Kaysun KCIA-26 DVR15 Commercial Range Instructions

July 3, 2024
Kaysun

Kaysun KCIA-26 DVR15 Commercial Range

Kaysun-KCIA-26-DVR15-Commercial-Range-PRODUCT

Product Information

Specifications

  • Model: KCIA-26 DVR15
  • Cooling Capacity (rated): 2.63 kW
  • Cooling Capacity (min. / max.): 0.35 kW / 3.07 kW
  • Heating Capacity (rated): 3.07 kW
  • Heating Capacity (min. / max.): 0.90 kW / 3.51 kW
  • Refrigerant: R-32
  • Refrigerant Charge: 0.65 kg
  • Liquid / Gas Pipe Diameter: 1/4 inch / 3/8inch
  • Net Weight (Outdoor Unit): 54 kg
  • Net Weight (Indoor Unit): 25.5 kg
  • Power Supply: 220-240V / 1 phase / 50 Hz

Product Usage Instructions

Installation

Ensure proper space for installation of the compact outdoor unit. Connect the indoor and outdoor units using the provided communication wiring.

Control via WiFi

Download the Kaysun app on your tablet or smartphone to control the units remotely. Use the weekly programmer for scheduling.

TWIN Installation

For improved air distribution and climate control, consider installing TWIN- type units with a single outdoor unit.

Fresh Air Supply

Ensure proper ventilation for fresh air supply to the system to maintain air quality indoors.

FAQ

Q: Can I install the Kaysun commercial range outdoors?

A: Yes, the Kaysun outdoor units are designed to be installed outdoors and require little space for installation.

Q: How can I control the units remotely?

A: You can control the Kaysun units remotely by using the WiFi feature and the dedicated Kaysun app on your tablet or smartphone.

Q: What is the benefit of using TWIN-type units?

A: TWIN-type units allow for greater distribution of air and improved climate control while utilizing a single outdoor unit, making them efficient for larger spaces.

The Kaysun R-32 commercial range includes axial outdoor units, in addition to several types of indoor units. The Kaysun outdoor units are compact, robust machines that require little space for installation. They can be used with up to 75 metres of refrigerant piping and a height difference of 30 metres, in accordance with capacity.

Full DC Inverter

The exclusive Kaysun GENIUS CORE algorithm provides the system with complete stability. Using the Alpha chip, the compressor, PWM module and DC motors in the unit work in an optimum way, adapting to the real demand and preventing losses of energy.
The dynamic adjustment of the electrical power guarantees constant equilibrium for the system, meaning the Kaysun when operating for long periods.

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-2

CASSETTE (600×600)

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-3

Set Model KCIA-26 DVR15 KCIA-35 DVR15 KCIA-52 DVR15

Set

Cooling capacity rated kW 2.63 3.52 5.28
Cooling capacity min. / max. kW 0.35 / 3.07 0.85 / 4.16 2.9 / 5.59
Heating capacity rated kW 3,07 3.81 5.57
Heating capacity min. / max. kW 0.90 / 3.51 0.47 / 4.34 2.37 / 6.1
Cooling input rated W 800 1015 1550
Cooling input min. / max. W 145 / 1100 160 / 1450 720 / 2040
Heating input rated W 1000 1020 1560
Heating input min. / max. W 300 / 1300 125 / 1390 700 / 1950
EER 3.29 3.47 3.41
COP 3.07 3.73 3.57
SEER 6.3 – A++ 6.8 – A++ 6.5 – A++
SCOP 4.1 – A+ 4.1 – A+ 4.1 – A+
Shielded communication wiring mm² 4×1 4×1 4×1
Air flow m³/h 2000 2000 2100
--- --- --- --- ---
Sound pressure dB(A) 54 54 56
Sound power level dB(A) 61 62
Width / Height / Depth mm 765 / 555 / 303 765 / 555 / 303 805 / 555 / 330
Net weight kg 24.6 24.6 32.5
Power supply V/ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50
Power wiring mm² (2+T)x2,5 (2+T)x2,5 (2+T)x2,5
Air flow low / medium / high m³/h 330 / 520 / 620 330 / 520 / 620 300 /

540 / 660
---|---|---|---|---
Sound pressure| dB(A)| 25.5 /| / 31.5 / 38.5 /| / 42 /| 25.5 /| / 31.5 / 38.5 /| / 42 /| 25 /| / 31.5 / 41 /| / 44 /
Sound power level| dB(A)| 55| 55| 59
Width / Height / Depth| mm| 570 / 245 / 570| 570 / 245 / 570| 570 / 245 / 570
Net weight| kg| 16.2| 16.2| 16.2
Power supply| V/ph/Hz| With communication| With communication| With communication
Panel; Model| KPA-03B 600×600| KPA-03B 600×600| KPA-03B 600×600
Panel; Width / Height / Depth| mm| 620 / 50 / 620| 620 / 50 / 620| / /
Panel; Net weight| kg| 2.7| 2.7|

Refrigerant

Type refrigerant R-32 R-32 R-32
Refrigerant charge kg 0.65 0.71
Liquid / Gas pipe diameter inch 1/4” / 3/8” 1/4” / 3/8”
Piping total length m 25 25
Vertical piping max. length m 10 10

Working range

Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50
---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24

Cooling and heating capacity. Cooling and heating input. Energy efficiency:
Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.

Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.

Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).

Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility, see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.

CASSETTE (840×840)

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-4

Set model| | KCISA-71 DVR15| KCISA-90 DVR15| KCISA-105 DVR14
---|---|---|---|---

SET

Cooling capacity rated kW 7.03 8.79 10.55
Cooling capacity min. / max. kW 3.3 / 7.91 2.23 / 9.38 2.7 / 11.43
Heating capacity rated kW 7.52 9.38 11.14
Heating capacity min. / max. kW 2.79 / 8.50 2.7 / 9.73 2.78 / 12.66
Heating capacity rated at -7°C kW 3.31 6.55 7.52
Cooling input rated W 2320 2750 4000
Cooling input min. / max. W 780 / 2750 190 / 3000 890 / 4150
Heating input rated W 1900 2450 3000
Heating input min. / max. W 610 / 2300 430 / 2550 780 / 4000
EER 2.88 3.2 2.65
COP 4.10 4 3.68
COP at -7°C 2.65 2.55 2.6
SEER 6.3 – A++ 6.6 – A++ 6.1 – A++
SCOP 4.1 – A+ 4.2 – A+ 4 – A+
Shielded communication wiring mm² 4×1 4×1 4×1
Air flow m³/h 3500 3800 4000
--- --- --- --- ---
Sound pressure dB(A) 60 62 63
Sound power level dB(A) 68 70 70
Width / Height / Depth mm 890 / 673 / 342 946 / 810 / 410 946 / 810 / 410
Net weight kg 41.9 51 66.900
Power supply V/ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50
Power wiring mm² (2+T)x2,5 (2+T)x2,5 (2+T)x4
Air flow low / medium / high m³/h 992 / 1118 / 1247 1300 / 1530 / 1700

1300 / 1530 / 1700
---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 42 / 47.5 / 50| 46 / 48 / 50.5| 46 / 49 / 51
Sound power level| dB(A)| 59| 63| 64
Width / Height / Depth| mm| 830 / 205 / 830| 830 / 245 / 830| 830 / 245 / 830
Net weight| kg| 21.6| 24.6| 27.2
Power supply| V/ph/Hz| With communication| With communication| With communication
Power wiring| mm²| With communication| With communication| With communication
Panel; Model| LCAC KPA4-04B 840×840| LCAC KPA4-04B 840×840| LCAC KPA4-04B 840×840
Panel; Width / Height / Depth| mm| 950 / 55 / 950| 950 / 55 / 950| 950 / 55 / 950
Panel; Net weight| kg| 6| 6| 6
Type refrigerant| R-32| R-32| R-32
---|---|---|---
Refrigerant charge| kg| 1.9| 2| 2.4
Liquid / Gas pipe diameter| inch| 3/8” / 5/8”| 3/8” / 5/8”| 3/8” / 5/8”
Piping total length| m| 50| 50| 75
Vertical piping max. length| m| 25| 25| 30
Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50
---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24

Cooling and heating capacity. Cooling and heating input. Energy efficiency:
Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.
Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.
Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).
Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility, see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.

Set model KCISA-140 DTR15 KCISA-160 DTR15
Cooling capacity rated kW 14.07 15.24
--- --- --- ---
Cooling capacity min. / max. kW 3.52 / 15.83 4.10 / 16.12
Heating capacity rated kW 16.12 18.17
Heating capacity min. / max. kW 4.20 / 17.29 4.40 / 19.05
Heating capacity rated at -7°C kW 9.74 10.53
Cooling input rated W 4980 5700
Cooling input min. / max. W 810 / 6350 1000 / 6250
Heating input rated W 4580 5700
Heating input min. / max. W 900 / 5500 1020 / 6350
EER 3.03 2.95
COP 3.5 3.22
COP at -7°C 2.68 2.59
SEER 6.1 – A++ 6.1 – A++
SCOP 4.0 – A+ 4.0 – A+
Shielded communication wiring mm² 4×1 4×1
Air flow m³/h 5600 5600
--- --- --- ---
Sound pressure dB(A) 64 65
Sound power level dB(A) 73 75
Width / Height / Depth mm 990 / 975 / 375 990 / 975 / 375
Net weight kg 90.0 92.0
Power supply V/ph/Hz 380-415/3/50 380-415/3/50
Power wiring mm² (4+T)x2,5 (4+T)x2,5
Air flow low / medium / high m³/h 1600 / 1750 / 1900 1650 / 1850 / 2000
--- --- --- ---
Sound pressure low / medium / high dB(A) 48 / 50.5 / 52.5 49.5 / 52 / 54.5
Sound power level dB(A) 66 66
Width / Height / Depth mm 830 / 287 / 830 830 / 287 / 830
Net weight kg 29.3 29.3
Power supply V/ph/Hz With communication With communication
Power wiring mm² With communication With communication
Panel; Model LCAC KPA4-04B 840×840 LCAC KPA4-04B 840×840
Panel; Width / Height / Depth mm 950 / 55 / 950 950 / 55 / 950
Panel; Net weight kg 6 6
Type refrigerant R-32 R-32
--- --- ---
Refrigerant charge kg 2.9 3
Liquid / Gas pipe diameter inch 3/8” / 5/8” 3/8” / 5/8”
Piping total length m 75 75
Vertical piping max. length m 30 30

Cooling and heating capacity. Cooling and heating input. Energy efficiency:

Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.
Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.
Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).
Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility, see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-6

Set model KPCA-140 DTR15 KPCA-160 DTR15

Set

Cooling capacity rated kW 14.07 15.24
Cooling capacity min. / max. kW 3.52 / 15.24 4.10 / 16.12
Heating capacity rated kW 16.12 18.17
Heating capacity min. / max. kW 4.10 / 17.59 4.40 / 19.35
Heating capacity rated at -7°C kW 9.91 10.53
Cooling input rated W 5000 5900
Cooling input min. / max. W 910 / 6200 1100 / 6500
Heating input rated W 4800 5950
Heating input min. / max. W 950 / 5950 1120 / 6350
EER 2.83 2.76
COP 3.07 3
COP at -7°C 2.65 2.6
SEER 6.1 – A++ 6.1 – A++
SCOP 4.0 – A+ 4.0 – A+
Shielded communication wiring mm² 4×1 4×1

Outdoor unit

Air flow m³/h 5600 5600
Sound pressure dB(A) 64 65
Sound power level dB(A) 73 75
Width / Height / Depth mm 990 / 975 / 375 990 / 975 / 375
Net weight kg 90.0 92.0
Power supply V/ph/Hz 380-415/3/50 380-415/3/50
Power wiring mm² (4+T)x2,5 (4+T)x4
Air flow low / medium / high m³/h 1600 / 1850 / 2200 1650 / 1950 /
--- --- --- ---
Sound pressure low / medium / high dB(A) 46 / 50 / 53 48 / 52 / 55
Sound power level dB(A) 67 67
Width / Height / Depth mm 1650 / 235 / 675 1650 / 235 / 675
Net weight kg 41.7 42.3
Power supply V/ph/Hz With communication With communication
Power wiring mm² With communication With communication

