GENERAL SSCB15-GRY Series Ceiling Mounted Electronic Air Cleaner Installation Guide
- July 8, 2024
- GENERAL
Table of Contents
- SSCB15-GRY Series Ceiling Mounted Electronic Air Cleaner
- SAFETY CONSIDERATIONS
- WHAT THE ELECTRONIC AIR CLEANER DOES
- BENEFITS
- HOW IT WORKS
- MAJOR COMPONENTS
- INSTALLATION
- OPERATION & MAINTENANCE
- SERVICE
- ELECTRONIC AIR CLEANER LIMITED ONE YEAR WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- 3 – White
- 4 – Red
- 5 – Yellow
- 6 – Black
GENERAL
SSCB15-GRY
Owner’s Manual
SSCB15-GRY Series Ceiling Mounted Electronic Air Cleaner
This Owner’s Manual is provided and hosted by Appliance Factory
Parts.
Shop genuine replacement parts for GENERAL
SSCB15-GRY
Find Your GENERAL Air Cleaner Parts – Select From 69
Models
——– Manual continues below ——–
Operation And Maintenance Manual
SSCB-15 SERIES
CEILING MOUNTED
ELECTRONIC AIR CLEANER
IMPORTANT: PLEASE READ MANUAL BEFORE INSTALLING, OPERATING, CLEANING OR
SERVICING UNIT IMPORTANT: Please read entire instructions before
installing the Electronic Air Cleaner.
Certified for shock and electrical fire hazard only.
SAFETY CONSIDERATIONS
Read and follow instructions carefully. Follow all local electrical codes
during installation. All wiring must conform to local and national electrical
codes. Improper wiring or installation may damage the Air Cleaner.
Understand the signal words WARNING and CAUTION which are present in the
Installation, Operation & Service Instructions.
WARNING and CAUTION signifies a hazard which could result in property damage,
personal injury or death.
WARNING
Before beginning any installation or modification, be certain that the main
line electrical disconnect switch is in OFF position. Electric shock could
result. Tag disconnect switch with suitable warning labels.
Installation and servicing of Electronic Air Cleaners can be hazardous. Only
trained and qualified service personnel should install, repair, or service
Electronic Air Cleaners.
Untrained personnel can perform the basic maintenance functions of cleaning
and replacing filters.
When working on air cleaning equipment, observe precautions in the manual,
labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
WHAT THE ELECTRONIC AIR CLEANER DOES
Your High Efficiency Electronic Air Cleaner has been designed to remove
tobacco smoke particles, cooking smoke and grease, atmospheric dust, coal
dust, insecticide dust, mites, pollen, mold spores, fungi, bacteria, viruses
and more down to 0.01 micron (0.01
micron = 1/2,540,000 of an inch).
BENEFITS
Helps clear up a smokey environment quickly, so customers can dine more
comfortably.
Helps employees reduce suffering from irritated eyes, nasal congestion and
respiratory problems that lead to absenteeism.
Helps prevent damaging black and greasy particles from staining ceilings,
walls and furnishings, reducing the amount of housekeeping and redecorating
costs.
Helps to lower energy bills by recycling air rather than exhausting expensive
heated or cooled air.
HOW IT WORKS
This Air Cleaner works on the principle of “Electrostatic Precipitation”.
Millions of airborne pollutants are drawn through the intake grill on the
bottom of the Air
Cleaner and first pass through a Prefilter which removes all large visible
particles such as lint. Next, smaller particles move to a two-stage
electrostatic Collecting Cell where they are given a powerful positive charge
by the ionizing wires. Charged particles then move into the collecting area
where they are attracted to a series of grounded plates. Pollutants are held
in this section like a magnet until washed away during cleaning. Clean air is
then dispersed from the side grills in four directions allowing superior air
flow circulation.
The Air Cleaner creates a circular air flow pattern which never allows air to
rest at the ceiling.
MAJOR COMPONENTS
Description
The Electronic Air Cleaner is approximately 29½ x 27 x 14½ inches (75 x 68.6 x
37 cm). The unit is designed to be mounted to the ceiling. The steel cover and
intake grill are hinged to allow easy access to the collecting cells and power
box. The unit is rated up to 1300 CFM (2210 m3 /hr).
Cabinet
The cabinet is constructed of 20 gauge steel. The external parts have a tough
powder-coated, scratchresistant finish. The internal parts are galvanized
steel. Access to the collecting cells, power box and prefilters is made by
lifting the cover, sliding towards the front and lowering. The cover is
interlocked to cut power to the unit when opened.
Prefilters
The washable prefilters measuring 12½ x 20 inches (31.75 x 50.8 cm) are
constructed of multi-layers of aluminum mesh for maximum filtration of large
particles.
Collecting Cells
The dual voltage collecting cells are constructed of heavy gauge aluminum to
resist rust and damage. The first stage, the ionizing section, is charged at
approximately 7500 VDC. The collecting plates are alternately grounded and
charged at 5000 VDC. The arrow on the cell indicates the direction of air flow
which must point up towards the fan motor.
Motor & Fan Blade
The motor is 1/12 HP, 1050 RPM, 3 speed, controlled by a 3-position slide
switch. The motor is thermally protected. The fan blade is aluminum, 18 inches
(45.7 cm) with a 16˚ pitch.
INSTALLATION
- Read instructions carefully. Failure to do so may result in product damage or injury.
- Make sure the sizing is correct for your application.
- Installation should be done by a knowledgeable technician.
- After installation, check out operation as provided in these instructions.
Mounting
- Remove the unit from the box with packing still on the unit and lay it on its back, grill side up.
- Release the cover by sliding towards the front of the unit and lifting up.
- Remove the “S” hook from each chain, tilt cover up, and release from back.
- Remove the cells and prefilters from the unit before installing.
- Holes are provided in the cabinet to accommodate 5/16 inch (8 mm) threaded rod. Threaded rod can be attached to angle iron, laid across the joists, and drilling holes through these supports. Pass threaded rod up through the supports and secure with two nuts and washers. This will allow adjustment of the unit so that it is flush with the underside of the ceiling. Leave enough room around the Air Cleaner for removal of collecting cells and prefilters.
- Replace the cells, prefilters and cover. Hook up the safety chain to the cover.
Do not hang the unit with chain only. This will not give the unit the necessary stability when removing the cells or servicing the unit.
Wiring
WARNING
Electrical shock can cause injury or death. Be certain main line disconnect
switch is off before wiring.
All wiring must comply with applicable codes and standards. See unit rating
label for correct voltage and amperage.
- A knockout is provided on top of the unit, adjacent to the wiring compartment. For convenience, a wall switch may be installed near the Air Cleaner, in series with the power source, to turn the unit on and off.
- Remove the cover of the wiring compartment to locate the input leads and ground stud. The Air Cleaner must be grounded for proper operation and safety.
- Once the unit is mounted and wired, the cover can be replaced on the hinge and the chain replaced on the “S” hooks. Close the cover by sliding it forward, lifting the cover over the front flange and sliding it back into place.
For information on wiring the remote switch control see page 7.
OPERATION & MAINTENANCE
Operation Check
- With both cells and prefilters in place and the cover closed, turn the system switch ON.
- Adjust the fan speed with the slide switch. Insure the unit functions on all speeds.
- The performance light should be ON, which indicates the power board is functioning properly.
- If the unit is not functioning properly see the “Troubleshooting Guide”
When the Air Cleaner is new it may arc or periodically make “snapping sounds”. A slight odor of ozone may be noticeable. The arcing and odor are due to rough edges and burrs on the cells. These symptoms will disappear during the first few weeks of normal operation. The ozone levels are well below government standards for indoor air concentration.
Maintenance Schedule
The collecting cells and prefilters must be cleaned on a regular basis for the
unit to function at its peak efficiency. The frequency of cleaning will vary
from one environment to another. The following is an average wash cycle:
- Stores, Offices, Computer & Conference Rooms = 4 Weeks
- Cafeterias, Restaurants, Lounges = 3-4 Weeks
- Bars, Bingo halls = 1-3 Weeks
The unit should be checked on a regular basis to determine the frequency of
cleaning required in each location and a cleaning schedule established.
Cleaning
CAUTION
Make sure Air Cleaner switch is OFF before performing any maintenance or
removing any components.
- Turn off the system switch and wait 15 seconds for high voltage to dissipate.
- Open the cover and cell access door and remove collecting cells and prefilters. Cell plates are sharp. Handle with care.
- Place cells in tub and spray completely with DAX Detergent, allowing detergent to run down both sides of plates and ionizing wires. Let sit for 5 minutes. Rinse cells well with hot water (140ºF / 60ºC maximum). Repeat washing process if necessary.
- If dirt or nicotine remains on plates, let cells soak in hot soapy water for 30 minutes. Never use any instrument to clean the cell, as this may damage the ionizing wires or bend cell plates.
- Spray prefilters with DAX Detergent and rinse well.
- To dry cells, tilt on 45º angle against wall with the arrow pointing sideways. Allow to dry completely for 10-24 hours. Place in sunlight for faster drying time.
- When the cells and prefilters are dry, place them back into the unit. The arrow on the cell points up. The red fiberboard on the cell should line up with the contacts in the cabinet. Close door and cover. If the cells arc when the switch is turned on or if the performance light does not come on, then the cells may be still wet. Allow more time for drying.
CAUTION
Damage to cells may occur if improperly handled or washed. Do not wash cells
in a dishwasher. Never use any object to clean between the cell plates, as
this may cause damage to plates or ionizing wires. Never place cell in oven to
dry. The edges of the cell may be sharp – handle with care.
Fig. 4 — DAX Detergent is available in 35 ounce (1 litre) spray bottles or 1
gallon (4.54 L) and 4.8 gallons (22 L) containers from your installer or
dealer.
The use of DAX Detergent is strongly recommended for cleaning as it is a
heavy-duty solution used expressly for removal of accumulated pollutants on
cell plates. If used as directed, DAX will not harm aluminum or steel. Any
problem arising out of the use of another cleaning agent will void the
warranty. Do not use detergents that are corrosive or abrasive or detergents
containing chlorine or ammonia.
SERVICE
WARNING
Electronic Air Cleaners use high voltage (low amperage). Only trained
personnel should perform service. USE CAUTION! Electric shock can cause injury
or death.
CAUTION
For most troubleshooting the cells should be removed from the Air Cleaner. A
short in one of the cells will cause the power board to shutdown and the
performance light will stay off. Unless otherwise directed remove the cells
from the unit when testing.
The Air Cleaner when operating normally will have the fan running and the
performance indicator light ON. If this is not the case the see the
Troubleshooting Guide for probable causes and remedies.
WARNING
When performing LIVE tests in the power box NEVER touch any parts other then
what are mentioned in the tests. Components carry dangerous voltages and
extreme care must be taken.
Testing For High Voltage At Power Board
For the following test you will need to have the hinged cover open with the
collecting cells out of the unit.
- Remove the cover panel to the power box. Push a screwdriver into the slot to defeat the interlock switch and turn the Air Cleaner ON.
- With a long shafted screwdriver, with a plastic handle, short between the grounded side of the power box and the HV1 terminal of the power board.
- If you draw a good spark, there is high voltage fromthe power board.
Measuring High Voltage At Power Board
A high voltage meter capable of measuring up to 10,000 VDC is required to test
the voltage.
-
The Air Cleaner should be ON with the cells installed and the cell access door closed. The Air Cleaner should be on at least 5 minutes to allow voltage to stabilize.
-
Open the hinged cover. Remove the cover panel from power box and leave the hinged cover open.
-
Connect the ground of the high voltage meter to ground stud in the power box.
-
Turn the Air Cleaner ON, and defeat the interlock switch.
-
Check terminals HV1 and HV2 on the power board to determine if voltage is present. See Fig. 5 for values.
-
If no voltage is present, remove both cells from the Air Cleaner.
a. Check the voltage at HV1 and HV2 again.
b. If voltage is present, the problem is with one of the cells or the wiring to the copper contacts.
c. Check the condition of the copper contacts.
d. If the contacts are not bent, replace one cell and retest voltage. If the performance light come ON, test the other cell. If the problem is with a cell, see the Troubleshooting Guide.
e. If there is no voltage with both cells removed, check the power board, system switch and transformer to make sure that they are functioning correctly. -
If there is voltage present, but the performance light does not come on, replace the light.
-
High voltage can be adjusted with the high voltage potentiometer if required.
Replacing A Performance Light
Before replacing the performance light, turn OFF power to the Air Cleaner
at the source.
- Lower the cover and remove the power box cover panel.
- Disconnect the performance light wiring connected to the neon lamp terminals (P5 and P6) on the power board. Carefully cut the wire ties from the wire bundle.
- Push the light out through front of power box.
- Push the new light into the power box.
- Connect the wiring to the neon lamp terminals on the power board, P5 and P6. Route the wires away from the high voltage section of the power board.
- Replace cover panel and close the cover.
- Return power to Air Cleaner. Test light.
Replacing A Power Board
Before replacing the power board, turn OFF power to the Air Cleaner at the
source.
- Lower the cover and remove the power box cover panel.
- Disconnect wiring from the neon lamp, HV1, HV2 and 24 V terminals. Make note of position of wires.
- Remove the hex nuts from the power board.
- Remove the power board from the studs.
- Place the new board onto studs with the 24 volt input close to the transformer.
- Replace the hex nuts removed in Step 3. Ensure the star washer is in place over the nut at the ground location under the power board. For proper grounding the washer must be located under the power board.
- Reconnect wiring to neon lamp, HV1, HV2, and 24 V terminals on the new power board. See Fig. 5.
- Return power to Air Cleaner. Test power board.
- Replace power box cover panel and close cover.
Note: The power board has been set before shipping. It is not usually
necessary to reset the voltage to the new load. If you do need to adjust the
voltage refer to Setting Voltage of Power Board section for more information.
Testing The 24 V Transformer
- Remove the cover panel to the power box.
- Disconnect the leads of the 24 V transformer from the power board. See Fig. 5. Do not short the leads.
- Push a screwdriver into the slot to defeat the interlock switch and turn the Air Cleaner ON.
- Measure the voltage across the leads with a voltmeter. Voltage should read 25 – 28 VAC.
- If no voltage is present, check the voltage from the system switch.
- If there is voltage to the transformer but no output, replace the transformer.
Replacing The 24 V Transformer
Before replacing the transformer, check the resistance across the power board
24 V input terminals, without the transformer connected. Resistance should
read above 20K ohms with an analog meter and above 4M ohms with a digital
meter. If the resistance readings are below these values, the power board may
be the cause of the transformer failure.
Before replacing the 24 V transformer, turn OFF the power to the Air Cleaner
at the source.
- Remove the power box cover panel.
- Disconnect the secondary leads from the transformer to the 24 V terminals on the power board. See Fig. 5.
- Remove the black primary lead from the system switch. Remove the wire nut from the other primary lead.
- Remove the 2 hex head nuts and washers from the transformer studs.
- Remove the transformer.
- Place new transformer over studs and re-install the hex head nuts and washers to secure into place.
- Connect the secondary leads (white) to the 24 V terminals on the power board (P1 & P2).
- Place one black lead on the system switch terminal.
- Place the other black lead with the two white leads from the terminal block and connect with the wire nutyou removed earlier.
- Replace power box cover panel and close cover.
- Turn ON the power to the Air Cleaner and test.
Setting Voltage Of Power Board
Voltage on the power board may drop below required level when the installation
area is too damp, too cold or the input power to the unit is low. Voltage on
power board may be too high when the installation area is too dry or too hot
or the input power to the unit is high. By adjusting the HV Adj.
potentiometer, the voltage can be set to optimum level. A high voltage meter
capable of measuring 10,000 VDC is required. To test and adjust voltage level,
perform the following procedure:
- Turn the Air Cleaner OFF, with the cells in the unit.
- Remove the power box cover panel.
- Connect the ground of the high voltage meter to the ground stud in the power box.
- Turn the Air Cleaner ON and wait 5 minutes before checking voltage to allow voltage on cells to stabilize.
- Measure the voltage at HV1 and HV2 on the power board.
- Adjust the HV Adj. potentiometer until the voltage reading matches the voltage in Fig. 5. Adjusting the potentiometer clockwise decreases the voltage and turning counter-clockwise increases the voltage.
- Turn OFF the Air Cleaner.
- Remove the high voltage meter.
- Replace the power box cover panel and close cover.
- Turn ON the Air Cleaner.
Setting Approximate Voltage Without High Voltage Meter
A high voltage meter should be used to set the high voltage. If one is not
available, this method can be used.
This will only set an approximate voltage. After using this method, the
voltage should be reset with a high voltage meter as soon as possible.
-
Remove power box cover panel, with the cells in the unit.
-
Turn the HV Adj. potentiometer fully counterclockwise.
The Air Cleaner may arc or snap at this point. -
urn the HV Adj. potentiometer clockwise approximately a quarter turn.
-
Replace power box cover panel and close cover.
Testing for Voltage At The Cell
- Remove the power box cover panel.
- The cells must be in the Air Cleaner for this test.
- Turn the Air Cleaner ON and defeat the safety interlock switch.
- Place a plastic handled screwdriver into the direction arrow slot. Do not apply excessive force.
- If there is a good snap then there is high voltage at the cell.
Testing Cell For Bad Contacts
- Remove the power box cover panel.
- The cells must be in the Air Cleaner for this test.
- Turn the Air Cleaner ON and defeat the safety interlock switch.
- Place a plastic handled screwdriver into the direction arrow slot. Do not apply excessive force.
- There should be an initial snap when the plates are shorted, then no sound. If a hissing occurs, then there is a bad contact. Look along the top of the cell, with the short still in place. If there is a small arc between the cell top and copper contact, then that is the bad contact. Pull the cell out and gently pull the copper contact down.
- If an arc is not seen and there is a bad contact, then the problem may be an internal contact in one of the cells.
See below for additional testing.
Testing Cell With An Ohmmeter
To test the cell for a dead short or a bad contact an ohmmeter can be used.
Always discharge the cell with a screw driver before testing with an ohmmeter.
- With the ohmmeter set on its lowest scale take a reading between the top center contact of the cell and the ionizing fingers on the bottom of the cell. You should have continuity. If you do not then there is a bad contact between the center contact and the top set of ionizing fingers.
- Test the resistance between the top center contact and the cell frame. You should read infinite resistance. If not you have a short in the ionizing section.
- Take a reading between the two outside contacts on the top of the cell. You should have continuity. If you do not then there is a bad contact between one of the contacts to the live cell plate. Test each top outside contact to the last plate in the cell to determine which contact is not mating properly.
- Test the resistance between the outside contacts and the cell frame. You should read infinite resistance. If not you have a short in the collecting section.
Replacing A Tungsten Ionizing Wire
Replacement wires are cut to the correct length and have eyelets at each end
for easy replacement.
- Turn OFF power to Air Cleaner.
- Remove cell from Air Cleaner.
- Remove all parts of broken wire from the cell. If necessary, the cell may be used temporarily with one wire missing until a replacement is received.
- Place one end of the loop over the finger at the bottom of the cell.
- Using needle-nose pliers, grip the other end of wire, near the bottom of the top loop. Pull the wire up toward the top finger. As you apply tension, the bottom finger will give, allowing the placement of the loop around the top finger.
- Install cell in Air Cleaner.
- Return power to Air Cleaner.
- Test cell for proper operation.
Replacing A Fan Motor
-
Turn OFF power to Air Cleaner at the source.
-
Open the cover and remove the cell and prefilter from Air Cleaner.
-
Remove the fan blade from the motor shaft.
-
Remove the power box cover panel. Disconnect the four motor wires from the terminal block. Gently pull the wires up into the motor compartment.
-
Remove the four hex nuts holding the motor plate to the cabinet. Remove the motor and plate.
-
Remove the four hex nuts from the back of the motor plate to release the motor.
-
Replace the isolator rubbers on the motor plate.
-
Attach the new motor to the motor plate with a flat washer on both sides of the rubber isolator. Place the motor plate into the cabinet with the wires toward the plastic bushing to allow the wires to be feed to the power box.
-
Secure the motor plate to the cabinet.
-
Feed the motor wires down through the plastic bushing and secure to the terminal block.
3 – White
4 – Red
5 – Yellow
6 – Black
The white wire on units with a remote switch control use a wire nut instead of terminal #3.
-
Reinstall the fan blade, cell and prefilter.
-
Replace the power box cover panel and close the cover.
-
Turn ON the Air Cleaner and test the motor on all speeds.
REMOTE SWITCH CONTROL
The remote switch control, if ordered with the unit, has two switches which
control power to the unit and control the speed of the motor. The remote
switch control cannot be added to a non-remote unit.
The switch control can be mounted in a convenient location and wired back to
the unit to control the functions. The control box has holes on the back for
mounting and knockouts on five sides for the electrical wire to be attached. A
terminal block is mounted inside the box to facilitate wiring.
Run an approved seven wire cable between the control box and the unit. Refer
to Fig. 6 for wiring connections between the control and the unit. Both the
remote box and the unit must be grounded for proper and safe operation.
Table 1 — TROUBLESHOOTING GUIDE
PROBLEM | PROBABLE CAUSE | REMEDY |
---|
Unit does not function correctly. Power switch ON and performance indicator
light and
motor are OFF.| Main breaker or fuse.| Check breaker or fuse and reset or
replace if necessary
Remote switch off.| If equipped with a remote switch ensure it is turned on.
Wiring or plug improperty connected.| Check wiring or if plug is inserted and
receptacle is powered.
Cover not closed.| Close cover and slide back on hinge.
Defective power switch.| Check power switch for continuity with ohmmeter.
Replace if defective.
Defective safety interlock.| Open cover and press safety interlock with a
screwdriver. If lights oome on, check if interlock bracket is bent.
Unit does not function correctly. Power switch Is ON, motor Is operating and
performance indicator light is OFF.| Short in cells due to:
1.Broken ionizing wire.
2.Large particles wedged between cell plates.
3.Cells washed recently and are still wet.
4.Cell end plate insulator Is dirty or damaged.
5.Cell plates are bent.| 1.Remove wire or wire fragments. Replace.
2.Shake large particles out or wash cell.
3.Allow cells to dry completely.
4.Clean or replace end plate insulator.
5.Straighten plates with pliers.
Defective performance indicator light.| Determine whether high voltage is
present by testing power board. If voltage is present, replace indicator
light.
Defective power board.
(Check power board with cells removed)| Adjust high voltage potentiometer on
power board counter-clockwise. If high voltage is not present check
transformer and switches. Replace power board if 24 V is present to power
board.
Off board 24 V transformer is not working.| Verify output of transformer.
Replace if necessary.
Defective power switch.| Verify output of switch. Replace if necessary.
Unit does not function correctly Power switch is ON, motor is not operating
and performance indicator light is ON.| Defective power switch.| Check power
switch for continuity with ohmmeter. Replace if defective
Defective speed selector switch.| Check switch for continuity with ohmmeter.
Replace if defective.
Defective fan motor.| Test motor and replace if defective.
Cell makes loud hissing noise or causes radio Interference.| Internal cell
contacts are not touching plates.| Test contacts and repair.
High voltage copper contacts not making good connection on cell.| With needle-
nose pliers. gently pull contacts down or replace contacts
Cells arcing excessively (performance indicator light ON or flashing).| Cells
wet from washing.| Allow cells to dry completely.
Panicles lodged in cell or broken ionizing wire.| Wash cell. Shake particle
out of cell. Replace wire, if necessary.
Cell plates are bent.| Remove cells and adjust to original spacing using
needle-nose pliers.
Voltage is too high.| Adjust high voltage potentiometer on power board
clockwise.
High voltage wires are on wrong copper contact.| Reposition high voltage wires
on proper contact (see Fig. 5).
Internal contact on cell out of alignment.| Realign cell contact.
Cells arcing excessively at top of cell near copper contacts (power light and
performance Indicator light ON).| Copper contact on high voltage contact board
is broken or bent upward.| If possible, pull down contact with needle-nose
pliers or replace contact.
Cells not collecting dirt (performance indicator light ON).| Arrow on cells
not pointing towards fan motor.| Reposition cell handle and place cell in
properly.
Not enough voltage on collecting cells.| Adjust high voltage potentiometer
counter-clockwise on power board.
Ozone odor| Cell plates are bent.| Straighten with needle-nose pliers.
Loose or broken ionizing wire.| Replace wire.
Dirty cells.| Wash cells.
Incoming voltage is higher than 120 V.| Adjust high voltage potentiometer
clockwise on power board.
Air Cleaner is oversized for room.| Use correct size of Air Cleaner.
Room is extremely dry.| Repair or install central humidifier.
# | Description | Part Number |
---|---|---|
1 | Fan Motor | EACCM13-01 |
2 | Fan Blade | EACCM13-02 |
3 | Copper Contact | EAC14-08 |
4 | Fibreboard (with 2 Copper Contacts) | EACCM13-04 |
5 | Intake Grill | EACCM13-05 |
6 | Cover Assembly (incl. Grill) (White) | EACCM13-06W |
6a | Cover Assembly (incl. Grill) (Gray) | EACCM13-06G |
7 | Collecting Cell | EACCM13-07 |
8 | Cell Handle | EAC14-16 |
9 | Ionizing Wire | EAC20-19 |
10 | Safety Interlock Switch | EACCM13-10 |
11 | Red Indicator Light | EACCM13-11 |
12 | Power Switch (Gray) | EACCM13-12W |
12a | Power Switch (Black) | EACCMI3-12G |
13 | 3-Position Slide Switch (Gray) | EACCM13-13W |
13a | 3-Position Slide Switch (Black) | EACCM13-13G |
14 | Power Board Fibreboard | EACCM13-14 |
15 | Power Board | EACCM13-15 |
16 | 24 Volt Transformer | EACCM13-16 |
17 | Cell Guide | EAC14-14 |
18 | Prefilter | EACCM13-18 |
19 | Remote Switch Box | EACCM13-19 |
20 | Door Label (Close Door Latch…) | EACCM13-20 |
21 | Door Label (Lift and Pull…) | EACCM13-21 |
22 | Dax Detergent | 9900 |
Use the diagram above to identify the part which is required. To order parts
call the number listed below or call your local contractor.
Table 2 — Technical Data
Dimensions Length
Width Height| 29.5 in
27.0 in
14.5 in| 75.0 cm
68.6 cm
37.0 cm
---|---|---
Weight| 95.0 lbs| 43.0 kg
Input Voltage| 120 V 60 Hz|
Power
Consumption (max)| 350 Watts|
Air Flow High
Medium Low| 1300 CFM 1050 CFM 750 CFM| 2210 m3/hr
1785 m3/hr
1275 m3/hr
Motor| 1/12 HP|
ELECTRONIC AIR CLEANER LIMITED ONE YEAR WARRANTY
Electronic Air Cleaners, if properly registered by the return of the attached
warranty registration to General Filters, Inc., are warranted to the consumer
against defects in materials and workmanship for a period of one year from the
date of installation, so long as the product has been installed and operated
in accordance with all appropriate manuals and wiring diagrams. Replacement or
routinely replaceable parts such as prefilters, are not covered by this
limited warranty or any other warranties. Any other defective parts will be
repaired without charge except for removal, reinstallation and transportation
costs. To obtain repair service under this limited warranty, the consumer must
send the defective part to General Filters, Inc.
THERE ARE NOT EXPRESS WARRANTIES COVERING THIS ELECTRONIC AIR CLEANER OTHER
THAN AS SET FORTH ABOVE. THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED. THE MANUFACTURER ASSUMES NO
LIABILITY IN CONNECTION WITH THE INSTALLATION OR USE OF THIS PRODUCT, EXCEPT
AS STATED IN THE LIMITED WARRANTY. THE MANUFACTURER WILL IN NO EVENT BE LIABLE
FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
This limited warranty gives you specific legal rights, and you may also have
other rights which vary from state to state. Some states do not allow either
limitations on implied warranties, or exclusions from incidental or
consequential damages, so the above exclusion and limitation may not apply to
you.
Any questions pertaining to this limited warranty should be addressed to
General Filters, Inc. General Filters, Inc. has elected not to make available
the informal dispute settlement mechanism which is specified in the Magnuson-
Moss Warranty Act.
General Filters, Inc.
43800 Grand River Ave.
Novi, Michigan 48375-1115
WWW.GENERALAire.COM
Canadian General Filters, Ltd.
39 Crockford Bivd.
Scarborough, Ontario
WWW.CGFPRODUCTS.COM