DATA NAB MBus-WTH-LCD-ETH Wall Temp Humidity Sensor Owner’s Manual
- June 24, 2024
- DATA NAB
Table of Contents
- DATA NAB MBus-WTH-LCD-ETH Wall Temp Humidity Sensor
- Product Usage Instructions
- Features
- Relative Humidity
- Temperature
- General
- Enclosure views and Dimensions
- Inside view & details
- Wiring Diagram
- Modbus Register List
- FAQ
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DATA NAB MBus-WTH-LCD-ETH Wall Temp Humidity Sensor
Product Specifications:
- Model : MBus_WTH_LCD_ETH & MBus_WTH_LCD_ETH_EXT
- Application : Temperature and Humidity Monitoring
- Output Signals: 4-20mA, 0-5V, 0-10V
- Communication Ports:
- MBus_WTH_LCD_ETH: RS485 Modbus-RTU, Ethernet Modbus TCP
- MBus_WTH_LCD_ETH_EXT: RS485 Modbus-RTU
- Power Supply:
- If not using analog output transducers: 12-24VAC/DC +/- 10%
- If using analog output transducers: 15-24VAC/DC +/- 10%
Product Usage Instructions
Configuration:
The sensor can be configured using the buttons and LCD display.
Communication:
For MBus_WTH_LCD_ETH:
- RS485 communications port for Modbus-RTU at 19.2/9600 Baud
- Ethernet Port for Modbus TCP communication over IP
Modbus Register List:
Default RS485 Comm Parameters:
- Baud Rate: 115200, Data Bits: 8, Parity: None, Stop Bit: 1
The default Modbus-ID for Modbus-RTU over RS485 communication is set to 1. The default IP Address for Modbus-TCP over IP communication is192.168.0.3. Use Function Code 3 (Read Holding Registers) to read values and Function Code 6 (Write Single Register) to write values.
Analog Output:
Analog output jumper settings:
- 1=0-10V, 2=0-5V, 3=4-20mA (Read Only)
Room Temperature and Humidity Readings
Register Addresses:
- Room Temp Reading in DegF x10: Register 100
- Room Temp Reading in DegC x10: Register 101
- Humidity Reading in %RH x10: Register 304
The MBus_WTH_LCD_ETH and MBus_WTH_LCD_ETH_EXT Modbus-enabled temperature and humidity sensors are designed for environment monitoring in industrial, commercial, and residential temperature & humidity applications.
Features
- The sensor can be configured using buttons & LCD Display
- High-performance digital sensors and circuits to ensure accurate measurement and temperature compensation.
- Good long-term stability and reliability
- Fast response
- Multiple output signals selectable: 4-20mA, 0-5V or 0-10V
- RS845 communications port for Modbus-RTU, 19.2/9600 Baud
- Ethernet Port for Modbus TCP communication over IP
Relative Humidity
- Sensor : capacitance polymer
- Operating Temperature : 0~50°C
- Operating Humidity Range : 0~98% RH (Non condensing)
- Output : 4-20mA, 0-5V or 0-10V, RS485 Modbus-RTU
- Accuracy : 5% RH (25°C, 20~80% RH)
- Hysteresis : < ±1% RH
- Response time : < 10s (25°C, in slow air)
- Drift : < ±0.5% RH / year
Temperature
- Sensor : Internal 10K Thermistor
- Operating Temperature Range: -30~50°C (-22~122°F)
- Output : 4-20mA, 0-5V or 0-10V, RS 485
- Accuracy : < ±0.5°C @ 25°C
General
- Power Supply:
- If NOT using 0-10V or 4-20mA output transducers: 12-24VAC/DC +/- 10%
- If using 0-10V or 4-20mA output transducers: 15-24VAC/DC +/-10%
- Power Consumption:
- 12VDC Power supply: assume 2 watts per sensor
- 24VAC Power supply : assume 1VA per sensor
- Current Output Load: < 500Ω
- Display: LCD screen for wall / outdoor mount and duct mount
- Display Resolution: 0.1°C, 0.1% RH
- Operating Temperature : -30~50°C, 0~98% RH (Non condensing) The humidity sensor only accurate from 0~50°C.
- Storage Temperature: -30~60°C
- Plastic Housing: Flammability rating UL 94V0 file E194560
- Protection: IP65
Enclosure views and Dimensions
Housing Dimensions (in mm) for both models. Probe Dimensions (in mm) for MBus_WTH_LCD_ETH
Probe Dimensions for MBus_WTH_LCD_ETH_EXT (mm)
Probe Dimensions for MBus_WTH_LCD_ETH_EXT (mm)
Inside view & details
Wiring Diagram
Modbus Register List
- Default RS485 Comm Parameters: 115200 baud, 8 data bits, no parity, 1 stop bit. (configurable under “misc” LCD menu)
- Default Modbus-ID for Modbus-RTU over RS485 communication is: 1. (configurable under “misc” LCD menu)
- Default IP Address for Modbus-TCP over IP communication is: 192.168.0.3 (configurable under “misc” LCD menu)
- Use Function Code 3 (Read Holding Registers) to read values and Function Code 6 (Write Single Register) to write values.
For more detailed modbus register information, please email support@datanab.com
FAQ
Q: How can I change the Modbus-ID for Modbus-RTU communication?
A: You can change the Modbus-ID under the LCD Miscellaneous menu.
Q: What is the default IP mode for Modbus-TCP communication?
A: The default IP mode is Static. You can change it to DHCP under the
miscellaneous LCD menu.