Refrigerant

Type refrigerant R-32 R-32
Refrigerant charge kg 2.4
Liquid / Gas pipe diameter inch 3/8” / 5/8”
Piping total length m 75
Vertical piping max. length m 30

Working range

Floor/Ceiling

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-7

Set model| | KPCA-52 DVR14| KPCA-71 DVR15| KPCA-105 DVR14
---|---|---|---|---
Cooling capacity rated| kW| 5.28| 7.03| 10.55
---|---|---|---|---
Cooling capacity min. / max.| kW| 2.71 / 5.86| 3.22 / 7.95| 2.73 / 11.78
Heating capacity rated| kW| 5.57| 7.62| 11.72
Heating capacity min. / max.| kW| 2.42 / 6.3| 2.72 / 8.50| 2.81 / 12.78
Heating capacity rated at -7°C| kW| 3.54| 4.87| 7.61
Cooling input rated| W| 1450| 2300| 4000
Cooling input min. / max.| W| 670 / 2027| 750 / 2730| 890 / 4300
Heating input rated| W| 1500| 1980| 3350
Heating input min. / max.| W| 540 / 1640| 650 / 2940| 780 / 3950
EER| 3.7| 2.95| 2.6
COP| 3.75| 4| 3.6
COP at -7°C| 2.88| 2.72| 2.5
SEER| 6.1 – A++| 6.1 – A++| 6.1 – A++
SCOP| 4 – A+| 4.1 – A+| 4 – A+
Shielded communication wiring| mm²| 4×1| 4×1| 4×1
Air flow| m³/h| 2100| 3500| 3800
---|---|---|---|---
Sound pressure| dB(A)| 56| 60| 62
Sound power level| dB(A)| 65| 68| 70
Width / Height / Depth| mm| 805 / 555 / 330| 890 / 673 / 342| 946 / 810 / 410
Net weight| kg| 32.5| 41.9| 52.8
Power supply| V/ph/Hz| 220-240/1/50| 220-240/1/50| 220-240/1/50
Power wiring| mm²| (2+T)x1,5| (2+T)x2,5| (2+T)x4
Air flow low / medium / high| m³/h| 723 / 839 / 958| 853 / 1023 / 1192| 1504 / 1728 / 1955
---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 37 / 41 / 44| 43 / 47 / 51| 45 / 47.5 / 51
Sound power level| dB(A)| 59| 55| 65
Width / Height / Depth| mm| 1068 / 235 / 675| 1068 / 235 / 675| 1650 / 235 / 675
Net weight| kg| 28| 28| 41.5
Power supply| V/ph/Hz| With communication| With communication| With communication
Power wiring| mm²| With communication| With communication| With communication
Type refrigerant| R-32| R-32| R-32
---|---|---|---
Refrigerant charge| kg| 1.15| 1.5| 2
Liquid / Gas pipe diameter| inch| 1/4” / 1/2”| 3/8” / 5/8”| 3/8” / 5/8”
Piping total length| m| 30| 50| 50
Vertical piping max. length| m| 20| 25| 25

Ducts

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-9

Set model| | KPCA-105 DTR14| KPCA-125 DVR14| KPCA-140 DVR15
---|---|---|---|---

Set

Cooling capacity rated kW 10.55 12.02 14.07
Cooling capacity min. / max. kW 2.73 / 11.43 2.93 / 12.31 3.52 / 15.83
Heating capacity rated kW 11.72 13.48 16.12
Heating capacity min. / max. kW 2.78 / 12.78 3.37 / 14.07 4.10 / 17.30
Heating capacity rated at -7°C kW 7.61 8.41 9.91
Cooling input rated W 3900 4200 5000
Cooling input min. / max. W 900 / 4250 680 / 4350 810 / 6350
Heating input rated W 3350 3700 4750
Heating input min. / max. W 800 / 3950 750 / 4250 910 / 6050
EER 2.6 2.85 2.83
COP 3.6 3.6 3.07
COP at -7°C 2.5 2.65 2.65
SEER 6.1 – A++ 6.1 – A++ 6.1 – A++
SCOP 4 – A+ 4 – A+ 4.0 – A+
Shielded communication wiring mm² 4×1 4×1 4×1

Outdoor unit

Air flow m³/h 4000 4000 5600
Sound pressure dB(A) 63 63 64
Sound power level dB(A) 70 70 73
Width / Height / Depth mm 946 / 810 / 410 946 / 810 / 410 990 / 975 / 375
Net weight kg 66.90 71 82.0
Power supply V/ph/Hz 380-415/3/50 220-240/1/50 220-240/1/50
Power wiring mm² (4+T)x2,5 (2+T)x4 (4+T)x2,5

Indoor unit

Air flow low / medium / high| m³/h| 1504 / 1728 / 2100| 1600 / 1850 / 2200| 1600 / 1850 / 2200
---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 45 / 48 / 51.5| 46 / 50 / 53| 46 / 50 / 53
Sound power level| dB(A)| 65| 67| 67
Width / Height / Depth| mm| 1650 / 235 / 675| 1650 / 235 / 675| 1650 / 235 / 675
Net weight| kg| 41.5| 41.7| 41.7
Power supply| V/ph/Hz| With communication| With communication| With communication
Power wiring| mm²| With communication| With communication| With communication

Refrigerant

Type refrigerant R-32 R-32 R-32
Refrigerant charge kg 2.4 2.8
Liquid / Gas pipe diameter inch 3/8” / 5/8” 3/8” / 5/8”
Piping total length m 75 75
Vertical piping max. length m 30 30

Working range

Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50
---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24

Cooling and heating capacity. Cooling and heating input. Energy efficiency:Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.
Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.
Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in
accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).
Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility,
see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-9

Set

Cooling capacity rated kW 12.02 14.07 14.07 15.24
Cooling capacity min. / max. kW 2,93 / 12,31 3,51 / 15,83 3,51 / 15,83

4,10 / 17,30
Heating capacity rated| kW| 13,48| 16,12| 16,12| 17,59
Heating capacity min. / max.| kW| 3,37 / 14,07| 4,10 / 17,59| 4,10 / 17,59| 4,39 / 20,52
Cooling input rated| W| 4200| 4800| 4800| 5250
Cooling input min. / max.| W| 680 / 4500| 810 / 6450| 810 / 6450| 1030 / 6650
Heating input rated| W| 3450| 4600| 4600| 5150
Heating input min. / max.| W| 750 / 4100| 950 / 5800| 950 / 5800| 950 / 6600
EER| 2.86| 2.93| 2.93| 2.90
COP| 3.91| 3.50| 3.50| 3.42
SEER| 6.1 – A++| 6.1 – A++| 6.1 – A++| 6.1 – A++
SCOP| 4.0 – A+| 4.0 – A+| 4.0 – A+| 4.0 – A+
Shielded communication wiring| mm²| 4×1| 4×1| 4×1| 4×1

Outdoor unit

Air flow m³/h 4000 5600 5600 5600
Sound pressure dB(A) 63 64.5 64.5 65
Sound power level dB(A) 73 73 73 74
Width / Height / Depth mm 946 / 810 / 410 990 / 975 / 375 990 / 975 / 375

990 / 975 / 375
Net weight| kg| 71.0| 90.0| 82.0| 92.0
Power supply| V/ph/Hz| 220-240/1/50| 380-415/3/50| 220-240/1/50| 380-415/3/50
Power wiring| mm²| (2+T)x4| (4+T)x2,5| (2+T)x4| (4+T)x2,5

Indoor unit

Air flow low / medium / high| m³/h| 1300 / 1700 / 2000| 1300 / 1700 / 2000| 1300 / 1700 / 2000| 1500 / 1900 / 2200
---|---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 36 / 37.5 / 39| 40 / 42 / 44| 40 / 42 / 44| 41.5 / 43 / 44.5
Sound power level| dB(A)| 65| 65| 65| 66
Max. pressure available| Pa| 160| 200| 200| 200
Width / Height / Depth| mm| 1200 / 245 / 750| 1200 / 245 / 750| 1200 / 245 / 750| 1200 / 300 / 750
Net weight| kg| 40.4| 40.4| 40.4| 47.4
Possibility of vertical installation| Yes| Yes| Yes| Yes

Refrigerant

Type refrigerant R-32 R-32 R-32 R-32
Refrigerant charge kg 2.8 2.9 2.9
Liquid / Gas pipe diameter inch 3/8” / 5/8” 3/8” / 5/8” 3/8” / 5/8”

/ 5/8”
Piping total length| m| 75| 75| 75| 75
Vertical piping max. length| m| 30| 30| 30| 30

Working range

Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50| -15 / 50
---|---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24| -15 / 24

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-9

Set Model| | KPDA-125 DVR15| KPDA-140 DTR15| KPDA-140 DVR15| KPDA-160 DTR15
---|---|---|---|---|---
Cooling capacity rated| kW| 12.02| 14.07| 14.07| 15.24
---|---|---|---|---|---
Cooling capacity min. / max.| kW| 2,93 / 12,31| 3,51 / 15,83| 3,51 / 15,83| 4,10 / 17,30
Heating capacity rated| kW| 13,48| 16,12| 16,12| 17,59
Heating capacity min. / max.| kW| 3,37 / 14,07| 4,10 / 17,59| 4,10 / 17,59| 4,39 / 20,52
Cooling input rated| W| 4200| 4800| 4800| 5250
Cooling input min. / max.| W| 680 / 4500| 810 / 6450| 810 / 6450| 1030 / 6650
Heating input rated| W| 3450| 4600| 4600| 5150
Heating input min. / max.| W| 750 / 4100| 950 / 5800| 950 / 5800| 950 / 6600
EER| 2.86| 2.93| 2.93| 2.90
COP| 3.91| 3.50| 3.50| 3.42
SEER| 6.1 – A++| 6.1 – A++| 6.1 – A++| 6.1 – A++
SCOP| 4.0 – A+| 4.0 – A+| 4.0 – A+| 4.0 – A+
Shielded communication wiring| mm²| 4×1| 4×1| 4×1| 4×1

Outdoor unit

Air flow m³/h 4000 5600 5600 5600
Sound pressure dB(A) 63 64.5 64.5 65
Sound power level dB(A) 73 73 73 74
Width / Height / Depth mm 946 / 810 / 410 990 / 975 / 375 990 / 975 / 375

990 / 975 / 375
Net weight| kg| 71.0| 90.0| 82.0| 92.0
Power supply| V/ph/Hz| 220-240/1/50| 380-415/3/50| 220-240/1/50| 380-415/3/50
Power wiring| mm²| (2+T)x4| (4+T)x2,5| (2+T)x4| (4+T)x2,5

Indoor unit

Air flow low / medium / high| m³/h| 1300 / 1700 / 2000| 1300 / 1700 / 2000| 1300 / 1700 / 2000| 1500 / 1900 / 2200
---|---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 36 / 37.5 / 39| 40 / 42 / 44| 40 / 42 / 44| 41.5 / 43 / 44.5
Sound power level| dB(A)| 65| 65| 65| 66
Max. pressure available| Pa| 160| 200| 200| 200
Width / Height / Depth| mm| 1200 / 245 / 750| 1200 / 245 / 750| 1200 / 245 / 750| 1200 / 300 / 750
Net weight| kg| 40.4| 40.4| 40.4| 47.4
Possibility of vertical installation| Yes| Yes| Yes| Yes

Refrigerant

Type refrigerant R-32 R-32 R-32 R-32
Refrigerant charge kg 2.8 2.9 2.9
Liquid / Gas pipe diameter inch 3/8” / 5/8” 3/8” / 5/8” 3/8” / 5/8”

/ 5/8”
Piping total length| m| 75| 75| 75| 75
Vertical piping max. length| m| 30| 30| 30| 30

Working range

Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50| -15 / 50
---|---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24| -15 / 24

Cooling and heating capacity. Cooling and heating input. Energy efficiency:Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.
Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.
Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).
Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility, see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-10

Set Model KPVA-160 DTR14
Cooling capacity rated kW 15,25
--- --- ---
Cooling capacity min. / max. kW 4,11 / 16,13
Heating capacity rated kW 18,18
Heating capacity min. / max. kW 4,40 / 18,77
Cooling input rated W 6000
Cooling input min. / max. W 1000 / 7200
Heating input rated W 5600
Heating input min. / max. W 1020 / 7200
EER 2.54
COP 3.24
SEER 5.8
SCOP 4.0 – A+
Shielded communication wiring mm² 4×1

Outdoor unit

Air flow m³/h 5600
Sound pressure dB(A) 65
Width / Height / Depth mm 980 / 975 / 375
Net weight kg 92
Power supply V/ph/Hz 380-415/3/50
Power wiring mm² (4+T)x4

Indoor unit

Air flow low / medium / high m³/h 1600 / 1750 / 1950
Sound pressure dB(A) 40 /
Sound power level dB(A) 64
Width / Height / Depth mm 600 / 1934 / 455
Net weight kg 61.4

Twin Cassette 840×840

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-12

Set model| | KPCA-52 DTR14 TWIN| KPCA-52 DVR14 TWIN| KPCA-71 DVR15 TWIN| KPCA-71 DTR15 TWIN
---|---|---|---|---|---

Set

Cooling capacity rated kW 2x 5,28 2x 5,28 14.07 14.07
Cooling capacity min. / max. kW 2.71 / 5.86 2.71 / 5.86 3,51 / 15,83 3,51

/ 15,83
Heating capacity rated| kW| 2x 5,57| 2x 5,57| 16,12| 16,12
Heating capacity min. / max.| kW| 2.42 / 6.3| 2.42 / 6.3| 4,10 / 17,59| 4,10 / 17,59
Cooling input rated| W| 1450| 1450| 4800| 4800
Cooling input min. / max.| W| 670 / 2027| 670 / 2027| 810 / 6450| 810 / 6450
Heating input rated| W| 1500| 1500| 4600| 4600
Heating input min. / max.| W| 540 / 1640| 540 / 1640| 950 / 5800| 950 / 5800
EER| –| –| 2.93| 2.93
COP| 3.61| 3.71| 3.50| 3.50
COP at -7°C| 2.6| 2.6| |
SEER| 6.1 – A++| 6.1 – A++| 6.1 – A++| 6.1 – A++
SCOP| 4 – A+| 4 – A+| 4.0 – A+| 4.0 – A+
Shielded communication wiring| mm²| 4×1| 4×1| 4×1| 4×1

Outdoor unit

Air flow m³/h 4000 3800 5600 5600
Sound pressure dB(A) 63 62 64.5 64.5
Sound power level dB(A) 70 70 73 73
Width / Height / Depth mm 946 / 810 / 410 946 / 810 / 410 990 / 975 / 375

990 / 975 / 375
Net weight| kg| 66.90| 52.8| 82.0| 90.0
Power supply| V/ph/Hz| 380-415/3/50| 220-240/1/50| 220-240/1/50| 380-415/3/50
Power wiring| mm²| (4+T)x2,5| (2+T)x4| (4+T)x2,5| (4+T)x2,5

Indoor unit

Air flow low / medium / high| m³/h| 723 / 839 / 958| 723 / 839 / 958| 853 / 1023 / 1192| 853 / 1023 / 1192
---|---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 37 / 41 / 44| 37 / 41 / 44| 43 / 47 / 51| 43 / 47 / 51
Sound power level| dB(A)| 59| 59| 55| 55
Width / Height / Depth| mm| 1068 / 235 / 675| 1068 / 235 / 675| 1068 / 235 / 675| 1068 / 235 / 675
Net weight| kg| 28| 28| 28| 28

Refrigerant

Type refrigerant R-32 R-32 R-32 R-32
Refrigerant charge kg 2.4 2.4 2.9
Liquid / Gas pipe diameter inch 3/8” / 5/8” 3/8” / 5/8” 3/8” / 5/8”

/ 5/8”
Piping total length| m| 75| 75| 75| 75
Vertical piping max. length| m| 30| 30| 30| 30

Working range

Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50| -15 / 50
---|---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24| -15 / 24

Cooling and heating capacity. Cooling and heating input. Energy efficiency:

Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.
Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.
Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).
Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility, see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.

Twin Duct

Kaysun-KCIA-26-DVR15-Commercial-Range-FIG-13

Set model| | KPDA-35 DVR15 TWIN| KPDA-52 DTR15 TWIN| KPDA-52 DVR15 TWIN
---|---|---|---|---

Set

Cooling capacity rated kW 7.03 10.55 10.55
Cooling capacity min. / max. kW 3,22 / 7,91 2.75 / 11.14 2.73 / 11.78
Heating capacity rated kW 7,62 11.72 11.72
Heating capacity min. / max. kW 2,78 / 8,56 2.78 / 12.78 2.78 / 12.84
Cooling input rated W 2280 3950 4000
Cooling input min. / max. W 750 / 2860 900 / 4150 890 / 4200
Heating input rated W 2000 3250 3250
Heating input min. / max. W 640 / 2500 800 / 3950 780 / 4000
EER 3.08 2.6 2.7
COP 3.81 3.71 3.71
SEER 6.5 – A++ 6.1 – A++ 6.1 – A++
SCOP 4.2 – A+ 4.0 – A+ 4.0 – A+
Shielded communication wiring mm² 4×1 4×1 4×1

Outdoor unit

Air flow m³/h 3500 4000 4000
Sound pressure dB(A) 60 63 63
Sound power level dB(A) 69 70 70
Width / Height / Depth mm 890 / 673 / 342 946 / 810 / 410 946 / 810 / 410
Net weight kg 41.9 80.5 66.9
Power supply V/ph/Hz 220-240/1/50 380-415/3/50 220-240/1/50
Power wiring mm² (2+T)x2,5 (4+T)x2,5 (2+T)x4

Indoor unit

Air flow low / medium / high| m³/h| 300 / 480 / 600| 600 / 780 / 900| 600 / 780 / 900
---|---|---|---|---
Sound pressure low / medium / high| dB(A)| 30 / 32 / 34| 34 / 31 / 36.5| 34 / 31 / 36.5
Sound power level| dB(A)| 56| 53| 53
Max. pressure available| Pa| 100| 160| 160
Width / Height / Depth| mm| 700 / 200 / 506| 700 / 245 / 750| 700 / 245 / 750
Net weight| kg| 18| 24.4| 24.4
Possibility of vertical installation| No| Yes| Yes

Refrigerant

Type refrigerant R-32 R-32 R-32
Refrigerant charge kg 1.4 2.4
Liquid / Gas pipe diameter inch 3/8” / 5/8” 3/8” / 5/8”
Piping total length m 50 75
Vertical piping max. length m 25 30

Working range

Outdoor ambient temperature for cooling min. / max.  °C| -15 / 50| -15 / 50| -15 / 50
---|---|---|---
Outdoor ambient temperature for heating min. / max.  °C| -15 / 24| -15 / 24| -15 / 24

Cooling and heating capacity. Cooling and heating input. Energy efficiency:

Data for standard conditions. The actual operation conditions depend on the place in which the equipment has been installed and the use made of it.
Sound pressure: Measurement of the sound pressure is taken using a semi- anechoic chamber at a distance of 1 m from the machine.
Power wiring: The power wiring is up to 10 m approximately. It must be calculated more precisely for each installation.
Supplementary charge: The initial factory charge of the machines is valid for the first 5 m (liquid line). For greater distances, a supplementary charge is required, in accordance with the formula 0.012 kg/m × (L-5) in the liquid line is 1/4”. For greater diameters, use 0.024 kg/m × (L-5).
Compatible controllers: The units can integrate one of the controllers from the table or the one recommended by Kaysun. For further information regarding compatibility, see the chapter on Controllers.
NOTE: Before installing these units, current legislation regarding refrigerant gases must be consulted.
*In these models it is possible to combine horizontal and vertical units. If you require the vertical, request the reference with the V.

MAIN OFFICE

Blasco de Garay, 4-6 08960 Sant Just Desvern (Barcelona)
Phone: +34 93 480 33 22 www.frigicoll.es
www.kaysun.es

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals