VTS HMI WING HY Wi-Fi Controller User Manual

June 10, 2024
VTS

HMI WING HY Wi-Fi (1-4-2801-0156)
MANUAL (ver. 04.2021)

HMI WING HY Wi-Fi Controller

HMI WING HY is a control panel, dedicated for all types of WING ECcurtains. It is characterised by very easy and intuitive operation due to the comfortable, practical keypad and backlit screen. HMI WING HY controller has been made from electronic materials of the highest class. The panel is adapted for continuous operation with 230 V AC single-phase power supply. Due to the well-thought design, the controller is installed in a very easy manner on a special outigraketi the Ø flush outigo. The ou ti g bracket enables easy installation and removal of the panel. Electric wires are connected directly to the terminal block, located at the back of the controller. The panel enables three-position regulation of rotational speed of the fans with EC motors, as well as threeposition regulation of the heating power. Due to the integrated thermostat and as well as programmer function, the controller enables to define operating parameters in the weekly schedule (on working days/at weekend, with 4 heating periods per 24 hours). The installation of an external door sensor enables the selection of one of three modes of automatic operation:

  • Door default oe: heating with the air supply or only the air supply, maintenance of set temperature. Active only with open door.
  • oo : heatig ith the air suppl or ol the air suppl air suppl activated manually), maintenance of the set temperature. Active regardless of the status of the door sensor.
  • Door + roo: heati g ith the air suppl or ol the air suppl, maintenance of the set temperature. Active, depending on the status of the door sensor. HMI WING HY controller optimises the operation of the curtains, ensuring their continuous and reliable operation, and well-thought functions of the device enable significant power efficiency.

VTS HMI WING HY Wi Fi Controller - Figure

Display and operation

No. Description Operation button
1 Heating mode:

Operation of single heater coils sections
Operation of two heater coils sections| Function A1[^] or [v]
2| Calendar-based work: | Function AE [^] or [v]
3| Operationg mode:
heating:  ventilation ;heationg + ventilation| Function A3 [^] or [v]
4| Temperature display:
ROOM (current temp.), SET (set temp.)
EXT (based on external temperature sensor) | Function A1 [^] or [v]
5| Day of the week| Hold [Set]+[v]
6| Hour, minute | Hold  [Set]+[v]
7| Screen lock| Hold [v]
8| Door close/open | n/a

Explanation of the operating modes:
– Speed I: Programmable value in the range of 15-80%.
– Speed II: Programmable value in the range of 15-90%.
– Speed III: Programmable value in the range of 15-100%.
Press to change the fan speed.
The values of the individual gears can be set from the advanced settings A: function A5, A6 and A7.
AntiFrost ( ): Frost protection of the heater medium. If the temperature falls below the set point, two-way valve opens. The function works even with deactivated controller or out of the working time set according to the calendar provided that controller is connected to a 230VAC power supply.
Programming mode
You may enter the advance settings A by holding the buttons [ ] for 5 seconds with the deactivated controller. You may go to the next set point by pressing the [Set] key. The values can be changed using [^] and [v] buttons. You may leave the programming mode by pressing any other button.

No. Function Set point
IP Communication Modbus RTU – address N/A
AO Modes of automatic operation: door [1], room [0], door+room [2] selection

[0, 1, 2]
Al| Regulation of the heating power level: without heating [0], first level [1], second level [2], third level [3]| Selectrion [0, 1, 2, 3]
A2| Temp. sensor calibration| max. ±8°C with the step of
0.5°C
A3| Heating mode: Heating [0], ventilation [1], heating+ventilation [2]| Selection [0, 1, 2]
A4| Hysteresis of differential adjuster| 0.5/1/2
A5| First speed value| 15-80%
A6| Second speed value| 15-90%
A7| Third speed value| 15-100%
A8| Fan speed delay| 30….200s
A9| Backlight time| 5….600s
AA| Door optimum| 0, +1, +2, +3
AB| Door sensor logic| NO [0], NC [1]
AC| Mim. Fan speed during cooling down| 45-100%
AD| Min. fan speed| Only display
AE| Calendar-based work| No [0], Yes [1]
AF| Time mode| 12h [1]; 24h [0]
BO| Buttons blockade| selectrion
B1| Extra heating time| 0….90s
Bo| Default settings| r 17, Hold v
BU| Version number| XX

You may enter the advance settings C by holding the buttons [Set] for 5 seconds with the deactivated controller. You may go to the next set point by pressing the [Set] key. The values can be changed using [^] and [v] buttons. You may leave the programming mode by pressingany other button.

No. Function Set point
CO Temperature units °C/°F
C1 Min. Temperature 5….15°C
C2 Max. Temperature 16…..40°C
C3 Communication Modbus RTU — speed N/A
C4 Communicatin Modbus RTU — parity N/A

**Outputs*
BMS connection (wires) – not available

B N/A
A N/A
Ao Analog output
GND Analog gnd. output
DS Door sensor
DS Door sensor
 L 230 V AC L
   N 230 V AC N
H1 Heating
H2 Heating

*For proper installation please refer to the wiring diagrams of the individual Volcano EC heaters.
Tables of Modbus variables available at www.vtsgroup.com
Calendar programming**

When the controller is switched on, pressing the [Set] button for a longer time (approx. 5 seconds) will activate the function of weekly programming. You may go to the next set point by pressing the [^] key. The value of specific set points is made using [Set], [^] and [v] buttons. The calendar is programmed for each day of the week individually. In both cases, there is a possibility of programming a maximum of four heating periods during 24 hours. The programming takes place in the time scope referring to the time when a given function is to be activated. Leaving the calendar programming mode is possible by pressing power button.

Function ‘Door Optimum”

The AA function in the advanced settings A allows to program the “Door optimum” function.

  • “+0” — no increase of fan speed after door opening detection
  • “+1” — increase by +1 of fan speed after door opening detection
  • “+2” — increase by +2 of fan speed after door opening detection Function “Door Optimum” dependent on others founctions that were set up:
  • When device is working in room mode function “Door Optimum” doesn’t have influence on parameters of air curtains because only temperature parameter is relavent.
  • When device is working in door mode or door + room mode function “Door Optimum” influence on parameters of air curtains. Door opening detection is followed by increasing fan speed by the value that was set up in “Door Optimum”. Door closing detection is followed by reducing fan speed by the value that was set up in “Door Optimum”.

Extra heating time
The B1 function in the advanced settings A enables the user to program the function of heating the room after the door is closed. The time can be set between 0 and 90 seconds.
Wi-Fi communication
The controller works with an application for Android and IOS. Tuya Smart application available for free download on Play Store and App Store.
First connection:
When configuring the application with the controller, make sure that both the smartphone and the HMI controller are within range of the same network. To make the connection easier and faster, run the GPS on your phone.
In the Tuya application we find “Thermostat” in the category of small devices.
Hold down the “ventilator” and “set” buttons on the controller until the following icons appear on the display and start blinking:VTS Icon
12
Each further connection is made in the same way as described for the first connection.
In the Tuya application, confirm the connection attempt and enter the password for the Wi-Fi network. The connection may take up to several minutes. When the above icons stop blinking, you will be connected to the application.
Control:
With the Tuya Smart application, the user has the possibility to view and change the operating parameters of individual functions available in the controller HMI.
To change the advanced settings (Set) it is necessary to enter the password: 123456.
Configuring the controller with the Tuya application does not mean that the devices cannot be controlled from the controller position.
Changes in the operating parameters can be made both from the position of the application and from the position of the controller.

VTS QR

Switching off the device
In order to switch off the panel, press the power supply button and the device will switch off after a short animation. Switching off shall take place after the power supply button has been pressed.

Technical specifications

Type control panel, adjuster
Temperature measurement -10°C … +99°C ; NTC1OK
Operation of the device Physical buttons of the keypad Advance settings A:

Holding the [ ] buttons for 5 seconds with deactivated device advance settings B:
Holding the [Set] buttons for 5 seconds with deactivated device
Calendar function| Programming weekly calendar (each day’s separate programming)
Communication| Modbus RTU protocol
Speed of transmission| 2400/4800/9600 bps
Outputs| 1 analogue output 0-10y (8 bit !max = 20 mA) 2 relay outputs (250 VAC, AC1 500 VA for 230 VAC)
Power supply| 230 V AC
Power consumption| 1.5 VA
Display| backlit, graphic LCD (white captions, blue background)
Structure| ABS + Plexiglas
Dimensions (W x H x D)| 86 mm x 86 mm x 17 mm
Installation| in a standard 060 mounting box on a mounting bracket
Weight| 150 g

Suggested electric wires

  • L, N : 2×1 mm2

  • H, C : 2×1 mm2

  • AO, GND : 2×0.5 mm2 LIYCY

  • External temperature sensor: 2×0.5 mm2 LIYCY
    Error messages

  • El internal temperature sensor error

SCHEMAT ELEKTRYCZNY

VTS HMI WING HY Wi Fi Controller - SCHEMAT ELEKTRYCZNY

Example connection diagram of WING W100-200 EC, full electrical diagrams available for download at www.vtsgroup.com.

  1. supply: 230V – 50Hz
  2. main switch, fuses
  3. WING W100-200 EC
  4. controller HMI WING HY
  5. valve actuator

VTS HMI WING HY Wi Fi Controller - based work 1

For proper electrical installation please refer to the electric wiring diagrams of air curtain WING EC
Norms and standards
The use of advanced technology and high quality standard of our products is the result of continuous development of our products. For this reason, there may be differences between attached documentation and functionality of your device. Therefore please understand that the data contained in it, drawings and descriptions cannot be the basis for any legal claims.

VTS Group S.A.
20, rue de l’industrie,
L-8399 WINDHOF, Luxembourg

Documents / Resources

| VTS HMI WING HY Wi-Fi Controller [pdf] User Manual
HMI WING HY Wi-Fi Controller, HMI WING HY, Wi-Fi Controller, Controller
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals