FITO QR-NA12V Wireless Inkable Smoke Alarm Coordinator Instruction Manual

June 29, 2024
FITO

FITO QR-NA12V Wireless Inkable Smoke Alarm Coordinator

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE!
This manual contains important information for the correct installation and use of the product. Please read this information carefully and retain the instruction for future reference. QR-NA12V relay to establish a connection between a network of ASD-10QR smoke alarms and a fire- or intruder control panel.

BASIC FUNCTIONS
Compatible with all alarm control panels

  • Connection to the control panel through a dry contact Creates a wireless network with up to 23 smoke alarms
  • One button operation for all modes
  • Compact size
  • Self-healing feature LED indication
  • Ability to amplify the signal through an antenna Made in Europe

SPECIFICATIONS

  • Input voltage: 9V to 15V
  • RF frequency: 868.100 (<1 % duty cycle)
  • RF power: +14 dBm max
  • RF range: Up to 120 m. open space
  • With external antenna: Up to 300 m. open space
  • NO / NC contact: with active load: 1 A/30VDC; 0.5A/125VAC
    • Max. switching power: 30W (1A/30VDC), 62.SVA (0.3A/125VAC)
    • Max. switching voltage: 11 0VDC
    • Max. switching current: 1 A DC
  • Operating temperature: 0°C to+ 55°C
  1. Antenna connector (ANT)
  2. Selection of NO/NC (normally open/normally closed) contact XP1
  3. NO/NC contact (COM)
  4. Test button (TEST)
  5. Power supply terminal (12V)
  6. Mode LED indication (HL 1)

CONNECTION PROCEDURE

Connect the QR-NA 12V to the alarm control panel and power it. Upon successful joining, the QR-NA 12V enters Standby mode, which is indicated oy one-blink of the LED indicator every 3-4 seconds. Upon receiving an event signal from one of the fire detectors in the network, the QR-NA 12V switches to “Fire” mode, where the relay is turned on. This is indicated by one blink of the LED indicator every 1 second. Depending on the type and requirements of the control panel, the coordinator allows connection through a normally open (NO) or normally closed (NC) contact.

PROCEDURE OF JOINING THE QR-NA12V TO A SECURITY EXCHANGE:
jumper XP1 (fig. 1, pos. 2) sets the use of a normally open (NO) or normally closed (NC) contact via the COM terminal (fig. 1, item 3) a free area of the control unit is connected

  • via the 12V terminal (fig. 1, item 5) the supply voltage from the central unit with a nominal value of 12V is connected, observing the polarity

ATTENTION!
With a normally closed contact, if the wires are interchanged when connecting to the COM terminal and the 12V terminal, it is possible to damage the security unit’s power supply.

SELF-RECOVERY MODE
Resetting the “Fire” mode and switching back to the Standby mode (disengaging the relay) takes place in the following situations:

  • The QR-NA12V receievs a signal to turn off the alarm from the same smoke alarm that sent the alarm that activated the QR-NA 12V.
  • After 16 seconds withourt receiving the alarm indication
  • By pressing the TEST button (fig. 1, pos. 4) for more than 2 seconds

PROCEDURE FOR CREATING OR JOINING THE NETWORK:

METHOD 1; Used when creating a new network

  1. The Coordinator button is pressed continuously, for more than 4 seconds, until the LED indicator lights up continuously
  2. All fire detectors that will be part of the network are removed from their bases. On each of them, i:iress the TEST button briefly once. In case of successful execution of this step, the LED indicators of the Coordinator and the connected fire detectors will flash in sync
  3. To terminate the joining mode, it is necessary to briefly press the button of the QR-NA 12V.

METHOD 2; Used when a network already exists

  1. Press the test button shortly 5 times on the QR-NA 12V. The QR-NA 12V enters the network connection mode for a period of 120 seconds. During this time the LED indicator blinks 1 long and 1 short blik every 2-3 seconds.
  2. Remove one of the connected smoke alarms from the bottom plate and shortly press the test button. In doing so, the QR-NA 12V accepts the existing network code and returns to Standby mode and blinks the red LED to confirm this.
  3. Turn the smoke alarm back on the bottom plate and test the operation.
    Note : If it is necessary to forcefully exit the joining mode, briefly press the button of the QR-NA-12V coordinator.

TESTING THE OPERATION OF THE CIRCUIT FROM THE CONTROL PANEL

  1. Press the test button shortly 7 times. The QR-NA 12V goes into alarm mode for a period of 120 seconds
  2. Alarm mode is reset by pressing and holding the button for 2 seconds

DISCONNECTING THE QR-NA12V FROM THE NETWORK:

  1. Press the test button 10 times on the QR-NA 12V while connected to the network.
  2. The power to the QR-NA 12V is turned off. After 3-4 seconds the power is restored
  3. Press and hold the time coordinator button for more than 4 seconds until the LED indicator lights continuously (mode for creating a network).
  4. The coordinator button is pressed briefly once to finalize the procedure.

SIGNAL AMPLIFICATION

Installing the QR-NA12V in a switchboard located in a metal box creates a i:irerequisite for signal interference between the QR-NA12V and the smoke alarms. In this case, it is recommended to strengthen the
signal by connecting an external antenna. The antenna needs to be connected to the QR-NA 12V via an RP SMA Male to RP SMA. Before using the external antenna, it is necessary to disconnect the internal antenna. To do this, you need to drill a hole on the PCB at the DP1 point with a drill with a diameter of 1.0-1.5 mm, as shown in the photo.

ANTENNA SPECIFICATIONS:

  • Impedance: 50 OHM
  • Frequency Range: 868MHZ
  • Gain: 3 – 6dbi
  • SWR: 1.5
  • Connector: SMA male
  • ATTENTION! The manufacture is not responsible for disconnection or product performance degradation due to RF interference.

LED modes:

FITO-QR-NA12V-Wireless-Inkable-Smoke-Alarm-Coordinator-
fig-3

PRODUCT WARRANTY

If installed, used and maintained properly, the manufacturer guarantees this product, against material and/or manufacturing faults for a period of 5 years from the original date of purchase by the consumer. Exceptions include damage arising from accidents or misuse. If the product becomes defective within the stated period, then it will be repaired or replaced free of charge. Please do not attempt to repair the product yourself or tinker with it, which will invalidate the warranty.

INSTRUCTIONS FOR REMOVAL
Do not dispose of the QR-NA 12V in the bin, but rather hand it into a local collection point for small, domestic waste.

Fite Products B.V.
De Langkamp 12a
3961 MS Wijk bij Duurstede
The Netherlands
www.fito.eu