All values in this table have read only access.

The amalgamated data table provides a copy of key variables in a single table, which may be read with a single Modbus command. The format and scaling of each parameter is identical to that found in the main tables

V1 Harmonics

Data Address| Modbus Register| Data| Scaling
---|---|---|---
7936| 47937| V1: 2nd Harmonic| 1000 = 100%
7937| 47938| V1: 3rd Harmonic| 1000 = 100%
7938| 47939| V1: 4th Harmonic| 1000 = 100%
7939| 47940| V1: 5th Harmonic| 1000 = 100%
7940| 47941| V1: 6th Harmonic| 1000 = 100%
7941| 47942| V1: 7th Harmonic| 1000 = 100%
7942| 47943| V1: 8th Harmonic| 1000 = 100%
7943| 47944| V1: 9th Harmonic| 1000 = 100%
7944| 47945| V1: 10th Harmonic| 1000 = 100%
7945| 47946| V1: 11th Harmonic| 1000 = 100%
7946| 47947| V1: 12th Harmonic| 1000 = 100%
7947| 47948| V1: 13th Harmonic| 1000 = 100%
7948| 47949| V1: 14th Harmonic| 1000 = 100%
7949| 47950| V1: 15th Harmonic| 1000 = 100%

V2 Harmonics

Data Address| Modbus Register| Data| Scaling
---|---|---|---
8192| 48193| V2: 2nd Harmonic| 1000 = 100%
8193| 48194| V2: 3rd Harmonic| 1000 = 100%
8194| 48195| V2: 4th Harmonic| 1000 = 100%
8195| 48196| V2: 5th Harmonic| 1000 = 100%
8196| 48197| V2: 6th Harmonic| 1000 = 100%
8197| 48198| V2: 7th Harmonic| 1000 = 100%
8198| 48199| V2: 8th Harmonic| 1000 = 100%
8199| 48200| V2: 9th Harmonic| 1000 = 100%
8200| 48201| V2: 10th Harmonic| 1000 = 100%
8201| 48202| V2: 11th Harmonic| 1000 = 100%
8202| 48203| V2: 12th Harmonic| 1000 = 100%
8203| 48204| V2: 13th Harmonic| 1000 = 100%
8204| 48205| V2: 14th Harmonic| 1000 = 100%
8205| 48206| V2: 15th Harmonic| 1000 = 100%

V3 Harmonics

Data Address| Modbus Register| Data| Scaling
---|---|---|---
8448| 48449| V3: 2nd Harmonic| 1000 = 100%
8449| 48450| V3: 3rd Harmonic| 1000 = 100%
8450| 48451| V3: 4th Harmonic| 1000 = 100%
8451| 48452| V3: 5th Harmonic| 1000 = 100%
8452| 48453| V3: 6th Harmonic| 1000 = 100%
8453| 48454| V3: 7th Harmonic| 1000 = 100%
8454| 48455| V3: 8th Harmonic| 1000 = 100%
8455| 48456| V3: 9th Harmonic| 1000 = 100%
8456| 48457| V3 10th Harmonic| 1000 = 100%
8457| 48458| V3: 11th Harmonic| 1000 = 100%
8458| 48459| V3: 12th Harmonic| 1000 = 100%
8459| 48460| V3: 13th Harmonic| 1000 = 100%
8460| 48461| V3: 14th Harmonic| 1000 = 100%
8461| 48462| V3: 15th Harmonic| 1000 = 100%

I1 Harmonics

Data Address| Modbus Register| Data| Scaling
---|---|---|---
8704| 48705| I1: 2nd Harmonic| 1000 = 100%
8705| 48706| I1: 3rd Harmonic| 1000 = 100%
8706| 48707| I1: 4th Harmonic| 1000 = 100%
8707| 48708| I1: 5th Harmonic| 1000 = 100%
8708| 48709| I1: 6th Harmonic| 1000 = 100%
8709| 48710| I1: 7th Harmonic| 1000 = 100%
8710| 48711| I1: 8th Harmonic| 1000 = 100%
8711| 48712| I1: 9th Harmonic| 1000 = 100%
8712| 48713| I1: 10th Harmonic| 1000 = 100%
8713| 48714| I1: 11th Harmonic| 1000 = 100%
8714| 48715| I1: 12th Harmonic| 1000 = 100%
8715| 48716| I1: 13th Harmonic| 1000 = 100%
8716| 48717| I1: 14th Harmonic| 1000 = 100%
8717| 48718| I1: 15th Harmonic| 1000 = 100%

I2 Harmonics

Data Address| Modbus Register| Data| Scaling
---|---|---|---
8960| 48961| I2: 2nd Harmonic| 1000 = 100%
8961| 48962| I2: 3rd Harmonic| 1000 = 100%
8962| 48963| I2: 4th Harmonic| 1000 = 100%
8963| 48964| I2: 5th Harmonic| 1000 = 100%
8964| 48965| I2: 6th Harmonic| 1000 = 100%
8965| 48966| I2: 7th Harmonic| 1000 = 100%
8966| 48967| I2: 8th Harmonic| 1000 = 100%
8967| 48968| I2: 9th Harmonic| 1000 = 100%
8968| 48969| I2: 10th Harmonic| 1000 = 100%
8969| 48970| I2: 11th Harmonic| 1000 = 100%
8970| 48971| I2: 12th Harmonic| 1000 = 100%
8971| 48972| I2: 13th Harmonic| 1000 = 100%
8972| 48973| I2: 14th Harmonic| 1000 = 100%
8973| 48974| I2: 15th Harmonic| 1000 = 100%

I3 Harmonics

Data Address| Modbus Register| Data| Scaling
---|---|---|---
9216| 49217| I3: 2nd Harmonic| 1000 = 100%
9217| 49218| I3: 3rd Harmonic| 1000 = 100%
9218| 49219| I3: 4th Harmonic| 1000 = 100%
9219| 49220| I3: 5th Harmonic| 1000 = 100%
9220| 49221| I3: 6th Harmonic| 1000 = 100%
9221| 49222| I3: 7th Harmonic| 1000 = 100%
9222| 49223| I3: 8th Harmonic| 1000 = 100%
9223| 49224| I3: 9th Harmonic| 1000 = 100%
9224| 49225| I3: 10th Harmonic| 1000 = 100%
9225| 49226| I3: 11th Harmonic| 1000 = 100%
9226| 49227| I3: 12th Harmonic| 1000 = 100%
9227| 49228| I3: 13th Harmonic| 1000 = 100%
9228| 49229| I3: 14th Harmonic| 1000 = 100%
9229| 49230| I3: 15th Harmonic| 1000 = 100%

Custom Data Table

This provides a custom table containing 32 Modbus registers, selected and arranged to suit individual requirements.
To set up a custom table first write the Data Addresses of the required parameters to the following Modbus table.

Data Address| Modbus Register| Data| Example
---|---|---|---
19200| 419201| Custom Address 0| 514| kWh High Word
19201| 419202| Custom Address 1| 515| kWh Low Word
19202| 419203| Custom Address 2| 516| kVAh High Word
19203| 419204| Custom Address 3| 517| kVAh Low Word
19204| 419205| Custom Address 4| 518| kvarh Inductive High Word
19205| 419206| Custom Address 5| 519| kvarh Inductive Low Word
19206| 419207| Custom Address 6| 520| kvarh Capacitive High Word
19207| 419208| Custom Address 7| 521| kvarh Capacitive Low Word
19208| 419209| Custom Address 8| 522| Import kvarh High Word
19209| 419210| Custom Address 9| 523| Import kvarh Low Word
19210| 419211| Custom Address 10| 524| Export kWh High Word
19211| 419212| Custom Address 11| 525| Export kWh Low Word
19212| 419213| Custom Address 12| 526| Export kvarh High Word
19213| 419214| Custom Address 13| 527| Export kvarh Low Word
19214| 419215| Custom Address 14| 2816| System kW
19215| 419216| Custom Address 15| 2817| System kVA
19216| 419217| Custom Address 16| 2818| System kvar
19217| 419218| Custom Address 17| 2819| System PF
19218| 419219| Custom Address 18| 2820| Frequency
19219| 419220| Custom Address 19| 2821| Phase 1 Volts
19220| 419221| Custom Address 20| 3331| Peak Hold Ph1 Volts
19221| 419222| Custom Address 21| 2824| Phase 2 Volts
19222| 419223| Custom Address 22| 3332| Peak Hold Ph2 Volts
19223| 419224| Custom Address 23| 2827| Phase 3 Volts
19224| 419225| Custom Address 24| 3333| Peak Hold Ph3 Volts
19225| 419226| Custom Address 25| 2822| Phase 1 Amps
19226| 419227| Custom Address 26| 3328| Peak Hold Ph1 Amps
19227| 419228| Custom Address 27| 2825| Phase 2 Amps
19228| 419229| Custom Address 28| 3329| Peak Hold Ph2 Amps
19229| 419230| Custom Address 29| 2828| Phase 3 Amps
19230| 419231| Custom Address 30| 3330| Peak Hold Ph3 Amps
19231| 419232| Custom Address 31| 3584| CT Primary

Write 514 to Modbus Register 419201 etc. The Data Addresses may be any valid Modbus register address listed in the above tables. Data Addresses in this table have read/write access. The corresponding Modbus Parameters pointed to by Data Address 0 – Data Address 31 are available at Modbus Addresses 419457 – 419488 (Data Addresses 19456 – 19487).

Specification

  • Aux Mains
    • Internally supplied from GIMA400 Auxiliary
    • Requires additional 1W max
  • Modbus
    • RS485 Half duplex, 2 Wires + 0V
    • RX Load : ¼ Unit load per meter (max 128 per bus)
    • TX Drive : 32 Unit loads maximum
    • Protocol: Modbus RTU/JBUS, 16-Bit CRC
    • Baud: 4800, 9600, 19200 user programmable
    • Address: 1-247 user programmable
  • Isolation
    • 3.5kV (1 minute) RS485 Port from all other circuit
  • Performance
    • Reply: Maximum 250ms
    • Rate: Min 5ms from reply to next request
    • Data: Meter readings & programmable settings
    • Maximum data length 20 Words.
  • General
    • Environmental: Refer to GIMA400 specification
    • Dimensions: Add 10mm to depth of GIMA400
    • Terminals: Rising clamp, max wire 4mm2

SIMPSON ELECTRIC COMPANY 520 Simpson Avenue Lac Du Flambeau, WI 54538 715-588-3311
Part #06-118352 Rev 01, 09/29/21

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Simpson User Manuals

Related Manuals