VTS HMI WING HY Controller Panel User Manual

July 4, 2024
VTS

VTS HMI WING HY Controller Panel

Product Information

Specifications:

  • Product Name: HMI WING HY
  • Model Number: 1-4-2801-0155
  • Manufacturer: VTS Group S.A.
  • Address: 11-13, Boulevard de la Foire, L-1528 Luxembourg

Product Usage Instructions

Display and Operation:
The HMI WING HY controller optimizes the operation of curtains, ensuring uninterrupted and reliable functioning. The device’s thoughtful features allow for significant energy savings.

Operating Modes:

  • Heating Mode: Operation of single heater coils
  • Calendar-based Work: Yes/No
  • Temperature Display: Current temperature (ROOM), Set temperature (SET), External temperature sensor (EXT)

Changing Fan Speed:
To change the fan speed, press the appropriate button corresponding to different speed levels. The fan speed can be adjusted within programmable ranges (Speed I: 15-80%, Speed II: 15-90%, Speed III: 15-100%). Advanced settings A: functions A5, A6, and A7 allow for setting individual gear values.

FAQ

  • How do I change the fan speed?
    To change the fan speed, press the button corresponding to the desired speed level. Adjustments can be made within the programmable range specified in the manual.

  • What does the calendar-based work feature entail?
    The calendar-based work feature allows users to schedule heating or ventilation operations based on programmed settings. Users can specify whether the system should operate according to a set schedule or not.

Introduction

HMI WING HY is a control panel, dedicated to all types of WING EC curtains. It has an interface with RTU Modbus protocol for easy integration with building management systems (BMS). It is characterised by very easy and intuitive operation due to the comfortable, practical keypad and backlit screen.

HMI WING HY controller has been made from electronic materials of the highest class. The panel is adapted for continuous operation with a 230 V AC single- phase power supply. Due to the well-thought-out design, the controller is installed in a very easy manner on a special mounting bracket in the Ø60 mm flush mounting box. The mounting bracket enables easy installation and removal of the panel. Electric wires are connected directly to the terminal block, located at the back of the controller. The panel enables three-position regulation of the rotational speed of the fans with EC motors, as well as three-position regulation of the heating power. Due to the integrated thermostat and as well as programmer function, the controller enables to define of operating parameters in the weekly schedule (on working days/at weekends, with 4 heating periods per 24 hours).

The installation of an external door sensor enables the selection of one of three modes of automatic operation:

  • Door (default one): heating with the air supply or only the air supply, maintenance of set temperature. Active only with an open door.
  • Room: heating with the air supply or only the air supply (air supply activated manually), maintenance of the set temperature. Active regardless of the status of the door sensor.
  • Door + room: heating with the air supply or only the air supply, maintenance of the set temperature. Active, depending on the status of the door sensor.

HMI WING HY controller optimises the operation of the curtains, ensuring their continuous and reliable operation, and the well-thought functions of the device enable significant power efficiency.

Overview

  • Explanation of the operating modes:
    • Speed I: Programmable value in the range of 15-80%.
    • Speed II: Programmable value in the range of 15-90%.
    • Speed III: Programmable value in the range of 15-100%.
  • Press to change the fan speed.
  • The values of the individual gears can be set from the advanced settings A: function A5, A6 and A7.

AntiFrost ( ): Frost protection of the heater medium. If the temperature falls below the set point, the two-way valve opens. The function works even with the deactivated controller or out of the working time set according to the calendar provided that the controller is connected to a 230VAC power supply.

Programming mode

You may enter the advance settings A by holding the buttons [ ] for 5 seconds with the deactivated controller. You may go to the next set point by pressing the [Set] key. The values can be changed using the [^] and [v] buttons. You may leave the programming mode by pressing any other button.

|

No.

| Function|

Setpoint

---|---|---|---
| IP| Communication Modbus RTU

– address

| 1 … 254
|

A0

| Modes of automatic operation:

door [1], room [0], door+room

[2]| selection [0, 1,

2]

|

A1

| Regulation of the heating power level:

without heating [0], first level [1],

second level [2], third level [3]

|

Selectrion [0, 1,

2, 3]

|

A2

|

Temp. sensor calibration

| max. ±8°C with the step of

0.5°C

|

A3

| Heating mode:

Heating [0], ventilation [1],

heating+ventilation [2]

| Selection [0, 1,

2]

| A4| Hysteresis of differential adjuster| 0.5/1/2
| A5| First speed value| 15-80%
| A6| Second speed value| 15-90%
| A7| Third speed value| 15-100%
| A8| Fan speed delay| 30….200s
| A9| Backlight time| 5….600s
| AA| Door optimum| 0, +1, +2, +3
| AB| Door sensor logic| NO [0], NC [1]
| AC| Mim. Fan speed during cooling down| 45-100%
| AD| Min. fan speed| 60% (in heating mode)
| AE| Calendar-based work| No [0], Yes [1]
| AF| Time mode| 12h [1]; 24h [0]
| B0| Buttons blockade| selection
| B1| Extra heating time| 0….90s
| Bo| Default settings|

Hold

| BU| Version number| XX

Note:
The controller operating in heating mode will not allow the fan speed value to go below 60%

You may enter the advance settings C by holding the buttons [Set] for 5 seconds with the deactivated controller. You may go to the next set point by pressing the [Set] key. The values can be changed using [^] and [v] buttons. You may leave the programming mode by pressing any other button.

No.

| Function|

Setpoint

---|---|---
C0| Temperature units| °C/°F
C1| Min. Temperature| 5….15°C
C2| Max. Temperature| 16…..40°C
C3| Communication Modbus RTU – speed| 2400/4800/9600 kbps.
C4| Communication Modbus RTU – parity| None/ odd/ even

Outputs

BMS connection (wires)


B

| ****

RS 485 B

---|---


A

| ****

RS 485 A


Ao

| ****

Analog output

---|---


GND

| ****

Analog gnd. output


DS

| ****

Door sensor


DS

| ****

Door sensor


L

| ****

230 V AC L

---|---


N

| ****

230 V AC N


H1

| ****

Heating


H2

| ****

Heating

  • For proper installation please refer to the wiring diagrams of the individual Volcano EC heaters.
  • Tables of Modbus variables are available at www.vtsgroup.com.

Calendar programming

When the controller is switched on, pressing the [Set] button for a longer time (approx. 5 seconds) will activate the function of weekly programming. You may go to the next set point by pressing the [^] key. The value of specific set points is made using the [Set], [^] and [v] buttons. The calendar is programmed for each day of the week individually. In both cases, there is a possibility of programming a maximum of four heating periods during 24 hours. The programming takes place in the time scope referring to the time when a given function is to be activated. Leaving the calendar programming mode is possible by pressing the power button.

Function Door Optimum

The AA function in the advanced settings A allows to programming of the “Door optimum” function.

  • ‘’+0” – no increase of fan speed after door opening detection
  • ‘’+1” – increase by +1 of fan speed after door opening detection
  • ‘’+2” – increase by +2 of fan speed after door opening detection

Function “Door Optimum” is dependent on other functions that were set up:

  • When the device is working in room mode function ‘’Door Optimum” doesn’t influence the parameters of air curtains because only the temperature parameter is relevant.
  • When the device is working in indoor mode or door + room mode function ‘’Door Optimum” influences on parameters of air curtains. Door opening detection is followed by increasing fan speed by the value that was set up in ‘’Door Optimum”. Door closing detection is followed by reducing fan speed by the value that was set up in ‘’Door Optimum”.

Extra heating time
The B1 function in the advanced settings A enables the user to program the function of heating the room after the door is closed. The time can be set between 0 and 90 seconds.

Suggested electric wires

  • L, N: 2×1 mm2
  • H, C: 2×1 mm2
  • AO, GND: 2×0.5 mm2 LIYCY
  • External temperature sensor: 2×0.5 mm2 LIYCY

Error messages
E1 – internal temperature sensor error

Switching off the device
To switch off the panel, press the power supply button and the device will switch off after a short animation. Switching off shall take place after the power supply button has been pressed.

Technical specifications

Type| control panel, adjuster|
---|---|---
Temperature measurement| -10°C … +99°C ; NTC10K|
Operation of the device| Physical buttons of the keypad Advance settings A:

Holding the [ ] buttons for 5 seconds with deactivated device advance settings B:

Holding the [Set] buttons for 5 seconds with the deactivated device

|
Calendar function| Programming weekly calendar (each day’s separate programming)|
Communication| Modbus RTU protocol|
Speed of transmission| 2400/4800/9600 bps|
Outputs| 1 analogue output 0-10V (8 bit, Imax = 20 mA) 2 relay outputs (250 VAC, AC1 500 VA for 230 VAC)|
Power supply

Power consumption

Display

Structure

Dimensions (W x H x D)

Installation

Weight

| 230 V AC

1.5 VA

backlit, graphic LCD (white captions, blue background)

ABS + Plexiglas

86 mm x 86 mm x 17 mm

in a standard Ø60 mounting box on a mounting bracket

150 g

|

ELECTRIC DIAGRAM

Example connection diagram of WING W100-200 EC, full electrical diagrams available for download at www.vtsgroup.com.

  1. Supply: 230V – 50Hz
  2. Main switch, fuses
  3. WING W100-200 EC
  4. Controller HMI WING HY
  5. Valve actuator

INSTALATION DIAGRAM

For proper electrical installation please refer to the electric wiring diagrams of air curtain WING EC.

Norms and standards
The use of advanced technology and high-quality standards of our products is the result of the continuous development of our products. For this reason, there may be differences between the attached documentation and the functionality of your device. Therefore please understand that the data contained in it, drawings and descriptions cannot be the basis for any legal claims.

VTS Group S.A.
11-13, Boulevard de la Foire L-1528 Luxembourg.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals