SOFAR ESI 3-6K-S1 PowerAll ESI Hybrid Inverter User Manual
- July 3, 2024
- SOFAR
Table of Contents
- SOFAR ESI 3-6K-S1 PowerAll ESI Hybrid Inverter
- Specifications
- Product Information
- FAQs
- Preface
- Basic Safety Information
- Product Introduction
- Product Installation
- Electrical Connection
- Commissioning
- Troubleshooting and maintenance
- Manufacturer’s Warranty and Liability Terms
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SOFAR ESI 3-6K-S1 PowerAll ESI Hybrid Inverter
Specifications
- Product Name: ESI 3-6K-S1
- Manufacturer: SHENZHEN SOFARSOLAR Co., Ltd.
- Model: ESI 3-6K-S1
- Capacity: 3-6K
- Installation: Electricians only
Product Information
1. Product Introduction
The ESI 3-6K-S1 is a solar inverter designed for residential and commercial use. It provides efficient conversion of solar energy into usable electricity.
- Product Overview: The inverter is designed to meet the needs of small to medium-sized solar power systems.
- Product Appearance: The inverter features a compact and sleek design suitable for indoor installations.
- Buttons and Indicator Lights: The inverter is equipped with intuitive buttons and indicator lights for easy monitoring and operation.
2. Product Installation
- Checking Before Installation: Ensure all components are included and in good condition before proceeding with the installation.
- Installation Tools: Prepare the necessary tools for installation, including screwdrivers, wrenches, and safety equipment.
- Installation Environment: Install the inverter in a well-ventilated area with proper clearance for heat dissipation.
- Installation Space: Allocate sufficient space around the inverter for maintenance and ventilation purposes.
- Product Installation: Follow the step-by-step installation guide provided in the manual to securely mount the inverter.
3. Electrical Connection
- Attentions Before Connection: Ensure all power sources are switched off before proceeding with electrical connections.
- Preparation of Connection Cables: Use appropriate cables and connectors as specified in the manual for safe and reliable connections.
- Electrical Connection for Internal System: Connect the inverter to the internal electrical system following the provided guidelines.
- External Electrical Connection: For external connections, adhere to local electrical codes and regulations.
FAQs
- Q: Who should install the ESI 3-6K-S1 inverter?
- A: The installation of the ESI 3-6K-S1 inverter should be carried out by qualified electricians only to ensure safety and proper setup.
- Q: What should I do if I encounter issues with the inverter?
- A: Refer to the troubleshooting section of the manual for guidance on identifying and resolving common issues. If problems persist, contact customer support for assistance.
- Q: Can the ESI 3-6K-S1 be used for off-grid systems?
- A: The ESI 3-6K-S1 is primarily designed for grid-tied systems. Consult with a professional to determine compatibility with off-grid setups.
Preface
Preface
Notice
The products, services or features you purchased shall be subject to the
company’s commercial contracts and terms. All or part of the products and
services described in this document may not within the scope of your purchase.
Unless additional terms and conditions in your contract, the company does not
make any statement or guarantee on the contents of this document. In addition,
the term “Product” as described in this document refers broadly to “ESI Series
products”.
Save this Instruction
This manual must be considered as an integral part of the equipment. Customer
can print the electronic version to hard copy and keeping properly for future
reference. Anyone who operates the device at any time must operate in
accordance with the requirements of this manual.
Copyright Declaration
The copyright of this manual belongs to SHENZHEN SOFARSOLAR Co., Ltd. Any
corporation or individual should not plagiarize, partially cope or fully copy
(including software, etc.), not allow to duplication and publishment in any
form and any way. All rights reserved, SOFAR reserves the right of final
interpretation. This manual subject to modify according to user’s or
customer’s feedback. Please check our website at http://www.sofarsolar.com for
latest version.
Document Updates
V4.1 2024-06-11
User Manual
1
Preface
Outline
Please read the product manual carefully before installation, operation or
maintenance. This manual contains important safety instructions and
installation instructions that must be followed during installation and
maintenance of the equipment.
Scope of Validity
This product manual describes the installation, electrical connections,
commissioning, maintenance and troubleshooting of ESI Series products.
Target Group
This manual is for qualified electricians. The tasks described in this manual
only can be performed by qualified electricians.
Symbols Used
The following types of safety instruction and general information appear in
this document as described below:
Danger Warning Caution Attention
Note
“Danger” indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
“Warning” indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
“Caution” indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
“Attention” indicates there are potential risks, if fail to prevent, may lead
to equipment cannot normally or property damage.
“Note” provides additional information and tips that are valuable for the
optimal operation of the product, will help you to solve a problem or save
your time.
2
ESI 3-6K-S1
Basic Safety Information
1 Basic Safety Information
Outlines of this Chapter Please read the instruction carefully. Faulty
operation may cause serious injury or death.
Note
If you have any question or problem when you read the following information, please contact SHENZHEN SOFARSOLAR CO., Ltd.
1.1 Requirement for Installation and Maintenance
Common Requirements
The product must be installed in full compliance with national and local power
grid standards and regulations.
Before installing and adjusting the produce, please read all of instructions,
cautions and warnings in this manual.
Before connecting the product to the electrical utility grid, contact the
local utility company for allowance. Also, this connection must be made only
by qualified electrician.
When any maintenance or repair is required, please contact the nearest
authorized maintenance center. If you don’t know which service center is
closest to you, please contact your local distributor. Don’t repair the
product by yourself, which may lead serious injury or damage.
Before installing and maintaining the device, using the DC switch to cut off
the high voltage direct current of the photovoltaic array. Otherwise, the high
voltage may cause serious injury.
The product should be placed in a well-ventilated place. Do not place
the product in a sealed or air-tight position or cabinet, otherwise it will
affect the operation performance and system life of the energy storage
system.
Avoid direct sunlight. Do not place this product near stoves and fire sources. Otherwise, the lithium battery in the product system will leak
User Manual
3
Basic Safety Information
or even explode.
The maintenance personnel of this product must understand the knowledge and
skills related to inverter and battery maintenance.
ESI Series products are transformerless inverter which requires the positive
pole and negative pole of the PV array are NOT grounded. Otherwise, it will
cause inverter failure. In the PV system, all non-current-carrying metal parts
(such as mounting frame, combiner box enclosure, etc.) should be connected to
earthed.
Reminder: Do not disassemble and destroy the battery. The toxic electrolyte in
the battery can damage your skin and eyes.
Caution: Comply with the following requirements during the installation and
maintenance of the product:
A) Remove watches, rings and other metal objects from your body.
B) Use tools with insulated handles.
C) Wear rubber gloves and shoes.
D) Do not place tools or metal objects on the battery.
E) Close the inverter before connecting/disconnecting the battery and the
energy storage inverter.
F) Battery +/- pole shall be isolated from ground.
Installation and maintenance personnel requirements When the product is in the
running state, some parts may be electrified and hot. Improper use, improper
installation or operation may result in serious injury to person or property.
Transport, loading, unloading, installation, start-up and maintenance
operations must be performed by a qualified electrical engineer (all accident
precautions in force in the user’s country must be followed!) SOFAR will not
be responsible for any personal injury or property injury caused by improper
use.
4
ESI 3-6K-S1
Basic Safety Information
Installation location requirement
Please install the product according to the following section. Place inverter
in an appropriate bearing capacity objects (such as solid brick wall, or
strength equivalent mounting surface, etc.) and make sure inverter vertical
placed. A proper installation location must have enough space for fire engine
access in order for maintenance if faulty occur. Ensure the inverter is
installed in a wall ventilated environment and have enough air cooling cycle.
Air humidity should less than 90%.
Transport Requirement
Inverter is in the good electrical and physical condition when it ship out
from factory. During transport, inverter must be placed in its original
package or other proper package. Transportation company should responsible for
any damage during transport period.
If you find any packing problems that may cause the damage of inverter or any
visible damage, please notice the responsible transportation company
immediately. You can ask your installer or SOFAR for help is necessary.
This product contains battery module through UN38.3, belongs to the ninth
category of dangerous goods. Therefore, loading and unloading must comply with
local laws and regulations and industry standards during transportation. Rough
loading and unloading may cause short circuit or damage to batteries in
containers, which may result in battery leakage, breakage, explosion, or fire.
Shipping complies with the IMDG CODE and the International Maritime Dangerous
Goods CODE.
For land transportation, comply with ADR or JT T617 shipping requirements.
Comply the regulatory requirements of the transport regulatory authorities of
the country of origin, route and destination.
Comply with international regulations for the transport of dangerous goods and
the supervision requirements of the corresponding national transport
regulatory authorities.
User Manual
5
Basic Safety Information
Electrical Connection
Please comply with all the current electrical regulations about accident prevention in dealing with the current inverter.
Danger Warming
Before the electrical connection, use opaque material to cover the PV modules
or disconnect PV string DC switch. PV arrays will produce dangerous voltage if
it is exposure under sun. When installing a battery, check the positive and
negative terminals of the battery and turn off the battery.
All operation must accomplish by certified electrical engineer Must be
trained; Completely read the manual operation and
understand all information.
Attention
Must get permission by local utility company before connecting to grid and the connection must be done by certified electrical engineers.
Operation Cautions
Danger
Touching the utility grid or the terminal conductors can lead to lethal electric shock or fire! Do not touch non-insulated cable ends, DC conductors and any live components. Attention to any electrical relevant instruction and document.
Attention
Enclosure or internal components may get hot during operation. Please wear insulated gloves.
Maintenance and Repair Cautions
Danger Attention
Before any repair work, turn OFF the AC circuit breaker between the product
and electrical grid first, then turn OFF the DC switch. After turning OFF the
AC circuit breaker and DC switch wait for at least 5 minutes before carry any
maintenance or repair work.
