HMI WING HY is a control panel, dedicated for all types of WING ECcurtains. It is characterised by very easy and intuitive operation due to the comfortable, practical keypad and backlit screen. HMI WING HY controller has been made from electronic materials of the highest class. The panel is adapted for continuous operation with 230 V AC single-phase power supply. Due to the well-thought design, the controller is installed in a very easy manner on a special outigraketi the Ø flush outigo. The ou ti g bracket enables easy installation and removal of the panel. Electric wires are connected directly to the terminal block, located at the back of the controller. The panel enables three-position regulation of rotational speed of the fans with EC motors, as well as threeposition regulation of the heating power. Due to the integrated thermostat and as well as programmer function, the controller enables to define operating parameters in the weekly schedule (on working days/at weekend, with 4 heating periods per 24 hours). The installation of an external door sensor enables the selection of one of three modes of automatic operation:
- Door default oe: heating with the air supply or only the air supply, maintenance of set temperature. Active only with open door.
- oo : heatig ith the air suppl or ol the air suppl air suppl activated manually), maintenance of the set temperature. Active regardless of the status of the door sensor.
- Door + roo: heati g ith the air suppl or ol the air suppl, maintenance of the set temperature. Active, depending on the status of the door sensor. HMI WING HY controller optimises the operation of the curtains, ensuring their continuous and reliable operation, and well-thought functions of the device enable significant power efficiency.
Display and operation
No. | Description | Operation button |
---|---|---|
1 | Heating mode: |
Operation of single heater coils sections
Operation of two heater coils sections| Function A1[^] or [v]
2| Calendar-based work: | Function AE [^] or [v]
3| Operationg mode:
heating: ventilation ;heationg + ventilation| Function A3 [^] or [v]
4| Temperature display:
ROOM (current temp.), SET (set temp.)
EXT (based on external temperature sensor) | Function A1 [^] or [v]
5| Day of the week| Hold [Set]+[v]
6| Hour, minute | Hold [Set]+[v]
7| Screen lock| Hold [v]
8| Door close/open | n/a
Explanation of the operating modes:
– Speed I: Programmable value in the range of 15-80%.
– Speed II: Programmable value in the range of 15-90%.
– Speed III: Programmable value in the range of 15-100%.
Press to change the fan speed.
The values of the individual gears can be set from the advanced settings A:
function A5, A6 and A7.
AntiFrost ( ): Frost protection of the heater medium. If the temperature falls
below the set point, two-way valve opens. The function works even with
deactivated controller or out of the working time set according to the
calendar provided that controller is connected to a 230VAC power supply.
Programming mode
You may enter the advance settings A by holding the buttons [ ] for 5 seconds
with the deactivated controller. You may go to the next set point by pressing
the [Set] key. The values can be changed using [^] and [v] buttons. You may
leave the programming mode by pressing any other button.
No. | Function | Set point |
---|---|---|
IP | Communication Modbus RTU – address | N/A |
AO | Modes of automatic operation: door [1], room [0], door+room [2] | selection |
[0, 1, 2]
Al| Regulation of the heating power level: without heating [0], first level
[1], second level [2], third level [3]| Selectrion [0, 1, 2, 3]
A2| Temp. sensor calibration| max. ±8°C with the step of
0.5°C
A3| Heating mode: Heating [0], ventilation [1], heating+ventilation [2]|
Selection [0, 1, 2]
A4| Hysteresis of differential adjuster| 0.5/1/2
A5| First speed value| 15-80%
A6| Second speed value| 15-90%
A7| Third speed value| 15-100%
A8| Fan speed delay| 30….200s
A9| Backlight time| 5….600s
AA| Door optimum| 0, +1, +2, +3
AB| Door sensor logic| NO [0], NC [1]
AC| Mim. Fan speed during cooling down| 45-100%
AD| Min. fan speed| Only display
AE| Calendar-based work| No [0], Yes [1]
AF| Time mode| 12h [1]; 24h [0]
BO| Buttons blockade| selectrion
B1| Extra heating time| 0….90s
Bo| Default settings| r 17, Hold v
BU| Version number| XX
You may enter the advance settings C by holding the buttons [Set] for 5 seconds with the deactivated controller. You may go to the next set point by pressing the [Set] key. The values can be changed using [^] and [v] buttons. You may leave the programming mode by pressingany other button.
No. | Function | Set point |
---|---|---|
CO | Temperature units | °C/°F |
C1 | Min. Temperature | 5….15°C |
C2 | Max. Temperature | 16…..40°C |
C3 | Communication Modbus RTU — speed | N/A |
C4 | Communicatin Modbus RTU — parity | N/A |
**Outputs*
BMS connection (wires) – not available
B | N/A |
---|---|
A | N/A |
Ao | Analog output |
GND | Analog gnd. output |
DS | Door sensor |
DS | Door sensor |
L | 230 V AC L |
N | 230 V AC N |
H1 | Heating |
H2 | Heating |
*For proper installation please refer to the wiring diagrams of the individual Volcano EC heaters.
Tables of Modbus variables available at
www.vtsgroup.com
Calendar programming**
When the controller is switched on, pressing the [Set] button for a longer time (approx. 5 seconds) will activate the function of weekly programming. You may go to the next set point by pressing the [^] key. The value of specific set points is made using [Set], [^] and [v] buttons. The calendar is programmed for each day of the week individually. In both cases, there is a possibility of programming a maximum of four heating periods during 24 hours. The programming takes place in the time scope referring to the time when a given function is to be activated. Leaving the calendar programming mode is possible by pressing power button.
Function ‘Door Optimum”
The AA function in the advanced settings A allows to program the “Door optimum” function.
- “+0” — no increase of fan speed after door opening detection
- “+1” — increase by +1 of fan speed after door opening detection
- “+2” — increase by +2 of fan speed after door opening detection Function “Door Optimum” dependent on others founctions that were set up:
- When device is working in room mode function “Door Optimum” doesn’t have influence on parameters of air curtains because only temperature parameter is relavent.
- When device is working in door mode or door + room mode function “Door Optimum” influence on parameters of air curtains. Door opening detection is followed by increasing fan speed by the value that was set up in “Door Optimum”. Door closing detection is followed by reducing fan speed by the value that was set up in “Door Optimum”.
Extra heating time
The B1 function in the advanced settings A enables the user to program the
function of heating the room after the door is closed. The time can be set
between 0 and 90 seconds.
Wi-Fi communication
The controller works with an application for Android and IOS. Tuya Smart
application available for free download on Play Store and App Store.
First connection:
When configuring the application with the controller, make sure that both the
smartphone and the HMI controller are within range of the same network. To
make the connection easier and faster, run the GPS on your phone.
In the Tuya application we find “Thermostat” in the category of small devices.
Hold down the “ventilator” and “set” buttons on the controller until the
following icons appear on the display and start blinking:
Each further connection is made in the same way as described for the first
connection.
In the Tuya application, confirm the connection attempt and enter the password
for the Wi-Fi network. The connection may take up to several minutes. When the
above icons stop blinking, you will be connected to the application.
Control:
With the Tuya Smart application, the user has the possibility to view and
change the operating parameters of individual functions available in the
controller HMI.
To change the advanced settings (Set) it is necessary to enter the password:
123456.
Configuring the controller with the Tuya application does not mean that the
devices cannot be controlled from the controller position.
Changes in the operating parameters can be made both from the position of the
application and from the position of the controller.
Switching off the device
In order to switch off the panel, press the power supply button and the device
will switch off after a short animation. Switching off shall take place after
the power supply button has been pressed.
Technical specifications
Type | control panel, adjuster |
---|---|
Temperature measurement | -10°C … +99°C ; NTC1OK |
Operation of the device | Physical buttons of the keypad Advance settings A: |
Holding the [ ] buttons for 5 seconds with deactivated device advance settings
B:
Holding the [Set] buttons for 5 seconds with deactivated device
Calendar function| Programming weekly calendar (each day’s separate
programming)
Communication| Modbus RTU protocol
Speed of transmission| 2400/4800/9600 bps
Outputs| 1 analogue output 0-10y (8 bit !max = 20 mA) 2 relay outputs (250
VAC, AC1 500 VA for 230 VAC)
Power supply| 230 V AC
Power consumption| 1.5 VA
Display| backlit, graphic LCD (white captions, blue background)
Structure| ABS + Plexiglas
Dimensions (W x H x D)| 86 mm x 86 mm x 17 mm
Installation| in a standard 060 mounting box on a mounting bracket
Weight| 150 g
Suggested electric wires
-
L, N : 2×1 mm2
-
H, C : 2×1 mm2
-
AO, GND : 2×0.5 mm2 LIYCY
-
External temperature sensor: 2×0.5 mm2 LIYCY
Error messages -
El internal temperature sensor error
SCHEMAT ELEKTRYCZNY
Example connection diagram of WING W100-200 EC, full electrical diagrams available for download at www.vtsgroup.com.
- supply: 230V – 50Hz
- main switch, fuses
- WING W100-200 EC
- controller HMI WING HY
- valve actuator
For proper electrical installation please refer to the electric wiring
diagrams of air curtain WING EC
Norms and standards
The use of advanced technology and high quality standard of our products is
the result of continuous development of our products. For this reason, there
may be differences between attached documentation and functionality of your
device. Therefore please understand that the data contained in it, drawings
and descriptions cannot be the basis for any legal claims.
VTS Group S.A.
20, rue de l’industrie,
L-8399 WINDHOF, Luxembourg
Documents / Resources
| VTS
HMI WING HY Wi-Fi
Controller
[pdf] User Manual
HMI WING HY Wi-Fi Controller, HMI WING HY, Wi-Fi Controller, Controller
---|---