Product should not work again until removing all faults. If any repair work is
required, please contact local authorized service center. Should not open the
product cover without authorized permit, SOFARSOALR does not take any
responsibility for that.
6
ESI 3-6K-S1
Basic Safety Information
EMC/Noise Level Electromagnetic compatibility (EMC) refers to that on
electrical equipment functions in a given electromagnetic environment without
any trouble or error, and impose no unacceptable effect upon the environment.
Therefore, EMC represents the quality characters of an electrical equipment.
The inherent noise-immune character: immunity to internal electrical noise
External noise immunity: immunity to electromagnetic noise of external system
Noise emission level: influence of electromagnetic emission upon environment
Danger
Electromagnetic radiation from the product may be harmful to health! Please do not continue to stay away from the product in less than 20cm when it is working
1.2 Symbols and Signs
Danger Caution
High voltage of inverter may be harmful to health! Only certified engineer can
operate the product; Juveniles, Disable, should not use this product; Keep
this product out of the reach of children;
Caution of burn injuries due to hot enclosure! Only touch the screen and
pressing key of the product while it is working
Attention Warning
PV array should be grounded in accordance to the requirements of the local
electrical grid company
Ensure the maximum DC voltage input is less than the product’s maximum DC
voltage (including in low temperature condition). Any damage cause by over-
voltage, SOFAR will not take the responsibility including warranty
User Manual
7
Basic Safety Information
The product has some safety symbols on it. Please read and fully understand
the content of the symbols before installation.
Sings on the inverter module
Symbols
Name
This is a residual voltage in the inverter module!
Caution of high voltage and electric shock
Caution of hot surface
Comply with European standard (CE) certification
Grounding Terminal
Explanation
After disconnect with the DC side, there is a residual voltage in the inverter
module, operator should wait for 5 minutes to ensure the capacitor is
completely discharged. The inverter module operates at high voltages. Prior to
performing any work on the product, disconnect the product from voltage
sources. All work on the product must be carried out by qualified persons
only. The inverter module can get hot during operation. Avoid contact during
operation. Prior to performing any work on the product, allow the product to
cool down sufficiently.
The product complies with the CE Certification
Connect the inverter module to the ground bar for grounding protection
Observe the documentation
Read all documentation supplied with the product before install
Positive pole and negative pole
Positive pole and negative pole of the input voltage (DC)
Temperature
Indicated the temperature allowance range
This side up
RCM (Regulatory Compliance Mark)
Inverter must always be transported, handled and stored in such a way that the
arrows always point upwards.
The product complies with the requirements of the applicable Australian
standards
8
ESI 3-6K-S1
Product Introduction
2 Product Introduction
2.1 Product Overview
2.1.1 Product Brief Introduction
ESI 3-6K-S1 series inverters support multi-power segment operation. Including
PV, energy storage, grid connection, EPS and other corresponding functions in
one. PV is two independent MPPT tracking channels, suitable for different
installation environments. The ESI 3-6K-S1 inverter can be installed with or
without batteries. If the inverter needs to be used with batteries, it can
only use BTS 5K battery model. The battery type is LiFePO4 (LFP). The maximum
energy storage capacity is 5kWh-30kWh. The inverter has the advantages of
multiple working modes in operation. Under different modes, energy can be
managed and distributed according to the actual situation to meet different
needs. Flexible monitoring mode, support RS485. Also support: WIFI/Bluetooth
remote control function.
The main features are as follows: Stack integrated design, convenient
installation, simple maintenance; Built-in battery pack equalization
management unit to improve battery
available capacity; Photovoltaic maximum input current 16A, applicable to
large current
and double-sided module; Battery side complete electrical isolation, safer
system; UPS function to ensure the stable operation of critical load; Supports
a mixture of new and old batteries; Supports battery switch off with a button.
User Manual
9
Product Introduction
Figure 2.1.1-1 ESI series application principle diagram
2.2 Product Model Description
Figure 2.2-1 Inverter Model Identifiers
Table 2.2-1 Inverter Model demonstration
Meaning
Meaning
Specification
Product Model Stacked optical storage all in one machine
5Kthe power grade of inverter is 5kw.
Power Grade
Power grade list
3kw/3.68kw/4kw/4.6kw/5kw/6kw
Inverter Model Single-phase hybrid energy storage inverter
10
ESI 3-6K-S1
Product Introduction
2.3 Product Capacity Description
The ESI series residential energy storage system supports power and capacity
expansion and supports up to six inverter modules in parallel. One inverter
module supports up to six batteries expansion modules.
Figure 2.3-1 Storage Capacity Description
Note
This product contains only inverter modules.
User Manual
11
2.4 Product Appearance
Product Introduction
Figure 2.4-1 Inverter front side and back side
Front Side
Back Side
Figure 2.4-2 System front side and back side
1
Inverter
5
2
DC Switch
6
3
LCD display screen
7
4
Battery Module
Pedestal Inverter Radiator Battery Module Radiator
12
ESI 3-6K-S1
Product Introduction 2.4.1 Inverter Port
1 6
2
3
7
8
4 9
10 5
Right side port
Left side port
Figure 2.4.1-1 Inverter port diagram
1
Grid connection port
6
2
Load connection port
7
3
Inverter signal port
8
4
PV DC Switch
9
5
PV input port
10
WIFI/4G port Battery button switch
Battery DC switch Battery connection port
Battery signal port
User Manual
13
2.5 Buttons and Indicator Lights
1 2
Product Introduction 3
4 Figure 2.5-1 Buttons and indicator lights
1
System power indicator
2
System status indicator
3
Buttons
4
LCD screen
2.5.1 Buttons
Press “back” to the previous screen or enter the main interface. Press “up” to
the upper menu option or value plus 1. Press “down” to the lower menu option
or value minus 1. Press “ok” to select the current menu option or switch to
the next
digit.
2.5.2 System status indicator
System Status
On-grid Standby(On-grid)
Off-grid Alarm
Blue light ON
Flashing
Indicator Green light
ON
Red light ON
14
ESI 3-6K-S1
Product Introduction 2.5.3 Battery capacity indicator
Icon
Battery capacity
Capacity explanation
80%-100%
The battery capacity is full
60%-80%
40%-60%
20%-40% 5%-20% 0%-5%
The battery capacity is insufficient, and the
battery generates a low voltage alarm.
The battery enters the standby state
User Manual
15
2.6 Product label
Product Introduction
Note
Figure 2.6-1 The location of the label
The picture is only for reference, please make the object as the standard.
16
ESI 3-6K-S1
Product Installation
Product Installation
3.1 Checking Before Installation
Checking Outer Packing Materials
Before opening the battery and inverter package, check whether the outer
package is damaged, such as holes and cracks, and check the inverter and
battery model. If any damage is found or the inverter and battery model does
not match your requirements, please do not open the product package and
contact your distributor as soon as possible.
3.2 Installation Tools
Before installation, prepare the following tools:
NO
Tool
Model
Function
Hammer drill
Used to drill holes on
1
Recommend Drill @
the wall.
8mm
Remove and install
2
Screwdriver
screws and wires
Remove and install
3
Cross screwdriver
screws and wires
4
Wire stripper
Used to peel cable
User Manual
17
5 6
7
8 9 10 11 18
Product Installation
M6 socket head wrench Crimping Tool
Multimeter
Secure the backplane and inverter
Use to crimp cable on grid side, load side and CT extensive cable
Check whether the cable connection is correct, the positive and negative
terminals of the battery are correct, and the grounding is reliable
Marker
Mark signs
Measuring tape
Measure distance
Level ESD gloves
Ensure the rear panel is properly installed
Installer wear when installing product
ESI 3-6K-S1
Product Installation 12
Safety goggle
Installer wear when drill holes
Installer wear when
13
Mask
drill holes
Remove the output
14
Removal Tool
terminal of the
battery module
Install Fixed support
15
sleeve
rack
Used to crimp OT
16
Crimping tools
connector
3.3 Installation environment
Choose a dry, clean, neat and convenient location for installation. Machine
ambient temperature: -10~50; Relative humidity: 5-95% (non-condensing); The
product should be placed in a well-ventilated place; There are no inflammable
and explosive objects near the
installation position of the product; The product system inverter AC over-
voltage level is three; The highest altitude of the installation environment
is 4000m. The installation position of the product should be chosen to avoid
direct sunlight and snow position.
User Manual
19
Product Installation
.
Figure 3.3-1 Installation Environment Diagram
3.4 Installation Space
To ensure sufficient space for installation and heat dissipation, reserve
sufficient space around the ESI series household energy storage system. The
requirements are as follows:
20
ESI 3-6K-S1
Product Installation
Figure 3.4-1 Installation space diagram
User Manual
21
3.5 Product Installation
Product Installation
Figure 3.5-1 ESI series installation dimensions diagram
Pedestal installation Procedure 1Place the pedestal against a wall and keep it
10 to 25mm away from
the wall. Adjust the hole positions using a level, and mark the hole positions
using a marker.
2 To install the pedestal, remove the pedestal, drill holes using a hammer
drill ( 8mm, depth range 60-65 mm), and tighten expansion screws to ensure
that the base is securely installed.
3 Use a marker to mark holes for securing the battery modules and
22
ESI 3-6K-S1
Product Installation
inverters based on the dimensions shown in Figure 3.5-2.
60mm
Inverter
Levelling instrument Third Battery PACK
10~25mm
Left
Right
Second Battery Wall PACK
Baseboard
Ground
First Battery PACK
M6
Enlarged drawing A
A If holes cannot be drilled on the ground,the battery expansion modules must
be secured on the wall
55 NN··mm
Figure 3.5-2 Pedestal installation Fixed installation between modules
Procedure 1Align the first battery module on the floor pedestal.
User Manual
23
Product Installation
2 Install connectors on both sides and tighten the six screws using a cross
screwdriver.
3Install the remaining battery modules and inverters from bottom to top.
(Before installing the next module, ensure that the screws on the side
connectors of the previous module are firmly installed.)
Figure 3.5-3 Battery module and inverter installation diagram Support rack
installation Procedure
1Drill holes with a hammer drill ( 8mm, depth range 60-65 mm). Reposition and
drill the holes, if the original one has a large deviation.
24
ESI 3-6K-S1
Product Installation 2Install the support rack B on the wall, and fastening
expansion bolt. 3Adjust the support rack A, make sure the holes are matched
between
rack A and rack B. 4Connect and fix the rack A and rack B with M6*16 screws.
Figure 3.5-4 Schematic diagram of wall fixing installation
User Manual
25
Electrical Connection
4 Electrical Connection
4.1 Attentions Before Connection
Attention Attention
The voltage in the power conversion circuit of this product is very high. Fatal danger of electric shock or severe burns. All electrical connections of photovoltaic modules, inverters and battery systems must be carried out by qualified personnel. Wear rubber gloves and protective clothing (protective glasses and boots) when operating high voltage/current systems such as inverters and battery systems. This product is mainly applied to photovoltaic energy storage systems for household use. If not used according to the instructions, the protection provided by the equipment may be damaged.
4.2 Preparation of Connection Cables
Figure 4.2-1 System connection diagram U26ser Manual
Electrical Connection Table 4.2-1 Cables prepared by customers
No
Cable
Recommended specifications
1
PV connection cable
UL10269 12AWG
2
AC Grid connection cable
UL10269 8AWG
3
EPS connection cable
UL10269 10AWG
4
Grounding cable
UL10269 8AWG
4.3 Electrical Connection for Internal System
4.3.1 Internal protection grounding cable connection
Connect the grounding cables of the battery module and inverter as shown in Figure 4.3.1-1.
Attention
Be sure to ground for safety. The protective grounding of the chassis shell
cannot
replace the PGND cable of the LOAD Port. Ensure that the two PGND cables are
reliably connected. When multiple inverters are deployed, ensure that the
protection ground points of all inverters are equipotential connected.
User Manual
27
Electrical Connection
Figure 4.3.1-1 Internal grounding cable connection
4.3.2 Power cables connection
As shown in Figure 4.3.2-1, connect the power ports (BAT+, BAT-) of the
inverter to the cascading positive and negative power cables (B+,B -) of the
battery module. Connect the remaining battery modules from top to bottom, and
secure the cables with cable ties. Ensure that the cables are securely
connected.
Precautions during installation
28
ESI 3-6K-S1
Electrical Connection
If the system capacity is greater than 15kWh, the batteries are connected to
the inverter’s battery input interface in two independent groups.
Figure 4.3.2-1 Connection of battery internal DC terminal
User Manual
29
Electrical Connection
4.3.3 Internal communication cable connection
Connect the communication terminals of the inverter and battery module from
top to bottom according to 4.3.3-1 in the following figure, and secure them
with cable ties. For the communication cable, tighten the large nut and then
the small nut. In addition, install a matching terminal resistance on the
communication interface of the last battery module in the system.
Figure 4.3.3-1 Internal signal cable connection
30
ESI 3-6K-S1
Electrical Connection 4.3.4 Data collector connection
Connect the standard WIFI/4G collector in the inverter package according to
4.3.4-1 in the following figure.
Figure 4.3.4-1 WIFI/4G connection
4.4 External Electrical Connection
4.4.1 External ground Connection of the PGND cable
Procedure 1 Crimp OT terminals Precautions When stripping the cable, do not
scratch the core of the cable. The conductor crimping plate of an OT terminal
is pressed to form a
cavity that completely covers the conductor core and tightly binds the
User Manual
31
Electrical Connection
OT terminal. The crimping line can be covered with heat shrink tubing or
insulation
tape.
Figure 4.4.1-1 Diagram of Crimping OT terminals Procedure 2 The OT terminal is crimped properly, and the ground cable is connected to the position shown in the following figure.
Figure 4.4.4-2 Connect the grounding wire
32
ESI 3-6K-S1
Electrical Connection 4.4.2 PV module connection
Recommended DC input cable specifications
Range
CAS (mm2) Recommended value
External cable diameter(mm2)
4.0~6.0
4.0
4.5~7.8
Connection Procedure Step 1Prepare PV positive and negative power cables
1 Positive connector
2
Negative connector
Figure 4.4.2-1 Prepare PV positive and negative power cable Step 2 Insert the crimped photovoltaic positive and negative power cable
into the corresponding photovoltaic connector.
3 Positive connector
4
Negative connector
Figure 4.4.2-2 Prepare PV positive and negative connectors
User Manual
33
Electrical Connection
Step 3Ensure that the DC voltage of each PV string is less than 600V and the
polarity of PV cables are correct. Insert the positive and negative connectors
into the corresponding PV region of the ESI series inverter until a click is
heard. As the figure 4.4.2-3 showing.
Figure 4.4.2-3 Connect PV connector
Caution
Ensure that the DC switch is turned off before removing the PV positive and negative connectors.
Follow-up Step Disconnect the PV connector using an MC4 wrench, as shown in
Figure
4.4.2-4.
Figure 4.4.2-4 Disconnect PV connectors
34
ESI 3-6K-S1
Electrical Connection 4.4.3 Grid connection
Install AC wiring terminals Take out AC wiring terminals from the carton of
the inverter, strip and install cables according to the cable specifications
listed in Table 4.4.3-1.
Figure 4.4.3.-1 Wire stripping size Installation Step
LN
PE
After riveting the peeling wire to the insulation terminal, thread it into the lock wire nut and the main body.
Insert the cable into the rubber core according to the wire sequence, make the insulation terminal flush with the surface of the rubber core, and press the screw torque 2.0± 0.1n.m.
User Manual
35
Electrical Connection
The body is inserted into the core and a click is heard
Tighten the nut with an open wrench and make a “click” sound
Insert the female end of the wire into the male end and hear a “click” sound.
Installation complete
Figure 4.4.3-2 Installation Procedure Diagram
Removal Step
Use a screwdriver to point at the unlocking position, hold the cable driver, and pull it back to separate the male and female.
The female connector is separated from the board connector.
36
ESI 3-6K-S1
Electrical Connection
Hold the unlocking buckle with one hand and rotate it in the direction indicated, while rotate the nut in the opposite direction with the other hand.
Remove the red circles on both sides using a screwdriver.
Figure 4.4.3-3 Removal procedure
Connect the AC wiring terminals to the corresponding AC Grid ports, as shown in the following figure.
Figure 4.4.3-4 Grid connection
User Manual
37
4.4.4 EPS connection
Electrical Connection
According to the cable specifications given in Table 4.2-1, peel the cable according to the following figure 4.4.4-1. Then install the EPS connector according to 4.4.4-2. Finally, insert the installed EPS connector into the corresponding position of the inverter according to Figure 4.4.4-3.
Figure 4.4.4-1 Stripping diagram Install procedure
Crimp terminal
L/N/PE are labeled here Insert the cable into the butt terminal
Crimp the wire with an inner hexagon screwdriver with a screw torque of 1.2±
0.1n.m
38
Insert the subject into the corresponding clasp and hear a “click” sound
ESI 3-6K-S1
Electrical Connection
Screw locking nut into main body, torque 2.5± 0.5n.m
Installation complete
Figure 4.4.4-2 EPS Connector installation
Figure 4.4.4-3 EPS connection
Note
The EPS connector must be connected to the inverter port, even if it is not used.
User Manual
39
Electrical Connection 4.4.5 COM-Multi function communication connection
Figure 4.4.5-1 COM port diagram
Table 4.4.5-1 Port description
PIN Definition
Function
Comment
1
N/A
N/A
2
UC-A
RS485 differential signal -A
Inverter monitoring
3
UC-B
RS485 differential signal -B
485 signal
4
EN+
RS485 differential signal +
Battery 485 signal
5
EN-
RS485 differential signal –
6
MET-A RS485 differential signal -A
Smart meter 485 signal
7
MET-B RS485 differential signal -B
8
CANH
9
CANL
CAN high data CAN low data
Battery CAN communication signal
10
N/A
N/A
11
N/A
N/A
40
ESI 3-6K-S1
Electrical Connection
12
GND
13
D1/5
14
D4/8
15
D2/6
16
D0
17
D3/7
18
CT+
19
CT-
20
N/A
Link Port
Logic interface signal
DRMSLogical
interfaces use for below standard AustraliaAS4777
Europe General 50549German
4105
Current transformer output positive terminal
Current transformer output negative pole
N/A
Current transformer communication signal
Icon 1 2 3
4
Figure 4.4.5-2 Link Port diagram
Table 4.4.5-2 Link Port description
Define
Function
Comment
Link Port 1 Link Port 0
Parallel signal output Parallel signal input
Parallel signal port RJ45
Link Port 1 dip switch
Link Port 0 dip switch
Match resistance on and off
The dial switch has ON (dial up) and 1 (dial down). 1 means
off.
User Manual
41
Electrical Connection
The wire stripping is divided into 2 to 9 holes and 12 to 19 holes. The wire
stripping size is defined according to the cable.
Figure 4.4.5-3 Schematic diagram of wire stripping size 1. RS485Wired
monitoring or inverter cascade monitoring
Refer to the figure shown below, connect the RS485+ and RS485- of the inverter
to the TX+ and TX- of the RS485 USB adapter, and connect the COM port of the
adapter to the computer.
Note
The length of the RS485 communication cable should be less than 1000 m.
Connect pins as shown(2pin and 3pin)
Figure 4.4.5-4 RS485 wiring diagram
42
ESI 3-6K-S1
Electrical Connection
RS485 wires are connected in parallel between inverters.
Note
When multiple inverters are connected via RS485 wires, set communication
address to differentiate the inverters
please refer to this manual <5.4.1 System setting6.Communication Addr>.
2. Logic interface The logic interface pin definitions and circuit connections are as follows:
Logic interface pin are defined according to different standard requirements
aLogic interface for AS/NZS 4777.2:2020, also know n as inverter demand response modes (DRMs).
The inverter will detect and initiate a response to all supported demand response commands within 2 s. The inverter will continue to respond while the mode remains asserted.
Table 4.4.5-3 Function description of the DRMs terminal
Pin NO. 12 13 14 15 16 17
Function GND D1/5 D4/8 D2/6 D0 D3/7
b Logic interface for EN50549-1:2019, is in order to cease active power output
within five seconds following an instruction being received at the input
interface.
The inverter can be connected to a RRCR (Radio Ripple Control Receiver) in
order to dynamically limit the output power of all the inverters in the
installation.
User Manual
43
Electrical Connection
Figure 4.4.5-5 DRMs wiring diagram Table 4.4.5-4 Function description of the terminal
COM Pin NO. Pin name
Description
Connected to (RRCR)
PIN 16(PIN2)
L1
Relay contact 1 input
K1 – Relay 1 output
PIN 12(PIN1)
G
GND
K1 – Relay 1 output
Table 4.4.5-5 The inverter is preconfigured to the following RRCR power levels, close is 1, open is 0
L1
Active Power
Power drop rate
Cos()
1
0%
5 seconds
1
0 3.Meter/CT
100%
/
1
PIN6 and PIN7 of COM are used for meter communication, the electricity meter is shown in the Figure 4.4.5-6, PIN6 and PIN7 correspond to 7, 8 respectively on the electricity meter, as shown in Figure 4.4.5-6.
The connection mode is shown in Figure 4.4.5-6. The 1/2 and 3/4 on the electricity meter are connected to voltage signals L and N respectively. And the current needs to be connected through the current transformer, 6, 7correspond to the current transformer.
NOTE: The direction of the current transformer is shown in Figure 4.4.5-6.
44
ESI 3-6K-S1
Electrical Connection
HY33C1
Figure 4.4.5-6 Meter
If you need to use the CT alone, attach the CT to PIN18 and PIN19.
There are two ways to get grid current information:
Plan A: CT (default)
Plan B: Meter +CT
If you need to use the meter +CT scheme, please contact SOFAR staff to purchase the appropriate meter and CT.
COM Installation procedure for connecting cables
User Manual
45
Electrical Connection
Remove the plug from the plug and thread the terminal in the order shown
Insert the wire into the
corresponding terminal
Crimp the wire with a flat-head screwdriver with a torque of 1.2± 0.1n.m
Line core, rubber core area can not appear riding line phenomenon, rubber core into the main body with a “click” sound
Insert the plug into the body and plug the unwired hole
Screw the lock nut into the main body, torque 2.5± 0.1n.m, complete installation
Figure 4.4.5-7 Procedure for connecting COM cables
46
ESI 3-6K-S1
Electrical Connection
Insert the stripped COM connector into the corresponding port of the inverter,
as shown in the following figure.
Figure 4.4.5-8 COM connection
4. Feed-in limit function
The feed-in limit function can be used to limit the power fed
back into the grid. In order to achieve this function, power measurement
devices must be installed according to the system.
Single-phase limit: The power output of the inverter to the power grid does
not exceed the set power limit value.
NOTE:
- For the Single-phase limit setting, the current sensor must be properly connected to the L line on the meter. The meter wiring is shown in Figure 4.4.5-6. In addition, refer to 5.3.2(3) for feed-in limit settings.
- If communication with the smart meter is interrupted, the inverter limits its output power to the set power limit value.
User Manual
47
4.4.6 Smart Meter /CT
Electrical Connection
Refer to the COM interface description in Figure 4.4.5-6 Meter, the RS485A and RS485B of the electricity meter should be connected to pin6 and pin7 of the COM port of the inverter.
Figure 4.4.6-1 Smart meter/CT connection diagram
4.5 Install the cover
After electrical connections are complete and cable connections are correct
and reliable, install the external protective cover and secure it using
screws.
48
ESI 3-6K-S1
Electrical Connection
Figure 4.5-1 Install the cover
4.6 Parallel system
Refer to figure 4.6-1 below and connect the system in parallel according to
the success of the master and slave (up to 6 units). The dip switch inside the
COM 24PIN connector of the first and last system inverter should be moved to
the position of ON.
User Manual
49
Electrical Connection
50
ESI 3-6K-S1
Electrical Connection
4.7 System Electrical Topology
SOFAR has already integrated RCMU (residual current monitoring unit) inside
inverter. If an external RCD is required, a type-A RCD with rated residual
current of 100mA or higher is suggested.
ESI series household energy storage system is mainly composed of PV modules,
BTS 5K battery modules, inverters, AC switches, load and distribution units,
smart meters /CT, and power grid.
The inverters AC GRID and AC LOAD are wired with different N and PE wires
depending on the regulatory requirements in different regions. For users in
Australia, South Africa and New Zealand, please use the System Electrical
Topology in Figure 4.7-2.
System 1: N and PE lines are wired separately in the distribution box The
wiring method in Figure 4.7-1 is applicable to areas without special
requirements for distribution system wiring.
Figure 4.7-1 System Electrical Topology (General)
User Manual
51
Electrical Connection
a. Ensure that the AC LOAD PE line and AC GRID PE line must be connected to
the PE-BAR in the distribution box, as shown in the diagram. Otherwise, the
inverter may be abnormal in off-grid mode.
b. Check whether NeutralPointGrounding is enabled, if not, enable it manually.
2.Advanced setting
Enter 0715 11.NeutralPointGrounding
11. NeutralPointGrounding
Disable
Enable System 2: N and PE lines are connected together in the distribution box The wiring method in Figure 4.7-2 is applicable to areas where N and PE are connected together in the distribution box, such as Australia, South Africa, New Zealand, etc.
52
ESI 3-6K-S1
Electrical Connection
Figure 4.7-2 System Electrical Topology
(For Australia, South Africa and New Zealand)
Danger
Install Residual current device (RCD)in front of the load
RCD is necessary for critical load, but optional for
normal load. In off-grid mode, the Entry master switch is unprotected
and load leakage could lead to shock danger. All RCDs connected to Loads are
Type B and its rated earth
leakage action current <30mA.
Danger
Be sure to ensure that the output is grounded
In system 1, The PE line of the inverter’s AC GRID port and AC LOAD port must
be grounded through the PE-Bar, otherwise there may be a risk of leakage.
Note
In system 2, NeutralPointGrounding is disabled by default. No manual setup required.
User Manual
53
Commissioning
5 Commissioning
5.1 Checking Before System Starting
Please double check the following items before running 1. The product should
be completely fixed on the pedestal bracket, and
the connection with the wall should be tight and firm. 2. The PV+/PV- line is
firmly connected, the polarity is correct, and the
voltage is in line with the accessible range. 3. BAT+/BAT- cables are firmly
connected, the polarity is correct, and the
voltage meets the accessible range. 4. Grid/load cable connections are
firm/correct. 5. The inverter power grid port is correctly connected to the
power grid
and the AC circuit breaker is disconnected. 6. The inverter load port is
correctly connected to the emergency load, and
the circuit breaker is disconnected.
5.2 Electrify for the First TimeImportant
Important: Please follow the steps below to turn on the inverter. 1. Ensure
that the phase connected to the inverter of the product does not
generate power. 2. Switch the DC switch on the PV side of the product to ON.
3. Switch the DC switch on the battery side of the product to ON, and press
the battery black start button to activate the battery. 4. Turn on the AC
circuit breaker between the inverter power grid port and
the power grid. 5. Turn on the AC circuit breaker between the inverter load
port and the
emergency load.
54
ESI 3-6K-S1
Commissioning
6. Press the system power button, and the inverter starts running. The system
status indicator is blue.
When the inverter is running, set the following parameters. Table 5-1 Setting
parameter
Language selection Set system time[1] Set Safety Param
English French Germany
2022-11-02 14:36:28
Select safety regulation
Please Set the Password[3]
Select country code 001 EN 50549-1
Select country[2] Enter country code
018 EN 50549
Cancel Confirm
019 IEC 61727
[1] If the collector or mobile APP is connected to the monitoring system, the
time has been calibrated to the local time.
[2] Refer to the grid code table below and select country and code. [3] Appears only when UK grid code is selected.
Note
If you select the UK grid code, all passwords will be changed to which you set.
Table 5-2 Safety parameter import
Code
Region
000 000 Germany
000
001 002 Italia
003
000
002
Australia
008
009 003 002 Spain
Grid Code VDE-AR-N 4105 CEI 0-21 Internal CEI 0-21 External CEI 0-21 Areti
Australia-A
Australia-B Australia-C NTS 631-BCD
Description
Germany low-voltage Italy low-voltage 11kVA
Italy low-voltage >11kVA
CEI 0-21 Areti New South WalesVictoria Queenslandsouth Australia Australian
Capital Territory Jervis Bay Territory Western Australia Northern Territory
Tasmania Spain NTS typeB/C/D
User Manual
55
003
004
006
004 000 Turkey
000
001
005
Denmark
002
003
000
006
Greece
001
007 000 Netherland
000
008
Belgium
002
000
001
009
UK
002
003
000
010
China
009
000
001
003
011
France
004
006
007
012 000 Poland
UNE 217002 RD647 Spain island NTS typeA EN 50549-1 Denmark DK-TR322 Western
Denmark Eastern Denmark GR-Continent GR-Island EN 50549-1 C10/11 Belgium-LV
G99
G98
G99/NI
G98/NI NB/T 32004-B NB/T 32004-A France FRArrete23 France VFR 2019 VDE 0126
Enedis VFR 2019 Enedis EN 50549-1 Poland-A
000
013
Austria
001
TOR Erzg.-A cos TOR Erzg.-A Q-U
015 000 Switzerland
EN 50549-1
018 001 EN 50549
EN 50549-1
019 000 IEC 61727
IEC 61727
000
021
Sweden
001
Sweden Sweden typeA
022 000 User defined-50 Hz User def.-50 Hz
000
Cyprus
001
024
Cyprus
002
CY-LV-RES CY-LN/MV-COM
003
CY-LV/MV-UT
027 000 New Zealand
New Zealand
000
SK-VSD
029 001 Slovakia
SK-SSE
002
SK-ZSD
030 000 Czechia
EN 50549-1
Commissioning
Spain UNE+RD Spain island Spain NTS typeA Turkey Denmark DK-TR 322 Western
Denmark Eastern Denmark GR-Continent GR-Island Netherland low-voltage Belgium
Belgium-LV UK output current16A UK output curren16A Nor Ireland output
current16A Nor Ireland output current16A NB/T 32004-B NB/T 32004-A France
FRArrete23 France VFR 2019 VDE 0126 Enedis VFR 2019 Enedis EN 50549-1
Poland-A:0.2MW Austria TOR A250kW and nominal voltage110kV Austria TOR A250kW
and nominal voltage110kV
Switzerland-A EN 50549-1 230V 50Hz IEC61727 230V 50Hz EN 50549-1 Sweden typeA
User defined-50 Hz Cyprus CY-LV-RES CY-LN/MV-COM CY-LV/MV-UT New Zealand SK-
VSD SK-SSE SK-ZSD EN 50549-1
56
ESI 3-6K-S1
Commissioning
002 003 031 000 Slovenia 039 001 Ireland 044 000 South Africa 123 000 Romania
125 000 Finland
PPDS 2023-A1 PPDS 2023 SIST EN 50549-1
EN 50549-1
NRS 097-2-1 ANRE 208 EN 50549-1
AC 16A,typeA1 AC16A,typeA2/B/C/D
Slovenia sigle phase inverter6KVA; three phase inverter 11KVA South Africa-A
Romania Finland
It’s very important to make sure that you have selected the correct country code according to requirements of local authority.
Caution
Please consult qualified electrical engineer or personnel from electrical
safety authorities about this.
SHENZHEN SOFARSOLAR Co., Ltd. is not responsible for any consequences arising
out of incorrect country code selection.
Table 5-3 Default values for other Settings
Item Energy Storage Mode EPS Mode Set Feed-in Limit IV Curve Scan Logic Interface
Default status Self-use Mode Disable Disable Disable Disable
5.3 Steps of Shutdown
Important: Please follow the steps below to turn off the inverter.
1. Close the AC circuit breaker between the inverter grid port and the grid to ensure that the machine is in standby mode;
2. Switch the DC switch on PV side of the product to OFF;
3. Press the battery switch button to turn off the battery output, switch the
User Manual
57
Commissioning
DC switch on the battery side of the product to OFF, and the blue indicator light of the system status goes out;
4. Close the AC circuit breaker between the inverter load port and the emergency load.
5.4 Menu
4 1
2
5
3
6
1
Circulates current PV and battery statue
4
Display current inverter status
2
PV Power
5
Grid Power
3
Battery Power
6
Loads Power
Figure 5-1 Main interface
In the main interface, press ” page.
” button to enter Grid/Battery/PV parameter
Main interface
Grid Information Grid Voltage…………………………………..V Grid Power…………………………………..*.kW Grid Frequency…………………………..*Hz Total Load Power……………………….kW Battery Information Batt Voltage…………………………………*.V Batt Current…………………………………..A Batt Power…………………………………...kW Batt Temperature……………………………
58
ESI 3-6K-S1
Commissioning
Batt SOC……………………………………………% Batt Cycles…………………………………………T PV Information
PV1 Voltage …………………………………..V PV1 Current…………………………………...A PV1
Power…………………………………...*kW PV2 Voltage …………………………………..V PV2
Current…………………………………...A PV2 Power…………………………………...*kW PV-Ext
Power……………………………..*.kW In the main interface, press ” ” button to enter main
menu. The main menu has the following six options.
Main Interface
1.System Settings 2.Advanced Settings 3.Energy Statistic 4.System Information 5.Event List 6.Software Update 7.Battery Real-time Information
5.4.1 System Setting
1. System Settings
1.Language Settings
2.Time 3.Safety Param. 4.Energy Storage Mode 5.Auto Test[1] 6.EPS Mode
7.Communication Addr.
User Manual
59
[1] Appears only when Italian grid code is selected.
Commissioning
1. Language Settings Used to set the menu display language.
1.Language Settings
2. System Time Set the system time for the inverter.
1. 2.English 3.Italiano 4.Português 5.Deutsch 6.Cestina 7.Française 8.Español 9.Polski 10.Suomi
2.Time
Time 2022-05-13 17:07:00
3. Safety Parameter.
3.Safety Param.
Enter 0715 1.Select safety regulations
Select the correct safety regulations according to the Table 5-2. 4. Energy Storage Mode
4.Energy Storage Mode
1.Self-use Mode 2.Time-of-use Mode
60
ESI 3-6K-S1
Commissioning
3.Timing Mode
4.1 Self-use Mode
4.Passive Mode
In Self-use mode, inverter will automatically charge & discharge the battery.
-
If PV power = load power (including emergency load and ordinary load), the inverter will not charge and discharge the battery.
-
If PV generation > LOAD consumption, the surplus power will be stored in the battery.
-
If the battery is fully charged or has reached its maximum charging power, the remaining power is sent to the grid (with Feed-in Limitation enabled, the remaining power is not sent to the grid).
-
If the PV power is less than the load power, the inverter will supply power to the load through battery discharge.
-
If the PV power plus battery power is still less than the load power, the inverter will purchase power from the grid to supply power to the load.
User Manual
61
Commissioning
4.2 Time-of-use Mode
If electricity is more expensive in high demand time (peak rate) & electricity is much cheaper in low demand time (off-peak rate). You can select an off-peak period to charge your battery. Outside the off-peak charge period, inverter is working in Auto Mode.
If your family normally go to work/school on weekdays & stay at home on weekends, which means the home electricity consumption is much higher on weekends. Thus, you need to store some cheap electricity on weekends only. This is possible using our Time-of-use mode.
In summer, if your PV system can produce more electricity than your home electricity consumption. Then you don’t need to set an off-peak charge period to charge your battery in summer at all. You can select an effective date (normally winter) for Time-of-use mode in this case. Outside the effective date, inverter is working in Auto Mode.
You can set multiple Time-of-use rules to meet your more complex requirement. Right now we support 4 rules maximum (rule 0/1/2/3).
2.Time-of-use Mode
4.3 Timing Mode
Time-of-use Mode
Rules. 0: Disabled
From
To
SOC
02h00m –
04h00m
70%
Effective Date
Dec. 22
–
Mar. 21
Weekday select
Mon. Tue. Wed. Thu. Fri. Sat. Sun.
Charge 01000W
Changing the value of a rule can set multiple timing rules.
62
ESI 3-6K-S1
Commissioning 3.Timing Mode
4.4 Passive Mode
Timing Mode Rules. 0: Enabled/Disabled Charge Start Charge End Charge Power DisCharge Start DisCharge End DisCharge Power
22 h 00 m 05 h 00 m
02000 W 14 h 00m 16 h 00m 02500 W
4.Passive Mode For more detailed information, please ask representative of SOFAR to get a copy of passive mode communication protocol. 5. EPS Mode
5.EPS Mode
1.EPS Mode Control
1If PV generation > LOAD consumption(P > 100W), inverter will charge battery.
2If PV generation = LOAD consumption(P > 100W), inverter wont’ charge or discharge battery.
3If PV generation < LOAD consumption(P 100W), inverter will discharge battery.
User Manual
63
6. Communication Addr 6.Communication Addr
Commissioning
1.Communication Addr. 2.Baud Rate
5.4.2 Advanced Setting
2.Advanced setting
Enter 0715
1.Battery Parameter 2.Battery Active 3.Set Feed-in Limit 4.IV Curve Scan 5.Logic Interface 6.Factory Reset 7.Reset Password[1] 8.Parallel Settings 9.Reset Bluetooth 10.CT Calibration 11.NeutralPointGrounding 12.Set PCC Power Offset [1] Appears only when UK grid code is selected.
1. Battery Parameter
1.Battery Parameter
1.Battery Number
2.Battery1
Battery Number
Group 1 represents the number of cascading battery modules for the BAT1 port of the inverter.
Group 2 represents the number of battery modules connected to the BAT2
64
ESI 3-6K-S1
Commissioning port of the inverter. Battery 1
2.Battery 1
1.Depth of Discharge
2.Enable Force Full Charge
Depth of Discharge
3.Save
For example: if Depth of Discharge = 50% & EPS Depth of Discharge = 80%.
While grid is connected: Inverter won’t discharge the battery when its SOC is less than 50%.
In case of blackout: Inverter will work in EPS mode (if EPS mode is enabled) & keep discharging the battery till battery SOC is less than 20%.
3.Depth of Discharge 2. Battery Active
Depth of Discharge
(on-grid)
80%
Depth of Discharge
(off-grid)
80%
2.Battery Active 3. Set Feed-in Limit
1.Auto Active Control 2.Force Active
Users can limit the maximum power sent from the system to the grid by enabling Feed-in Limit. Counter current power is the maximum power expected to be sent to the grid (e.g., 0KW means no energy is fed into the grid).
User Manual
65
3.Set Feed-in Limit
Commissioning
1.Feed-in Limit 2.Hard Limit Control 3.Feed-in Power 4.PCC Limit Scheme Config
4.PCC Limit Scheme Config 4. IV Curve Scan
1.PCC Limit bit 2.Device type 3.Current limit percent 4.Lock enable bit 5.Reset flag bit 6.Lock flag bit cleared 7.Status query
When a component of PV modules is blocked or abnormal, multiple power peaks occur, the maximum power peaks can be traced by enabling this function.
The user can enter the scan period to make the inverter scan immediately.
4.IV Curve Scan 5. Logical Interface
1.Scan Control 2.Scan Period 3.Force Scan
Enable Disable ***min
Enables or disables a logical interface. This feature is only available under certain safety regulations.
5.Logical Interface
DRM0:
Enable
66
ESI 3-6K-S1
Commissioning
6. Factory Reset
DRMn:
Disable
6.Factory Reset
1.Clear Energy Data
2.Clear Events
3.Factory Reset
Clear the total energy yield of the inverter.
1.Clear Energy Data
Cancel
Clear the history events of the inverter.
Enter 0715
2.Clear Events 7. Reset Password
Cancel
7.Reset Password
Please Set the Password
Cancel
Confirm
8. Parallel Setting
User Password Set to
Cancel
Confirm
For the parallel system, please refer to <4.6 Parallel System > .
8.Parallel Settings
1.Parallel control
2.Set Master/Slave 3.Set Parallel Address 4.Save 1) Parallel control: Enable or disable the parallel function. This function must be enabled on both the master and slave machines.
User Manual
67
Commissioning
- Set master and slave: Set the master and slave. Select one inverter as the master and the others as slave machines.
- Set parallel address: Set the parallel address for each inverter. In a parallel system, each inverter should have a parallel address that does not duplicate that of other machines. (Note: Parallel addresses are different from communications addresses used for monitoring.)
- Save: Be sure to save after the Settings.
9. Reset Bluetooth
9.Reset Bluetooth 10. CT Calibration
Please Confirm
Succeed
Used to calibrate the orientation and phase of the CT. The battery should be charged or discharged when using this feature.
10.CT Calibration
Start CT Calibration?
11. NeutralPointGrounding
Succeed/Failed
11. NeutralPointGrounding 12. Set PCC Power Offset
Disable Enable
12.Set PCC Power Offset
Disable Enable
5.4.3 Energy Statistic 3.Energy Statistic
Today PV ……………………………………………….***kWh
68
ESI 3-6K-S1
Commissioning
Load …………………………………………..kWh Export………………………………………..kWh
Import……………………………………….kWh Charge……………………………………….kWh
Discharge…………………………………kWh
Month
PV ……………………………………………….kWh Load …………………………………………..kWh
Export………………………………………..kWh Import……………………………………….kWh
Charge……………………………………….kWh Discharge…………………………………kWh
Year
PV ……………………………………………….kWh Load …………………………………………..kWh
Export………………………………………..kWh Import……………………………………….kWh
Charge……………………………………….kWh Discharge…………………………………kWh
Lifetime
PV ……………………………………………….kWh Load …………………………………………..kWh
Export………………………………………..kWh Import……………………………………….kWh
Charge……………………………………….kWh Discharge…………………………………***kWh
User Manual
69
5.4.4 System Information 4.System Information
Commissioning
1.Inverter Info 2.Battery Info 3.Safety Param. 4.PCU Info 5.BMS Info
1.Inverter Info 2.Battery Info
Inverter Info (1) Product SN Hardware Version Power Level Inverter Info (2)
Software Version Country Safety Lib Version Inverter Info (3) Energy Storage
Mode RS485 Address Inverter Info (4) Logic Interface Power Factor Inverter
Info (5) Feed-in Limit Insulation Resistance
Battery 1 Info (1)
70
ESI 3-6K-S1
Commissioning
3.Safety parameters.
4.PCU Info User Manual
Battery Type Battery Capacity Depth of Discharge Battery 1 Info (2) Max Charge
(A) Max Discharge (A) Force Full Charge Start Force Full Charge End
Safety Param.(1) OVP 1 OVP 2 UVP 1 UVP 2 Safety Param. (2) OFP 1 OFP 2 UFP 1
UFP 2 Safety Param.(3) OVP 10mins
PCU Info(1) PCU serial number PCU hardware version
71
Commissioning PCU software version
4.BMS Info
BMS Info(1) BMS serial number BMS Software Version Battery Discharge
5.4.5 Event List
Once a fault occurs, the fault information is displayed on the event list page. The event list displays the current event records, including the event ID and occurrence time of each event. You can access the event list screen on the main screen to view detailed information about real-time events. Events are listed by occurrence time, and the latest events are listed first.
5.Event List
1.Current event 2.History event
ID042 IsoFault
2.Historical Fault Information
1.ID001 2020-4-3 14:11:45
2.ID005 2020-4-3 11:26:38
1.ID001 Grid OVP 2.ID005 GFCI Fault
5.4.6 Software Update
You can upgrade the software using the USB flash drive to maximize the performance of the product and avoid abnormal operation caused by software bugs. The upgrade file folder name is firmware. These three upgrade file names are HYD3-6K-HV_ARM_N2.bin, HYD3-6K-HV_DSPM_D0.bin,
72
ESI 3-6K-S1
Commissioning
HYD3-6K-HV_DSPS_N4.bin. Step 1 Insert the USB drive into the computer. Step 2 SOFAR will send the upgraded firmware to the users who need to upgrade. After receiving the file, decompress it and save it in a USB flash drive. Step 3 Insert the USB disk into the USB/WiFi interface of the machine. Step 4 Turn on DC switch. Step 5
6.Software Update
Enter 0715
Update(PCS)
Update(BMS)
Update(PCU)
Update(sofar)
Update safety package
Step 6 If the following error occurs, upgrade again. If this situation persists for
several times, contact technical support for help.
USB error
DSPM file error DSPS file error
ARM file error
Upgrading DSPM fail
Upgrading ARM fail Upgrading DSPS fail
Step 7 After the upgrading, turn off the DC switch, wait for the LCD screen to go off, then restore the WiFi connection, and then turn on the DC switch and AC switch again, and the inverter will enter the running state. You can view the current software version in System Info >> Software Version.
5.4.7 Battery real-time Info
7.Battery real-time Info
1.BMS Info
User Manual
73
1.BMS Info
2.PCU Info
Commissioning
BMS Info (BMS1) Batt Voltage…………………………………..*.V Batt
Current……………………………………..A Max Charge……………………………………...A Max
Discharge………………………………...A Batt SOC………………………………………………%
Batt SOH……………………………………………..%
Batt Temperature……………………………
Batt Cycles……………………………………………**T
2.PCU Info
PCU Info (PCU1) PCU low voltage…………………………..*.V PCU high
voltage…………………………***.V PCU low power…………………………..kW PCU
state……………………………………………..** Internal temp……………………………………
radiator temp……………………………………
Note
LCD menu may be modified without notice, please refer to the actually displayed interfaces as final. The latest menu can be downloaded from the official website.
74
ESI 3-6K-S1
Commissioning
5.5 Monitoring description
The operation information (generated energyalertoperation status) of the
inverter can be transferred to PC or uploaded to the server via WiFi(4G is
optional). Users can choose to use web or APP for monitoring and viewing
according to their needs. You need to register an account and bind the device
with the WiFi/4G SN number. The SN number of the WiFi/4G shall be affixed to
the package box and the WiFi/4G.
Web: https://home.solarmanpv.com (Recommended browser: Chrome58 Firefox49IE9
and above version)
User Manual
75
Troubleshooting and maintenance
6 Trouble shooting and maintenance
6.1 Troubleshooting
This section describes the potential errors for this product. Please read
carefully for the following tips when doing the troubleshooting:
View the warning or error information and error codes displayed on the display
to record all error information
If no error message is displayed on the LCD, perform the following steps to
check whether the current installation status meets the operating requirements
of the inverter:
— Is inverter be installed in a clean, dry, ventilated environment? — Is the
DC switch turn off? — Are the cable cross section area and length meet the
requirement? — Are the input and output connection and wiring in good
condition? — Are the configuration settings correctly for the particular
installation? — Is the display panel properly connected to the communication
cable and intact? To view the recorded fault information, perform the
following steps: On
the home screen, press “XXX” to enter the main menu. Select “Events” and press
“XXXX” to enter. Ground fault alarm The integrated inverters in this product
comply with the ground fault alarm monitoring of IEC 62109-2 clause 13.9. If a
grounding fault alarm occurs, the fault will be displayed on the LCD screen
with red light on, and the fault can also be found in the fault history. For
the machine equipped
76
ESI 3-6K-S1
Trouble shooting and maintenance
with WiFi/4G data collector, the alarm information can be seen on the corresponding monitoring website or received through the APP on the mobile phone. List of common events Table 6-1 List of common events
ID No. ID001
ID002
ID003
ID004
ID005 ID008 ID009 ID012 ID013
Name
Grid overvoltage
Grid undervolt
Grid overfreq
Grid underfreq
GFCI Fault IslandFault GridOVP Instant1 InvOVP Reflux OverLoad
Description
The grid voltage is too high
The grid voltage is too low
The grid frequency is too high
The grid frequency is too low
Charge Leakage Fault Island protection error Transient overvoltage of grid
voltage Inverter voltage error Feed-in Limit function is faulty
Solution
If the alarm occurs occasionally, the possible cause is that the electric grid
is abnormal occasionally. Inverter will automatically return to normal
operating status when the electric grid’s back to normal. If the alarm occurs
frequently, check whether the grid voltage/frequency is within the acceptable
range. If yes, please check the AC circuit breaker and AC wiring of the
inverter. If the grid voltage/frequency is NOT within the acceptable range and
AC wiring is correct, but the alarm occurs repeatedly, contact SOFAR technical
support to change the grid over-voltage, under- voltage, over-frequency,
under-frequency protection points after obtaining approval from the local
electrical grid operator.
Internal faults of inverter. Switch OFF inverter, wait for 5 minutes, then
switch ON inverter. Check whether the problem is solved. If not, please
contact SOFAR technical support.
User Manual
77
Trouble shooting and maintenance
ID032 N-PE fault
ID042 IsoFault
ID043 ID045 ID046
PEConnect Fault CT Disconnect Reversal Connect
ID047
Parallel Fault
ID049 ID050 ID057 ID059 ID065
Temp Fault_Bat TemFault Radiat1 TemFault Env1 TemFault Inv1 VbusRms Unbalan
ID066
VbusInst Unbalan
ID067 BusUVP ID068 BusZVP
ID069 PVOVP
Neutral ground fault
Low insulation impedance
Ground fault
CT Disconnected Input reverse connection error
Parallel Fault
Battery temperature protection Radiator temperature protection Ambient
temperature protection Module temperature protection Unbalanced bus voltage
RMS The transient value of bus voltage is unbalanced Bus undervoltage during
grid connection Bus voltage low
PV over-voltage
Check the insulation resistance between the photovoltaic array and ground
(ground), if there is a short circuit, the fault should be repaired in time.
If not solved, please contact SOFAR technical support. Check ac output PE wire
for grounding. Check whether the CT connection is correct Check whether the DC
input connection is correct Check whether parallel is enabled. Check whether
parallel addresses overlap. Check whether the parallel network is connected
properly. Make sure the inverter is installed in a place free from direct
sunlight. Make sure the inverter is installed in a cool/well-ventilated place.
Ensure that the inverter is installed vertically and the ambient temperature
is lower than the upper limit of the inverter temperature.
Internal faults of inverter. Switch OFF inverter, wait for 5 minutes, then
switch ON inverter. Check whether the problem is solved. If not, please
contact SOFAR technical support.
Check whether the PV series voltage (Voc) is higher than the maximum input
voltage of the inverter. If yes, adjust the number of PV modules in
78
ESI 3-6K-S1
Trouble shooting and maintenance
ID070 BatOVP
ID072
SwBus RmsOVP
Bat over-voltage
Inverter bus voltage RMS software overvoltage
series and reduce the PV string voltage to fit the input voltage range of the inverter. After correction, the inverter will automatically return to normal state. Check whether the battery overvoltage Settings are inconsistent with battery specifications
ID073
SwBus InstantOVP
Inverter bus voltage instantaneous value software overvoltage
ID081 ID082 ID083 ID084
ID085 ID086 ID087 ID088 ID098 ID099 ID100 ID102
SwBat OCP
DciOCP
SwOCP Instant SwBuck BoostOCP SwAc RmsOCP SwPvOCP Instant Ipv Unbalance Iac
Unbalance
HwBusOVP
HwBuck BoostOCP
HwBatOCP
HwPVOCP
Battery overcurrent protection by software Dci overcurrent protection Output instantaneous current protection BuckBoost software overcurrent The output RMS overcurrent PV overcurrent software protection PV flows in uneven parallel Unbalanced output current Inverter bus hardware overvoltage BuckBoost hardware overcurrent Battery hardware overcurrent PV hardware
Internal faults of inverter. Switch OFF inverter, wait for 5 minutes, then switch ON inverter. Check whether the problem is solved. If not, please contact SOFAR technical support.
User Manual
79
Trouble shooting and maintenance
ID103 HwACOCP
ID105
Meter Comm Lose
overcurrent Ac output hardware overcurrent
Meters communication fault
ID110 Overload1 Overload Protection
ID113
OverTem Derate
Overtemperature derating
ID114 ID116 ID124 ID125
ID129 ID130 ID131 ID132 ID133
Freq Derating Volt Derating LowBattery Bat Discharge Prohibited
HwAcOCP
BusOVP
HwBusOVP
Ipv Unbalance EPSBatOCP
Frequency derating
Voltage derating
Battery Low
Battery Discharge Prohibit
Output hardware overcurrent permanent fault Bus overvoltage permanent fault
Bus hardware overvoltage permanent fault PV unbalance current permanent fault
EPS mode battery overcurrent
Check whether the meter is enabled. Check whether the meter wiring is correct
Check whether the load power is greater than the inverter output power Make
sure the inverter is installed in a place free from direct sunlight. Make sure
the inverter is installed in a cool/well-ventilated place. Ensure that the
inverter is installed vertically and the ambient temperature is lower than the
upper limit of the inverter temperature.
Make sure the grid frequency and voltage are within acceptable range.
Check whether the battery voltage is too low or the battery depth of discharge
is too low.
Internal faults of inverter. Switch OFF inverter, wait for 5 minutes, then
switch ON inverter. Check whether the problem is solved. If not, please
contact SOFAR technical support.
80
ESI 3-6K-S1
Trouble shooting and maintenance
ID134
ID135 ID138 ID139 ID140 ID141 ID142
AcOCP Instant
Iac Unbalance PVOCP Instant
HwPVOCP
RelayFail Vbus Unbalance SpdFail(DC)
Output transient overcurrent permanent fault Output current imbalance permanent fault Input overcurrent permanent fault Input hardware overcurrent permanent fault Relay permanent fault Bus unbalance permanent fault DC SPD fault
ID145 USBFault
USB fault
Check the USB port of the inverter.
ID152 ID153 ID154 ID156
SafetyVer Fault SciLose(DC)
SciLose(AC) SoftVer Error
Safety parameter version error SCI communication error (DC) SCI communication error (AC) Inconsistent software versions
ID157
BMS1 Comm Fault
Lithium battery communication error
ID162 ID163
Remote Shutdown Drms0 Shutdown
ID177 BMS OVP
Remote shutdown
Drms0 shutdown BMS over-voltage alarm
Please contact SOFAR technical support.
Contact technical support to obtain the upgrade software. Make sure the
battery you use is compatible with the inverter. CAN communication is
recommended. Check whether the communication cable or port between the battery
and the inverter is faulty.
The inverter is shut down remotely.
The inverter is Drms0 shut down.
The lithium battery is faulty. Shut down the inverter and lithium
User Manual
81
Trouble shooting and maintenance
ID178 BMS UVP
ID179 BMS OTP
ID180 BMS UTP
ID181 BMS OCP
ID182 BMS Short
ID808 ID809
HS1 HighTemp Warning Env HighTemp Warning
ID813
StopChg Warning
ID814
StopDchg Warning
ID864
HS1 OverTemp Fault
ID865
OverTemp Fault_Env
ID867 ID872
Can1Com mFault SwBus InstantOVP
BMS under-voltage alarm BMS high temperature alarm BMS low temperature alarm BMS charge and discharge overcurrent BMS Short circuit alarm
battery. Wait for 5 minutes and start the inverter and lithium battery. Check
whether the problem is rectified. If not, contact technical support.
Please make sure the battery is installed in a cool well-ventilated place. If
The battery is installed correctly, please contact technical support.
Power off and wait for 2 hours. If the problem is not solved, please contact
technical support.
Radiator 1 high temperature alarm
Ambient high temperature alarm
Please make sure the battery is installed in a cool well-ventilated place. If The battery is installed correctly, please contact technical support.
Charging prohibition alarm
Discharging prohibition alarm
Over temperature protection of radiator 1 Over temperature protection of
ambient temperature Can1 communication failure Bus software overvoltage
If the battery is almost fully, no action is required. Otherwise, please
contact technical support. If the battery is almost empty, no action is
required. Otherwise, please contact technical support.
Power off and wait for 2 hours. If the problem is not solved, please contact
technical support.
If this fault occurs occasionally, wait a few minutes to see whether the
problem is solved. If this fault occurs frequently, please contact technical
82
ESI 3-6K-S1
Trouble shooting and maintenance
ID873 ID874 ID875 ID876 ID879 ID880 ID881 ID882 ID883 ID894 ID895 ID899 ID900 ID901 ID903
SwBus InstantUVP SwBat InstantOVP SwBat InstantUVP SwBat InstantOCP HwOCP
Unrecover BusAvgOV
Unrecover BatAvgUV Unrecover OCPInstant Unrecover HwOCP Unrecover BatActFail
Unrecover BusRPP BMS OVOCP SwBat AvgOCP SwAvg OverloadP
SwCBCOCP
Bus software undervoltage Battery software overvoltage Battery software
undervoltage Battery software overcurrent Hardware overcurrent
Permanent bus overvoltage
Permanent battery undervoltage Permanent Instant overcurrent Permanent
hardware overcurrent Permanent battery activation failed Permanent bus reverse
connection BMS overvoltage and overcurrent fault Battery average overcurrent
protection Average overload protection Software CBC overcurrent protection
support.
Restart the battery and wait for minutes. If the problem is not resolved,
please contact technical support.
Check whether the wiring is correct and restart the battery. If the problem is
not resolved, please contact technical support.
If this fault occurs occasionally, wait a few minutes to see whether the
problem is solved. If this fault occurs frequently, please contact technical
support.
Note
This table only shows part of the events, please go to our website for
details.
The events whose ID number over 800 are related to the battery module BTS 5K.
User Manual
83
Trouble shooting and maintenance
6.2 Daily Maintenance
This product usually does not require maintenance or calibration, but ensure
that the inverter and the heat sink of the battery module are not covered by
dust or dirt. Clean the inverter and battery modules:
Please clean the inverter with an air blower, a dry & soft cloth or a soft
bristle brush. Do NOT clean the inverter with water, corrosive chemicals,
detergent, etc. Clean radiator:
In order to ensure the normal function and long service life of the product,
it is necessary to ensure that there is enough air flow space around the
radiator at the rear of the product, and there is no material around the
radiator that obstructs the air flow, such as dust or snow, must be removed.
Clean the radiator with compressed air, a soft cloth, or a soft brush. Do not
use water, corrosive chemicals, cleaning agents, or strong detergents to clean
the heat sink.
84
ESI 3-6K-S1
Datasheet
7 Datasheet
Note Model PV Input
The following parameters may change without notice, please refer to the user manual and DataSheet on our website.
ESI 3K-S1
ESI 3.68K-
S1
ESI 4K-S1
ESI 4.6K-
S1
ESI 5K-S1
ESI 5K-S1
-A
ESI 6K-S1
Recommended Max. PV Power
4500 Wp
5400 Wp
6000 Wp
6900 Wp
7500 Wp
7500 Wp
9000 Wp
Max. input voltage Start-up Voltage[1] Rated Input Voltage MPPT Voltage Range Number of MPPT Max. Number of Input Strings per MPPT Max. Input Current Max. Isc Battery Voltage Range Number of Battery Input Channels Max. Charging/ Discharging Power Max. Charging/ Discharging Current
3 kW
3.68 kW
550 Vd.c. 100 Vd.c. 360 Vd.c. 85-520 Vd.c.
2 1/1
16/16 A 22.5/22.5 A 350-435 Vd.c.
2
4.6
4 kW
5 kW 5 kW 6 kW
kW
20 A
Battery Type[2]
Lithium-ion
User Manual
85
Datasheet
BMS
Communication
AC Input(Grid)
Rated Input
Voltage
Rated Input
Frequency
Max. Input Current
27.3/ 26.1/ 25.0 A
AC Output(Backup)
Rated Output
Voltage
Rated Output
Frequency
Rated Output
3
Power
kW
Rated Output Current
13.6/ 13.0/ 12.5 A
Rated Apparent
3
Power
kVA
Max. Output Current
13.6/ 13.0/ 12.5 A
Max. Apparent
3
Power
kVA
Peak Output Apparent Power
4.5 kVA, 60s
THDv(@ linear
load)
Switching Time
AC Output(Grid)
Rated Output
Voltage
Rated Output
Frequency
33.5/ 32.0/ 30.7 A
3.68 kW 16.7/ 16.0/ 15.3 A 3.68 kVA 16.7/ 16.0/ 15.3 A 3.68 kVA 5.52 kVA, 60s
CAN
L+N+PE,220/230/240 Va.c.
50/60 Hz
36.4/ 34.8/ 33.3 A
41.8/ 40.0/ 38.3 A
45.5/ 43.5/ 41.7 A
L+N+PE,220/230/240 Va.c.
50/60 Hz
4 kW 18.2/ 17.4/ 16.7 A 4 kVA 18.2/ 17.4/ 16.7 A 4 kVA 6 kVA, 60s
4.6 kW 20.9/ 20.0/ 19.2 A 4.6 kVA 20.9/ 20.0/ 19.2 A 4.6 kVA 6.9 kVA, 60s
5 kW 22.7/ 21.7/ 20.8 A
5 kVA 22.7/ 21.7/ 20.8 A
5 kVA 7.5 kVA, 60s
<3%
10 ms default
L+N+PE,220/230/240 Va.c. 50/60 Hz
45.5/ 43.5/ 41.7 A
5 kW 22.7/ 21.7/ 20.8 A
5 kVA 22.7/ 21.7/ 20.8 A
5 kVA 7.5 kVA, 60s
54.5/ 52.2/ 50.0 A
6 kW 27.3/ 26.1/ 25.0 A 6 kVA 27.3/ 26.1/ 25.0 A 6 kVA 9 kVA, 60s
86
ESI 3-6K-S1
Datasheet
Rated Output Power
Rated Output Current
Max. Apparent Power
Max. Output Current
THDi Power Factor Range Efficiency Max. MPPT Efficiency Max. Efficiency
European Efficiency Max. Efficiency of Charging/ Discharging[3] Protection DC
Switch PV Reverse Connection Protection Battery Reverse Connection Protection
Output Short Circuit Protection Output Overcurrent Protection Output
Overvoltage Protection
3 kW 13.6/ 13.0/ 12.5 A 3.3 kVA 15.0/ 14.3/ 13.8 A
3.68 kW 16.7/ 16.0/ 15.3 A 3.68 kVA 16.7/ 16.0/ 15.3 A
4 kW 18.2/ 17.4/ 16.7 A 4.4 kVA 20.0/ 19.1/ 18.3 A
4.6 kW 20.9/ 20.0/ 19.2 A 4.6 kVA 20.9/ 20.0/ 19.2 A <3%
5 kW 22.7/ 21.7/ 20.8 A 5.5 kVA 25.0/ 23.9/ 22.9 A
5 kW 22.7/ 21.7/ 20.8 A
5 kVA 22.7/ 21.7/ 20.8 A
6 kW 27.3/ 26.1/ 25.0 A 6.6 kVA 30.0/ 28.7/ 27.5 A
0.8 lagging-0.8 leading
99.9% 97.7% 97.7% 97.7% 97.8% 97.8% 97.8% 97.8% 97.0% 97.0% 97.0% 97.1% 97.1%
97.1% 97.1%
97%
Yes Yes
Yes Yes Yes
Yes
User Manual
87
Datasheet
Insulation Impedance Detection Residual Current Detection Anti-island Protection Surge Protection General Parameter Inverter Topology Protective Class IP Rating Overvoltage Category Operating Temperature Range Relative Humidity Range Max. Operating Altitude Standby Self-consumption [4] Dimensions(WH D) Cooling Mode Weight Communication Display
Yes
Yes Yes PV:Type II, AC:Type II Non-Isolation Class I IP65 AC III, DC II
-10 to +50 (derating above +45)
5%-95% 4000 m (derating above 2000 m)
<10 W
708410170 mm Natural
Approx. 26 kg CAN/RS485/WiFi,Optional:4G/LAN
LCD & APP
[1] Minimum PV voltage to start MPPT operation. [2] Please refer to document “SOFAR inverter Model compatible battery list”. [3] Battery-AC maximum efficiency of battery charge and discharge. [4] Standby loss at rated input voltage.
88
ESI 3-6K-S1
Manufacturer’s Warranty and Liability Terms
8 Manufacturer’s Warranty and Liability Terms
SOFAR standard warranty document
Warranty period and calculation method of SOFAR battery products refer to the
Quality Assurance Agreement of SOFAR ESI Series Household Energy Storage
System.
Extended warranty period
If the purchased battery exceeds the warranty period stipulated in the
Warranty Agreement of SOFAR ESI Series Household Energy Storage System, the
customer can apply for the extended warranty period by providing the serial
number of the product to the sales team of the company, and the Company has
the right to reject the purchase application for the extended warranty period
that does not meet the requirements. If the original buyer wants to apply for
the extended warranty service, please contact the sales team of SHENZHEN
SOFARSOLAR Co., LTD to purchase the products that exceed the extended warranty
period but have not passed the warranty period stipulated in the Warranty
Agreement of SOFAR ESI Series Household Energy Storage System, the original
buyer shall bear different extended premiums. Upon purchase of the extended
warranty service, our company will issue an extended warranty card to the
customer to confirm the extended warranty period.
Invalid warranty clause
User Manual
89
Manufacturer’s Warranty and Liability Terms
Equipment failure caused by the following reasons is not covered by the
warranty: 1) The “warranty card” has not been sent to the distributor or
Shenzhen SOFARSOLAR Co., LTD; 2) Without the consent of SHENZHEN SOFARSOLAR
Co., LTD to change equipment or replace parts; 3) Use unqualified materials to
support SHENZHEN SOFARSOLAR Co., LTD ‘s products, resulting in product
failure; 4) Technicians who don’t belong to SOFARSOLAR Co., LTD modify or
attempt to repair and erase the product serial number or silk screen; 5)
Incorrect installation, debugging and use methods; 6) Failure to comply with
safety regulations (certification standards, etc.); 7) Damage caused by
improper storage by dealers or end users; 8) Transportation damage (including
scratches caused by internal packaging during transportation). Please claim
directly from the transportation company or insurance company as soon as
possible and obtain damage identification such as container/package unloading;
9) Failure to follow the product user manual, installation manual and
maintenance guidelines; 10) Improper use or misuse of the device; 11) Poor
ventilation of the device; 12) The product maintenance process does not follow
relevant standards; 13) Failure or damage caused by natural disasters or other
force (such as earthquake, lightning strike, fire, etc).
90
ESI 3-6K-S1
Manufacturer’s Warranty and Liability Terms
User Manual
91
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>