NAPOLEON Vector Series Dynamic Heat Control Instruction Manual
- June 22, 2024
- Napoleon
Table of Contents
- Vector Series Dynamic Heat Control
- Product Information
- Specifications
- Safety Information
- Product Usage Instructions
- Installation
- Optional Dynamic Heat ControlTM System
- Heat ControlTM
- Safety Measures
- Q: What should I do in case of a fire risk hazard or delayed
- Q: How do I handle chemicals exposure concerns related to the
Vector Series Dynamic Heat Control
“`html
Product Information
Specifications
Natural Gas Models: TLV50N / TLV6A2DND/PTRLOVD74UNCT/
TCLOVD5E0NH2ER/ ETL(VT6R2AND2E /GTOLTVH7I4CNL2T STD FONT)
Propane Gas Models: TLV50P / TLV62P / TLV74P / TLV50P2 / TLV62P2
/ TLV74P2
Safety Information
! WARNING
FIRE OR EXPLOSION HAZARD Failure to follow
safety warnings exactly could result in serious injury, death, or
property damage.
-
Do not store or use gasoline or other flammable vapours and
liquids in the vicinity of this or any other appliance. -
Installation and service must be performed by a qualified
installer, service agency, or the supplier.
Product Usage Instructions
Installation
This appliance may be installed in an aftermarket, permanently
located, manufactured home (USA only) or mobile home, where not
prohibited by local codes.
This appliance is only for use with the type of gas indicated on
the rating plate. Do not attempt to use other gases unless a
certified kit is used.
Installer: Leave the manual with the appliance. Consumer: Retain
the manual for future reference.
Optional Dynamic Heat ControlTM System
This appliance is suitable for the optional Dynamic Heat
ControlTM / Ducted Heat ManagementTM System. Refer to the
installation manual for more details.
Heat ControlTM
For indoor use only, certified to Canadian and American national
standards. Ensure compliance with relevant standards and
regulations for safe operation.
Safety Measures
Ensure that hot glass is not touched until cooled. Keep children
away from the glass to prevent burns. Follow all safety warnings
provided in the manual.
FAQ
Q: What should I do in case of a fire risk hazard or delayed
ignition?
A: High supply pressure can damage the
valve/controls. Disconnect the main gas valve/control from the
supply piping during system pressure testing exceeding 1/2 psi (3.5
kPa). Isolate the appliance with its shut off valve during any
pressure testing of the supply piping.
Q: How do I handle chemicals exposure concerns related to the
product?
A: This product may expose you to chemicals
including lead and lead compounds, which are known to the State of
California to cause cancer, and carbon monoxide, which can cause
birth defects or reproductive harm. Refer to www.P65Warnings.ca.gov
for more information.
“`
NATURAL GAS MODELS: TLV50N / TLV6A2DND/PTRLOVD74UNCT/ TCLOVD5E0NH2ER/ ETL(VT6R2AND2E /GTOLTVH7I4CNL2T STD FONT) PROPANE GAS MODELS: TLV50P / TLV62P / TLV74P / TLV50P2 / TLV62P2 / TLV74P2
ENGLISH FRENCH PG. 81
INSATADLDLAMTAIONNUAMLATNITULAEL
SAFETY INFORMATION
! WARNING
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could
result in serious injury, death, or property damage.
(MUST useVtPeitrlcoedtf(uorTocLrVmtTM5N0PaNrm2icSeielleu/BsCrtorioaoetdekeds)) ADD ____ ILLUSTRATED
– Do not store or use gasoline or other flammable vapours and liquids in the
vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS: · Do not try to light any appliance. · Do not
touch any electrical switch; do not
use any phone in your building. · Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s instructions. · If you cannot
reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified installer, service
agency, or the supplier.
SAFEATDYD PBROADRUCRTIIEMRAGE
This appliance may be installed in an aftermarket, permanently located,
manufactured home (USA only) or mobile home, where not prohibited by local
codes.
This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
INSTALLER: Leave this manual with the appliance
CONSUMER: Retain this manual for future reference
THIS APPLIANCE IS SUITABLE FOR THE OPTIONAL DYNAMIC HEAT CONTROLTM / DUCTED
HEAT MANAGEMENTTM SYSTEM (See Dynamic Heat ControlTM / Ducted Heat
ManagementTM
installation manual)
HEAT CONTROLTM
FOR INDOPOATRENTUPSENEDINOG NLY
FOR INDOOR USE ONLY CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS:
CECRSTAIF2I.E2D2
ATNODTHAENSCIAZN2A1.D5I0AFNOARNVDEANMTEEDRIDCEACNONRAATTIIOVNEAGLASSTAAPNPDLAIRANDCS:ES
CSA 2.22 AND ANSIIZF2I1N.5S0 TFOARLLVAETNITOEND D+ECOOPREARTAIVTEIGOANS,
AAPDPDLIASNECREISAL
CSA / INTERTEK
LOGO
NUMBER LABEL HERE
IF SPELPAACRAETSE EMRAINAULANLSU,MADBDER”PLLAACBEEL BARCODE LAOBNELTHONE TOHWE
NOWERN’ESR’MS AMNAUNAUALL”
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030 Phone 1 866-820-8686 · www.napoleon.com · hearth@napoleon.com
$10.00
W415-4121 / D-0 / 05.22.24
EN safety information
! WARNING
· This appliance is hot when operated and can cause severe burns if contacted.
· Any changes or alterations to this appliance or its controls can be
dangerous and is prohibited.
! DANGER HOT GLASS WILL CAUSE
· Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fire or injury.
BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
· Ensure the glass door is opened or removed when lighting the pilot for the first time and when the gas supply has run out.
NEVER ALLOW CHILDREN TO TOUCH GLASS.
· Risk of fire or asphyxiation, do not operate
A barrier designed to reduce the risk of burns from the hot
·
appliance with fixed glass removed and never obstruct the front opening of the appliance. Do not connect 110 volts to the control valve,
viewing glass is provided with this appliance and must be installed for the protection of children and other at-risk
with the exception of models; GSST8 and
individuals.
GT8.
· Risk of burns. The appliance should be turned off and cooled before servicing.
· Do not install damaged, incomplete or substitute components.
· Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during installation. Sheet metal edges may be sharp.
· Do not burn wood or other materials in this appliance.
· Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing and operating the appliance.
· High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test pressures above 1/2 psig. Close the manual shut-off valve before pressure testing gas line at test pressures equal to or less than 1/2 psig (35mb).
· The appliance must not be operated at temperatures below freezing (32°F / 0°C). Allow the appliance to warm to above freezing prior to operation, with the exception of models; GSS36, GSS42, RSS36, and RSS42; these appliances are suitable for 0°F / -18°C.
· Children and adults should be alerted to hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
· Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
· Clothing or other flammable material should not be placed on or near the appliance.
· Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
· Furniture or other objects must be kept a minimum of 4 feet (1.22m) away from the front of the appliance.
· Ensure you have incorporated adequate safety measures to protect infants/toddlers from touching hot surfaces.
· Even after the appliance is off, it will remain hot for an extended period of time.
· Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the floor.
· Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the appliance.
· It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
· If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it serviced. Keep burner and control compartment clean.
· Under no circumstances should this appliance be modified.
· Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner flame patterns.
2
W415-4121 / D-0 / 05.22.24
safety information EN
! WARNING
· Do not use a blower insert, heat exchanger insert or other accessory not
approved for use with this appliance.
· This appliance must not be connected to a chimney flue pipe serving a
separate solid fuel burning appliance.
· Do not use this appliance if any part has been under water. Immediately call
a qualified service technician to inspect the appliance and to replace any
part of the control system and any gas control which has been under water.
· Do not operate the appliance with the glass door (if equipped) removed,
cracked or broken. Replacement of the glass should be done by a licensed or
qualified service person.
· Do not strike or slam shut the appliance glass door, if equipped. · Only
doors / optional fronts certified with the appliance are to be installed on
the appliance. · Keep the packaging material out of reach of children and
dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from
children and infants. · Carbon or soot should not occur in a vent free
appliance as it can distribute into the living area of your
home. If you notice any signs of carbon or soot, immediately turn off your
appliance and arrange to have it serviced by a qualified technician before
operating it again. · If equipped, the screen must be in place (closed) when
the appliance is in operation. · When equipped with pressure relief doors,
they must be kept closed while the appliance is operating to prevent exhaust
fumes containing carbon monoxide, from entering into the home. Temperatures of
the exhaust escaping through these openings can also cause the surrounding
combustible materials to overheat and catch fire. · Carbon monoxide poisoning
may lead to death; early signs of carbon monoxide poisoning resemble the flu,
with headache, dizziness and/or nausea. If you have these signs, the appliance
may not be working properly. Get fresh air at once! Have appliance serviced.
Some people; pregnant women, persons with heart or lung disease, anemia, those
under the influence of alcohol, those at high altitudes are more affected by
carbon monoxide than others. Failure to keep the primary air opening(s) of the
burner(s) clean may result in sooting and property damage. · As with any
combustion appliance, we recommend having your appliance regularly inspected
and serviced as well as having a Carbon Monoxide Detector installed in the
same area to defend you and your family against Carbon Monoxide (not
applicable for outdoor appliances). · Ensure clearances to combustibles are
maintained when building a mantel or shelves above the appliance. Elevated
temperatures on the wall or in the air above the appliance can cause melting,
discolouration or damage to decorations, a TV or other electronic components.
· For appliances equipped with a safety barrier; if the barrier becomes
damaged, the barrier shall be replaced with the manufacturer’s barrier for
this appliance. · Installation and repair should be done by a qualified
service person. It is imperative that control compartments, burners and
circulating air passageways of the appliance be kept clean. · For outdoor
products only: this appliance must not be installed indoors or within any
structure that prevents or inhibits the exhaust gases from dissipating in the
outside atmosphere. · If applicable, the millivolt version of this appliance
uses and requires a fast acting thermocouple. Replace only with a fast acting
thermocouple supplied by Wolf Steel Ltd.
! WARNING:This product can expose you to chemicals including lead and lead
compounds,
Add California Prop 65 warning which are known to the State of California to
cause cancer, and chemicals including carbon
monoxide, which are known to the State of California to cause birth defects or
other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
! WARNING !
FIRE RISK HAZARD / DELAYED IGNITION
High supply pressure will damage the valve / controls.
Disconnect the appliance main gas valve/control from the supply piping when
pressure testing that system at pressures in excess of 1/2 psi (3.5 kPa).
Isolate the appliance with it’s shut off valve during any pressure testing of
the supply piping at
pressures equal to or less than 1/2 psi (3.5 kPa).
W415-4121 / D-0 / 05.22.24
3
EN table of contents
1.0 general information
5 7.0 gas installation
45
1.1 rates and efficiencies 1.2 installation checklist 1.3 installation overview 1.4 rating plate/lighting instruction
6 7 8
8.0 operation
8.1 pilot-on-demand
9.0 nailing tab installation
46
47
48
location 1.5 mobile home installation
10 11
10.0 finish framing – after
1.6 hardware list
11
appliance installation
49
1.7 lifting handles installation/removal
2.0 dimensions
11
12
10.1 framing with non-combustibles
11.0 finishing
49
48
2.1 single-sided
12
2.2 see-through
13
3.0 minimum venting requirements 14
11.1 fastener placement restriction
49
11.2 finishing with non-combustibles
53
11.3 installing non-combustible board
55
3.1 typical venting installation
16
11.4 minimum combustible mantel
3.2 minimum air terminal location
clearances
56
clearances
18
11.5 TV mounting restrictions
3.3 horizontal termination (natural gas) 19
(without DHCTM)
57
3.4 vertical termination (natural gas)
22
11.6 safety barrier installation / removal 58
3.5 horizontal termination (propane)
23
11.7 firebox glass door installation /
3.6 vertical termination (propane)
26
removal
58
4.0 rough framing – before
11.8 media installation / removal
60
11.9 adjusting the finishing trim
61
appliance installation
27 12.0 adjustments
62
4.1 minimum framing dimensions
28
12.1 restricting vertical vents
62
4.1.1 minimum clearance to combustible
12.2 venturi adjustment
62
enclosures 4.2 front frame installation
5.0 venting installation
29
12.3 pilot burner adjustment
63
32
12.4 flame characteristics
63
32 13.0 maintenance
64
5.1 firestop spacer assembly
33
13.1 annual maintenance
65
5.2 horizontal installation
34
13.2 control access
65
5.3 vertical installation
35
13.3 burner removal
66
5.4 using flexible vent components
36
13.4 valve removal
66
5.4.1 horizontal air terminal installation 36
5.4.2 vertical air terminal installation
37
5.4.3 appliance vent connection
37
13.5 control module removal 13.6 LED replacement 13.7 glass / door replacement 13.8 care of glass
67 68 69 69
5.5 restricting vertical vents
38
13.9 care of plated parts
69
5.5.1 TLV50 / TLV50_2
38 14.0 replacement parts
70
5.5.2 TLV62 / TLV62_2 / TLV74 /
TLV74_2
38
14.1 overview 14.2 burner components
71 72
5.6 vent shield installation
6.0 electrical information
6.1 hard wiring connection
39
40
40
15.0 16.0
troubleshooting warranty
74 77
6.2 receptacle wiring diagram
40
6.3 in the event of a power failure
40
6.4 battery holder/switch installation
41
6.5 initializing the battery holder/switch
for the first time
41
6.6 access panel
42
6.7 wiring
42
6.8 eFIRE application controller
42
6.8.1 TLV50 / TLV50_2 wiring diagram 43
6.8.2 TLV62 / TLV62_2 / TLV74 /
TLV74_2 wiring diagram
44
note:
The information throughout this manual is believed to be correct at the time
of printing. Wolf Steel Ltd. reserves the right to change or modify any
information within this manual at any time without notice. Changes, other than
editorial are denoted by a vertical line in the margin.
4
W415-4121 / D-0 / 05.22.24
general information EN
Installer: please fill out appliance checklist in the owner’s manual.
1.0 general information
When the appliance is installed at elevations above 4,500ft (1372m), and in
the absence of specific recommendations from the local authority having
jurisdiction, the certified high altitude input rating shall be reduced at the
rate of 4% for each additional 1,000ft (305m). Expansion / contraction noises
during heating up and cooling down cycles are normal and are to be expected.
Change in flame appearance from “HI” to “LO” is more evident in natural gas
than in propane.
This appliance is approved for bathroom, bedroom and bed-sitting room
installations and is certified for mobile home installation.
This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
There is a switch that controls the function of the appliance. The battery
holder/switch must be placed in the middle position. If the switch is not
placed in the middle position, the appliance will not work.
note: A barrier designed to reduce the risk of burns is provided with the
appliance and must be installed. Never operate the appliance without the
barrier installed.
The protective wrap on plated parts is best removed when the assembly is at
room temperature but this can be improved if the assembly is warmed, using a
hair dryer or similar heat source. The protective wrap must be removed before
operating the appliance.
This appliance is a decorative product. It is not a source of heat and not
intended to burn solid fuel.
This appliance is equipped with a remote control and a wall switch, which
requires batteries to be installed. The remote takes 3 “AAA” batteries and the
wall switch takes 4 “AA” batteries.
Batteries must be disposed of according to the local laws and regulations.
Some batteries may be recycled, and may be accepted for disposal at your local
recycling center. Check with your municipality for recycling instructions.
This appliance is suitable for use with Napoleon’s optional Ducted Heat
ManagementTM & Ducted Heat ManagementTM Plus systems. THIS MANUAL DOES NOT
include detailed information relating to these optional systems. Framing and
finishing are NOT the same. For further details, refer to the Ducted Heat
ManagementTM installation manual provided with the kit before starting
installation.
W415-4121 / D-0 / 05.22.24
5
EN general information
1.1 rates and efficiencies
Appliance Type Fuel Type Altitude (FT) Max. Input (BTU/HR) Min. Input (BTU/HR)
TLV50N Natural Gas
36,000 23,000
TLV50 / TLV50_2 0-4,500
TLV50P Propane
31,500 25,000
Appliance Type Fuel Type Altitude (FT) Max. Input (BTU/HR) Min. Input (BTU/HR)
TLV62N Natural Gas
44,000 29,000
TLV62 / TLV62_2 0-4,500
TLV62P Propane
38,000 31,000
Appliance Type Fuel Type Altitude (FT) Max. Input (BTU/HR) Min. Input (BTU/HR)
TLV74N Natural Gas
48,000 31,000
TLV74 / TLV74_2 0-4,500
TLV74P Propane
41,500 33,000
TLV50 / TLV62 / TLV74 / TLV50_2 / TLV62_2 / TLV74_2
Natural Gas
Min. Inlet Gas Supply Pressure
4.5″ w.c. (11mb)
Max. Inlet Gas Supply Pressure
7″* w.c. (17mb)
Manifold Pressure (Under Flow Conditions)
3.5″ w.c. (9mb)
*Maximum inlet pressure not to exceed 13″ w.c. (32mb).
Propane 11″ w.c. (27mb)
13″ w.c. (32mb).
10″ w.c. (25mb)
6
W415-4121 / D-0 / 05.22.24
1.2 installation checklist
general information EN
GAS FIREPLACE INSTALLATION CHECKLIST
Customer: Address: Model: Serial #:
Date Installed: Installer: Dealer: Dealer Phone #:
This checklist is a reference tool only. It is not intended as a substute for the installaon instrucons.
Fireplace Installaon Is the fireplace level and secured? Are the factory
supplied non-combusble materials installed? Is the exterior wall insulated and
dry-walled? Are the clearances to combusbles maintained? Are the logs/media
installed as instructed? Are the accessories installed as instructed? Is the
glass door properly sealed and unobstructed? Is the safety barrier installed
and secure? Are all required accessories installed (i.e. door trims)?
Venng Installaon Is the venng configuraon within the parameters? Has the venng
been sealed with the appropriate sealant? Is the venng supported and secured?
Are all clearances to combusbles maintained? Are the appropriate firestops and
shields properly installed? Is the terminal, level, secured and sealed?
Gas and Electrical Was the fireplace converted to propane? If yes, does the
fireplace have a power vent? Was the appropriate supply pressure verified?
Were all gas connecons leak tested? Is the 110 VAC supply connecon to the
fireplace compliant? Are all electrical wires protected from damage? Finishing
Non-combusble materials used as per instrucons? Enclosure instrucons forwarded
to builder/finisher? Minimum enclosure dimensions compliant? Combusble Mantel
Clearances compliant?
Commissioning Was the fireplace test fired and all operaon verified? Safety
and lighng instrucons reviewed with the Customer? Operang Instrucon Manual le
with the Customer?
YES
IF NOT, PLEASE EXPLAIN WHY?
Wolf Steel Ltd. recommends photographs of the various stages of construcon be filed along with a copy of this completed form.
W415-4121 / D-0 / 05.22.24
7
EN general information
1.3 installation overview
12
11 8
9 54 7 3
6
Safety Barrier
Recommended installation steps: 1. Determine venting requirements before
deciding the final location of the appliance. 2. Plan out appliance enclosure,
framing, fronts, accessories, etc. 3. Install rough framing (refer to “rough
framing” section). 4. Place the appliance in its final position. 5. Install
nailing tabs (refer to “nailing tab installation” section). 6. Install
appliance venting (refer to “venting installation” section). 7. Install vent
shield (refer to “vent shield installation” section). 8. Install all
electrical wirings (refer to “electrical information” section). 9. Install gas
lines (refer to “gas installation” section). 10. Test appliance. 11. Complete
framing (refer to “finish framing” section). 12. Finishing (refer to
“finishing” section). 13. Complete installation checklist in the owner’s
manual and apply serial number to owner’s manual.
note:
For Dynamic Heat ControlTM/Ducted Heat ManagementTM installation steps, refer
to the leaflet provided with the Dynamic Heat ControlTM/Ducted Heat
ManagementTM kit. Start Dynamic Heat ControlTM/Ducted Heat ManagementTM
installation before step 3 (place the appliance in its final position)
8
W415-4121 / D-0 / 05.22.24
general information EN ! WARNING
· Always light the pilot whether for the first time or if the gas supply has
run out, with the glass door opened or removed.
· Provide adequate clearance for servicing and operating the appliance. ·
Provide adequate ventilation. · Never obstruct the front opening of the
appliance. · Objects placed in front of the appliance must be kept a minimum
of 48″ (121.9cm) from the front face of the
appliance. · Surfaces around and especially above the appliance can become
hot. Avoid contact when appliance is
operating. · Fire risk. Explosion hazard. · High pressure will damage valve.
Disconnect gas supply piping before pressure testing gas line at test
pressures above 1/2 PSIG. Close the manual shut-off valve before pressure
testing gas line at test pressures equal to or less than 1/2 PSIG (35mb). ·
Use only Wolf Steel approved optional accessories and replacement parts with
this appliance using non-listed accessories (blowers, doors, louvres, trims,
gas components, venting components, etc.) could result in a safety hazard and
will void the warranty and certification. · The appliance must not be operated
at temperatures below freezing (32ºF / 0ºC). Allow the appliance to warm, to
above freezing prior to operation. · This appliance has been designed and
certified for indoor use only.
THIS GAS APPLIANCE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region
and it is important to know the specifics that apply to your area, for example
in the state of Massachusetts: · This product must be installed by a licensed
plumber or gas fitter when installed within the commonwealth of
Massachusetts. · The appliance damper must be removed or welded in the open
position prior to installation of an appliance insert or gas
log. · The appliance off valve must be a “T” handle gas cock. · The flexible
connector must not be longer than 36 inches (0.9m). · A carbon monoxide
detector is required in all rooms containing gas fired appliances. · The
appliance is not approved for installation in a bedroom or bathroom unless the
unit is a direct vent sealed
combustion product.
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1
We suggest that our gas
in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or ANSI Z223.1 and NFPA 54 in the United States.
hearth products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace
The appliance and its individual shutoff valve must be disconnected
Institute® (NFI) as NFI Gas
from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (35 mb).
Specialists
www.nficertified.org
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (35 mb). When installed
with a blower or fan, the junction box must be electrically connected and grounded in accordance with local codes. In the
absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI / NFPA 70 National
Electric Code in the United States. In the case where the blower is equipped with a power cord, it must be connected into a
properly grounded receptacle. The grounding prong must not be removed from the cord plug.
The following does not apply to inserts; as long as the required clearance to combustibles is maintained, the most desirable and beneficial location for an appliance is in the center of a building, thereby allowing the most efficient use of the heat created. The location of windows, doors and, the traffic flow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a floor or roof joist. If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.
W415-4121 / D-0 / 05.22.24
9
EN general information
1.4 rating plate/lighting instruction location
Both the rating plate and lighting instructions are attached to a chain
located on the left side of the control area near the valve (access side).
Remove the safety barrier and the control cover to gain access to the control
area, refer to the “safety barrier installation / removal” section for
detailed removal instructions.
To replace, slide the instructions back into the control area and reinstall
the safety barrier assembly.
Rating plate location
Certified to Canadian and American National Standards: CSA 2.22-XXXX / ANSI Z21.50-XXXX for Vented Decorative Gas Appliances
Certifié selon les normes Nationales Canadiennes et Américaines: CSA 2.22-XXXX / ANSI Z21.50-XXXX pour les Appareils à gaz décoratif à évacuation
Direct vent, vented gas fireplaces. Approved for bedroom, bathroom and bed- sitting room installation. Suitable for mobile home installation, if installed in accordance with the current
standard CAN / CSA Z240MH Series gas equipped mobile homes in Canada, or, in the United States, the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280. When this US Standard is not applicable, use the Standard for Fire Safety Criteria for Manufactured Home Installations, Sites and Communities, ANSI / NFPA 501A. This appliance must be installed in accordance with local codes, if any; if none, follow the current ANSI Z223.1 or CSA B149. For use with barrier WXXX-XXXX. Follow installation instructions. Foyer à gaz ventilé. Homologué pour installation dans une chambre à coucher, une salle de bain et un studio. Approprié pour installation dans une maison mobile si son installation
conforme aux exigences de la norme CAN / CSA Z240MH Séries de maisons mobile équipées au gaz en vigueur au Canada, ou, aux États-Unis selon la norme 24 CFR, Part 3280,
Manufactured Home Construction and Safety Standard. Dans le cas ou cette norme d’États-Unis n’est pas pertinentes, utiliser la norme NFPA 501A, Fire Safety Criteria for Manufactured
SAMPLE Home Installations, Sites and Communities. Installer l’appareil selon
les codes ou règlements locaux ou, en l’absence de tels règlements, selon les
codes d’installation ANSI Z223.1 ou
CSA B149 en vigueur. Utiliser uniquement avec l’écran WXXX-XXXX. Suivre les
instructions d’installation.
REFERENCE# 161746
9700539 (WSL)
4001658 (NAC)
4001657 (NGZ)
4001659 (WUSA)
VENTED DECORATIVE GAS APPLIANCE: NOT A SOURCE OF
XXXX
MODEL / MODÈLE
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
Altitude
0-XXXXft (0-XXXXm)
Élévation
Input Reduced Input P4
XX,XXX XX,XXX XX.X%
XX,XXX XX,XXX XX.X%
Alimentation Alimentation Réduite
P4
Manifold Pressure: 3.5″ w.c. (NG)
Manifold Pressure: 10″ w.c. (P)
Minimum Supply Pressure: 4.5″ w.c. (NG)
Minimum Supply Pressure: 11″ w.c. (P)
Maximum Supply Pressure: 7″* w.c. (NG)
Maximum Supply Pressure: 13″* w.c. (P)
Pression au Collecteur: 3,5″ d’une colonne d’eau (GN)
Pression au Collecteur: 10″ d’une colonne d’eau (P)
Pression d’Alimentation Min.: 4,5″ d’une colonne d’eau (GN)
Pression d’Alimentation Min.: 11″ d’une colonne d’eau (P)
Pression d’Alimentation Max.: 7″ * d’une colonne d’eau (GN) Pression d’Alimentation Max.: 13″ d’une colonne d’eau (P)
** Maximum inlet pressure not to exceed 13″.
** Pression d’alimentation maximale ne devait pas dépasser 13″.
Minimum clearance to combustible materials:
Dégagements minimaux des matériaux combustibles:
Top, sides & back: per standoff spacers for framing and finishing Dessus, côtés et arrière: selon les espaceurs de dégagements
materials. For non-combustible framing and finishing materials,
pour les matériaux d’ossature selon le manuel du propriétaire
see installation manual.
pour les matériaux de finition.
HEAT, NOT INTENDED FOR USE AS A HEATING
APPLIANCE, NOT FOR USE WITH SOLID FUEL.
APPAREIL À GAZ DÉCORATIF À ÉVACUATION: N’EST PAS
UNE SOURCE DE CHALEUR; N’EST PAS DESTINÉ À ÈTRE
UTILISÉ COMME UN APPAREIL DE CHAUFFAGE; NE
CONVIENT PAS AUX COMBUSTIBLES SOLIDES.
FOR USE WITH GLASS DOORS CERTIFIED WITH THIS APPLIANCE ONLY. POUR UTILISATION
UNIQUEMENT AVEC LES PORTES EN VERRE CERTIFIÉES AVEC L’APPAREIL.
For natural gas when equipped with No. XX drill size orifice. For propane when
equipped with No. XX drill size orifice.
Convient au gaz naturel quand l’appareil est muni d’un injecteur de diamètre
no. XX. Convient au propane quand l’appareil est muni d’un injecteur de
diamètre no. XX.
WARNING: Do not add any material to the appliance which will come in contact
with the
Top X”
Dessus X”
flames, other than that supplied by the manufacturer with the appliance.
Floor X”
Plancher X”
AVERTISSEMENT: N’ajoutez pas à cet appareil aucun matériau devant entretien
Sides X”
Côtés X”
contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant.
Back X” Vent top X” Vent sides & bottom X” Recessed depth X” Mantel X”
from appliance opening
Maximum horizontal extension: X”. See installation manual for
Arrière X” Dessus du conduit d’évent X” Côtés et dessous du conduit d’évent X”
Profondeur d’encastré une face X” Tablette X” de l’ouverture de l’appareil
L’extension horizontale maximale: X”. Référez au manuel d’installation
pour des
The appliance must be vented using the appropriate Napoleon vent kits. See
installation manual for venting specifications. Proper reinstallation and
resealing is necessary after servicing
the vent-air intake system.
L’appareil doit être ventilé à l’aide de l’ensemble d’évacuation propre à
Napoleon. Référez au manuel d’installation pour les spécifications
d’évacuation. Il est nécessaire de bien réinstaller et
resceller l’évacuation après avoir executer l’entretien du système de prise
d’air.
greater extensions, minimum vent
extensions plus grandes, les longueurs
lengths and maximum vent lengths. Electrical rating: 115V, 60HZ. Less than 12 amperes.
d’évacuation minimaux et maximum. Spécifications électriques: 115V, 60HZ. Moins de 12 ampère.
Serial Number / N° de Série:
XXXX
WOLF STEEL LTD. 24 Napoleon Road, Barrie, ON, L4M 0G8 Canada
W385-XXXX
This illustration is for reference only. Refer to the rating plate on the
appliance for accurate information.
note: The rating plate must remain with the appliance at all times. It must
not be removed.
10
W415-4121 / D-0 / 05.22.24
1.5 mobile home installation
general information EN
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate. This mobile/manufactured home listed appliance comes factory equipped with a means to secure the appliance. The shipping brackets that secure the appliance to the pallet can be used to secure the appliance to the floor for mobile home installation. For mobile home installations, the appliance must be secured. This appliance is certified to be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. Conversion Kits This appliance is field convertible between Natural Gas (NG) and Propane (P). To convert from one gas to another, consult your Authorized dealer/distributor.
1.6 hardware list
1
2
Description 1 Hex Head Sheet Metal Screw 2 Round Head Sheet Metal Screw 3 Hex Head Sheet Metal Bolt
3
Quantity 22 4 18
note: Only fasteners supplied with the appliance are illustrated.
1.7 lifting handles installation/removal
Remove 4 screws each side (8 total) then install the lifting handles to the
side of the appliance and secure using 4 screws each side (8 total). Once the
appliance is in place remove the four screws from each handle to the
appliance. Discard the lifting handles.
note:
The lifting handles MUST be removed prior to rough framing the appliance.
Safety barrier
W415-4121 / D-0 / 05.22.24
11
EN d2.i0mednimsioensions
2.1 single-sided
49
7 16
”
47
15 16
”
1256mm 1217mm
26
13 16
”
681mm
Finishing Flange
7
1 16
”
180mm
SAFETY BARRIER
A 52
9 16
”
1335mm
Finishing Flange
B 63
5 16
”
1608mm
C 65
5 16
”
1659mm
8.000 203
5.000 127
196″ 14mm
41″ 1041mm
3
1 8
”
80mm
8
1 16
”
205mm
16
3 16
”
412mm
17
11 16
”
449mm
19
7 8
”
505mm
8
1 16
”
205mm
TLV50
TLV62
TLV74
A (Finishing Flange)
52 9/16″ (1335mm)
64 9/16″ (1639mm)
76 9/16″ (1944mm)
B
63 5/16″
75 5/16″
87 5/16″
(1608mm)
(1912mm)
(2217mm)
C
65 5/16″
77 5/16″
89 5/16″
(1659mm)
(1963mm)
(2268mm)
*Finishing flange depth (the finishing flange defines the perimeter of the fireplace opening. Framing or finishing materials must NEVER encroach inside the finishing flange).
12
W415-4121 / D-0 / 05.22.24
2.2 see-through
dimensions EN
49
7 16
”
1256mm
47
15 16
”
1217mm
26
13 16
”
681mm
Finishing Flange
7
1 16
”
180mm
SAFETY BARRIER
A B C
8.000 203
5.000 127
196″ 14mm
41″ 1041mm
3
1 8
”
80mm
8
1 16
”
205mm
16
3 16
”
412mm
8
1 16
”
205mm
TLV50_2
TLV62_2
TLV74_2
A (Finishing Flange)
52 9/16″ (1335mm)
64 9/16″ (1639mm)
76 9/16″ (1944mm)
B
63 5/16″
75 5/16″
87 5/16″
(1608mm)
(1912mm)
(2217mm)
C
65 5/16″
77 5/16″
89 5/16″
(1659mm)
(1963mm)
(2268mm)
*Finishing flange depth (the finishing flange defines the perimeter of the fireplace opening. Framing or finishing materials must NEVER encroach inside the finishing flange).
W415-4121 / D-0 / 05.22.24
13
EN m3.0inimuinmimvuemntivnegntrienqgurireeqmuiernemtsents ! WARNING
· Risk of fire. Maintain specified air space clearances to vent pipe and
appliance. · The vent system must be supported every 3′(0.9m) for both
vertical and horizontal runs. Use support ring assembly
W010-0067 or equivalent non-combustible strapping to maintain the minimum
clearance to combustibles for both vertical and horizontal runs. Spacers are
attached to the inner pipe at predetermined intervals to maintain an even air
gap to the outer pipe. This gap is required for safe operation. A spacer is
required at the start, middle, and end of each elbow to ensure this gap is
maintained. These spaces must not be removed.
This appliance uses a 5″ (127mm) exhaust / 8″ (203.2mm) air intake vent pipe
system. Refer to the section applicable to your installation. For safe and
proper operation of the appliance follow the venting instructions exactly.
Deviation from the minimum vertical vent length can create difficulty in
burner start-up and/or carboning. Under extreme vent configurations, allow
several minutes (5-15) for the flame to stabilize after ignition. Although not
a requirement, it is recommended for vent lengths that pass through unheated
spaces (attics, garages, crawl spaces) be insulated with the insulation
wrapped in a protective sleeve to minimize condensation.
Provide a means for visually checking the vent connection to the appliance
after the appliance is installed. Use a firestop, vent pipe shield or attic
insulation shield when penetrating interior walls, floor or ceiling.
The vent terminal may be painted with high temperature paint to match exterior
colours. Use an outdoor paint suitable for 400°F (200°C). Application and
performance of paint is the consumer’s responsibility. Spot testing is
recommended. Appliance should be off.
note: If for any reason the vent air intake system is disassembled; reinstall
per the instructions provided for the initial installation. This appliance
must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions, such as a chimney as part of the
vent system, is not permitted.
All vent measurements start at the base of the air collar of the appliance.
IMPORTANT: For ease of installation, the front frame can be removed. The front
frame must be reinstalled prior to installing the nailing tabs.
Horizontal vent sections: A minimum clearance of 3″ (76mm) on the top outside
of the enclosure and 2″ (51mm) on the sides and bottom outside of the
enclosure all around the vent pipe on all horizontal runs to combustibles is
required. Horizontal vent sections within enclosures require a minimum
clearance of 6″(152mm) at the top of the vent pipe. Vertical vent sections: A
minimum of 1″ (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliances enclosures.
Vertical vent sections within enclosures require a minimum clearance of 1″
(25mm) around the vent pipe.
14
W415-4121 / D-0 / 05.22.24
minimum venting requirements EN
Use only Wolf Steel, Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp
venting components. Minimum and maximum vent lengths, for both horizontal and
vertical installations, clearances from vent pipes to combustibles and air
terminal locations as set out in this manual apply to all vent systems and
must be adhered to. For Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct
Temp, follow the installation procedure provided with the venting components
or on the website for your venting supplier. A starter adaptor must be used
with the following vent systems and may be purchased through Wolf Steel or
from the corresponding supplier listed below:
Venting System Manufacturer
Supplier
Website
SureSeal Direct Vent Pro Pro-Form Direct Temp
Ventis
Metal-Fab Simpson DuraVent BDM Selkirk Olympia Chimney and Venting
Wolf Steel Wolf Steel BDM Selkirk Olympia Chimney and Venting
www.mtlfab.com www.duravent.com www.dalsinmfg.com www.selkirkcorp.com
www.olympiachimney.com
Connections made by means of an adaptor at the appliance, as well as the
connection at the vent terminal must be sealed. RTV sealant may be used on
both the inner exhaust and outer intake vent pipe joints of all other approved
vent systems, except for the exhaust vent pipe connection to the appliance
flue collar which must be sealed using the black high temperature sealant Mill
Pac.
For all vent systems is strongly recommend for all installations but required
when power venting the appliance, that the outer air intake joints are sealed
using either high temperature silicone (RTV) or a suitable aluminum tape that
covers each joint in the vent system entirely around its circumference. This
will ensure the best performance in every application and avoids performance
or condensation concerns that may occur in “tightly” constructed homes,
particularly those in cold climates.
When using Wolf Steel venting components, use only approved Wolf Steel rigid /
flexible components with the following termination kits: wall terminal kit
GD422R-2 or ST58U-1, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to
12/12 roof terminal kit GD411, flat roof terminal kit GD412 or periscope kit
GD401 (for wall penetration below grade). With flexible venting, in
conjunction with the various terminations, use either the 5 foot (1.5m) vent
kit GD420 or the 10 foot (3.1m) vent kit GD430.
For optimum flame appearance and appliance performance, keep the vent length
and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air
terminal at least once a year to verify that it is unobstructed and undamaged.
Rigid and flexible venting systems must not be combined. Different venting
manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the
appliance. The maximum allowable horizontal run is 20 feet (6.1m). The maximum
allowable vertical vent length is 40 feet (12.2m). The maximum number of vent
connections is two horizontally or three vertically (excluding the appliance
and the air terminal connections) when using flexible venting.
Horizontal runs may have a 0″ (0mm) rise per foot/meter however for optimum
performance it is recommended that all horizontal runs have a minimum 1/4″
(21mm) rise per foot/meter using flexible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and
elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap all around between the
inner liner and outer liner is required for safe operation.
W415-4121 / D-0 / 05.22.24
15
EN minimum venting requirements
3.1 typical venting installation
18″ (457mm) maximum
22″ (559mm) minimum
base of air collar
62 3/4″ (1594mm) minimum plus rise
B
minimum
base of air collar
A
maximum
C
minimum plus rise
SINGLE-SIDED
SEE-THROUGH
SEE-THROUGH
TLV50_2
TLV62_2
A
46 1/2″ (1181mm)
52 1/2″ (1334mm)
B
22″ (559mm)
40″ (1016mm)
C
54 1/2″ (1384mm)
72 1/2″ (1842mm)
TLV74_2
58 1/2″ (1486mm) 50″ (1270mm)
82 1/2″ (2096mm)
16
W415-4121 / D-0 / 05.22.24
minimum venting requirements EN
special vent installation (periscope termination)
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
final grading is completed, the bottom air slot is located a minimum 12″ (30.5cm) above grade. The maximum
allowable vent length is 10′ (3m).
46 1/2″ (1181mm)
maximum
30″ (762mm) min.
12″ (305mm) minimum to grade
30″ (762mm) min
12″ (305mm) minimum to grade
base of air collar
base of air collar
TLV50 / TLV50_2 only
*For TLV62 / TLV62_2 / TLV74 / TLV74_2 models use the 30″ x 18″ periscope provided.
SINGLE-SIDED OR SEE-THROUGH
16″ (406mm) minimum
note:
A 6′ (1.83m) minimum vertical rise is considered the minimum practical
dimension for the specific appliance enclosure and a minimal building
structure. However, a greater minimum vertical rise may be needed to suit the
specific application constraints or local codes and/ or regulatory
requirements.
40 ft (12m) maximum 6 ft (1.83m) minimum
base of air collar
W415-4121 / D-0 / 05.22.24
17
EN minimum venting requirements
3.2 minimum air terminal location clearances
Covered balcony applications *
QS
P
R
G
18
INSTALLATIONS
CANADA
U.S.A.
QMIN = 3 feet (0.9m)
R MAX = 2 x QACTUAL
RMAX 15 feet (4.6m)
note:
Wall terminals are for illustration purposes only. Size and shapes may vary.
Wall terminal measurements taken from the exhaust outlet, not the mounting
plate.
A
12″ (30.5cm)
12″ (30.5cm) Clearance above grade, veranda porch, deck or balcony.
B 12″ (30.5cm) 9″ (229mm) Clearance to windows or doors that open.
C 12″ (30.5cm) 12″ (30.5cm) Clearance to permanently closed windows.
D
18″ (45.7cm)**
18″ (45.7cm)**
Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2′ (0.6m) from the center line of the terminal.
E 12″ (30.5cm) 12″ (30.5cm) Clearance to unventilated soffit.
F
0″ (0mm)
0″ (0mm)
Clearance to an outside corner wall.
0″ (0mm)***
0″ (0mm)*** Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
G
2″ (51mm)***
2″ (51mm)*** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H
3′(0.9m)
3′(0.9m)****
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15′ (4.6m).
I
3′ (0.9m)
3′ (0.9m)**** Clearance to a service regulator vent outlet.
J 12″ (30.5cm)
9″ (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K
6′ (1.8m)
3′ (0.9m) Clearance to a mechanical air supply inlet.
L
7′ (2.1m)
7′ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M 12″ (30.5cm) 12″ (30.5cm)**** Clearance under a veranda, porch, deck or overhang.
N 16″ (40.6cm)
16″ (40.6cm) Clearance above the roof.
O
2′ (0.6m)*
2′ (0.6m) * Clearance from an adjacent wall including neighbouring buildings.
P
8′ (2.4m)
8′ (2.4m)
Roof must be non-combustible without openings.
Q
3′ (0.9m)
3′ (0.9m)
See chart for wider wall dimensions.
R
6′ (1.8m)
6′ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
S
12″ (30.5cm)
12″ (30.5cm) Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
- Recommended to prevent condensation on windows and thermal breakage ** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits. * The periscope requires a minimum 18 inches clearance from an inside corner. ** This is a recommended distance. For additional requirements, check local codes. 3 feet above if within 10 feet horizontally.
note:
Clearances are to be in accordance with local installation codes and the
requirements of the gas supplier. In their absence, clearances are to be as
listed above and are based on national codes.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
-
Recommended to prevent recirculation of exhaust products. For additional requirements, check local codes.
-
Permitted only if the balcony is fully open on a minimum of one side.
W415-4121 / D-0 / 05.22.24
minimum venting requirements – natural gas EN
flexible and rigid venting
3.3 horizontal termination (natural gas)
TLV50 / TLV62 / TLV74 SINGLE-SIDED
40′ 38 1/2′ (462″)
30′
V+H 40 ft. (For longer vent runs, a power
vent is required).
H 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
1-6 elbow zone 1-5 elbow zone
Refer to appliance specific GPV/
PVA instructions for other venting configurations.
1-4 elbow zone
1-3 elbow zone 1-2 elbow zone
1 elbow zone
V 20′
15′
10′
5′
1 7/8′ (22″) min.*
0′ Base of air collar
5′ 1 1/2′ (18″) max.*
0′
10′
15′
H
20′
25′
W415-4121 / D-0 / 05.22.24
19
EN minimum venting requirements – natural gas
flexible and rigid venting
TLV50_2 / TLV62_2 / TLV74_2 SEE-THROUGH
40′ 38 1/2′ (462″)
V+H 40 ft. (For longer vent runs, a power vent is required). H 20 ft. V + H are measured from the centre of vent elbows. Elbows are considered as 90º. Two 45º elbows = One 90º elbow.
30′
V 20′
1-6 elbow zone 1-5 elbow zone 1-4 elbow zone 1-3 elbow zone 1-2 elbow zone 1 elbow zone
15′
10′
5′
TLV74_2 – 4 1/8′ (40″) min. TLV62_2 – 3 3/8′ (40″) min. TLV50_2 – 1 7/8′
(22″) min.*
0′ Base of air collar
5′
10′
15′
3 7/8′ 4 3/8′ 4 7/8′
H
(46 1/2″) (52 1/2″) (58 1/2″)
max. max. max.*
TLV50_2 TLV62_2 TLV74_2
0′
20
W415-4121 / D-0 / 05.22.24
20′
25′
minimum venting requirements example – natural gas EN
flexible and rigid venting (NATURAL GAS ONLY)
40′
V = V + V = 8 ft
1
2
H = H + H = 10 ft
1
2
90°
V 2
90° H
1
V 1
30′
H 2
V 20′
15′
Base of
air collar
10′
4 3/4″ 5′ (57″)
V 1
0′
Base of air collar
H 1 5′
0′
1-6 elbow zone 1-5 elbow zone 1-4 elbow zone 1-3 elbow zone 1-2 elbow zone 1 elbow zone
H 2 V 2
10′
15′
H
20′
25′
V and H are measured from the center of the vent elbows
This example represents a vent that has a maximum of three 90º elbows, a
combined horizontal vent length (H ) of 10 feet and a combined vertical vent
length (V ) of 8 feet.
Since the vent is located in the dark shaded area, it is within the acceptable
vent configuration
W415-4121 / D-0 / 05.22.24
21
EN minimum venting requirements – natural gas
flexible and rigid venting
3.4 vertical termination (natural gas)
ALL APPLIANCES (NATURAL GAS ONLY)
40′
V+H 40 ft. (For longer vent runs,
a power vent is required).
H 20 ft.
0 elbow zone V + H are measured from the
centre of vent elbows. Elbows are
considered as 90º.
Two 45º elbows = One 90º elbow.
Refer to appliance
specific GPV/
PVA instructions
30′
for other venting
configurations.
2-7 elbow zone
2-6 elbow zone
2-5 elbow zone
2-4 elbow zone 2-3 elbow zone 2 elbow zone
20′
15′
10′
6′ 5′
0′ Base of air collar
22
0′
W415-4121 / D-0 / 05.22.24
5′
10′
15′
20′
note:
A 6′ (1.83m) minimum vertical rise is considered the minimum practical dimension for
the specific appliance enclosure and a minimal building structure. However, a greater
minimum vertical rise may be needed to suit the specific application constraints or
local codes and / or regulatory requirements.
minimum venting requirements – propane EN
rigid venting only
3.5 horizontal termination (propane)
TLV50 / TLV62 / TLV74 SINGLE-SIDED
40′ 38 1/2′ (462″)
30′
V+H 40 ft. (For longer vent runs, a power
vent is required).
H 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
1-6 elbow zone 1-5 elbow zone
Refer to appliance specific GPV/
PVA instructions for other venting configurations.
1-4 elbow zone
1-3 elbow zone 1-2 elbow zone
1 elbow zone
V 20′
15′
10′
5′
1 7/8′ (22″) min.*
0′ Base of air collar
1 1/2′ (18″) max.*
0′
5′
10′
15′
20′
25′
H
note: For natural vent propane appliances rigid venting must be used.
W415-4121 / D-0 / 05.22.24
23
EN minimum venting requirements – propane
rigid venting only
TLV50_2 / TLV62_2 / TLV74_2 SEE-THROUGH
40′ 38 1/2′ (462″)
V+H 40 ft. (For longer vent runs, a power vent is required). H 20 ft. V + H are measured from the centre of vent elbows. Elbows are considered as 90º. Two 45º elbows = One 90º elbow.
30′
V 20′
1-6 elbow zone 1-5 elbow zone 1-4 elbow zone 1-3 elbow zone 1-2 elbow zone 1 elbow zone
15′
10′
5′
TLV74_2 – 4 1/8′ (40″) min. TLV62_2 – 3 3/8′ (40″) min. TLV50_2 – 1 7/8′
(22″) min.*
0′ Base of air collar
5′
10′
15′
3 7/8′ 4 3/8′ 4 7/8′
H
(46 1/2″) (52 1/2″) (58 1/2″)
max. max. max.*
TLV50_2 TLV62_2 TLV74_2
0′
24
W415-4121 / D-0 / 05.22.24
20′
25′
minimum venting requirements – propane EN
(PROPANE – RIGID VENT ONLY)
40′
V = V + V = 8 ft
1
2
H = H + H = 10 ft
1
2
90°
V 2
90° H
1
V 1
30′
H 2
V 20′
15′
Base of
air collar
10′
4 3/4″ 5′ (57″)
V 1
0′
Base of air collar
H 1 5′
0′
1-6 elbow zone 1-5 elbow zone 1-4 elbow zone 1-3 elbow zone 1-2 elbow zone 1 elbow zone
H 2 V 2
10′
15′
H
20′
25′
V and H are measured from the center of the vent elbows
This example represents a vent that has a maximum of three 90º elbows, a
combined horizontal vent length (H ) of 10 feet and a combined vertical vent
length (V ) of 8 feet.
Since the vent is located in the dark shaded area, it is within the acceptable
vent configuration
W415-4121 / D-0 / 05.22.24
25
EN minimum venting requirements – propane
rigid venting only
3.6 vertical termination (propane)
ALL APPLIANCES (PROPANE ONLY)
40′
V+H 40 ft. (For longer vent runs,
a power vent is required).
H 20 ft.
0 elbow zone V + H are measured from the
centre of vent elbows. Elbows are
considered as 90º.
Two 45º elbows = One 90º elbow.
Refer to appliance
specific GPV/
PVA instructions
30′
for other venting
configurations.
2-7 elbow zone
2-6 elbow zone
2-5 elbow zone
2-4 elbow zone 2-3 elbow zone 2 elbow zone
20′
15′
10′
6′ 5′
0′ Base of air collar
26
0′
W415-4121 / D-0 / 05.22.24
5′
10′
15′
20′
note:
A 6′ (1.83m) minimum vertical rise is considered the minimum practical dimension for
the specific appliance enclosure and a minimal building structure. However, a greater
minimum vertical rise may be needed to suit the specific application constraints or
local codes and / or regulatory requirements.
4.0 rough framing – before appliance installation EN
note: When using optional finishing accessories, the framing dimensions and
finishing materials may differ from what is outlined in the section below;
refer to the leaflet instructions supplied in the accessory kit for specific
framing and finishing specifications.
! WARNING
· Risk of fire! · In order to avoid the possibility of exposed insulation or
vapour barrier coming in contact with the appliance
body, it is recommended that the walls of the appliance enclosure be
“finished” (i.e. drywall / sheetrock), as you would finish any other outside
wall of a home. This will ensure that clearance to combustibles is maintained
within the cavity. · Do not notch the framing around the appliance stand offs.
Failure to maintain air space clearance may cause over heating and fire.
Prevent contact with sagging or loose insulation or framing and other
combustible materials. Block opening into the chase to prevent entry of blown-
in insulation. Make sure insulation and other materials are secured. · When
constructing the enclosure, allow for finishing material thickness to maintain
clearances. Framing or finishing material closer than the minimums listed must
be constructed entirely of non-combustible materials. Materials consisting
entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or
any combination thereof are suitable. Materials that are reported as passing
ASTM E136, standard test method for behaviour of materials in a vertical tube
furnace at 1382ºF (750ºC) and UL763 shall be considered non-combustible
materials. · Minimum clearance to combusibles must be maintained or a serious
fire hazard could result. · The appliance requires a minimum enclosure height.
Measure from the appliance base. · If steel stud framing kits with cement
board are provided, or specified in the installation instructions, they must
be installed. · If specified in the installation instruction, finishing must
be done using a non-combustible board, ceramic tile, marble, etc. Do NOT use
wood or drywall. Any fire rated drywall is not acceptable.
note: For heavier finishing materials such as marble, we recommend adding
extra support to the frame. Ensure there is adequate floor support for the
appliance and finishing material.
W415-4121 / D-0 / 05.22.24
27
EN rough framing – before appliance installation
4.1 minimum framing dimensions
6″ (152mm) min.
H
G
1″ (25mm) min.
F E
F I
Do not put objects in front of the appliance (minimum distance of 4 feet)
minimum framing
TLV50 E
TLV62 20 1/8″ (511mm)
TLV74
F 65 13/16″ (1672mm) 77 13/16″ (1976mm) 89 13/16″ (2281mm)
G 71 1/8″ (1807mm) 79 9/16″ (2022mm) 88 1/16″ (2237mm)
H
17 3/8″ (442mm)
I 102 3/16″ (2595mm) 114 1/8″ (2899mm) 126 1/8″ (3204mm)
Horizontal vent sections: A minimum clearance of 3″ (76mm) on the top outside of the enclosure and 2″ (51mm) on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections within enclosures require a minimum clearance of 6″(152mm) at the top of the vent pipe. Vertical vent sections: A minimum of 1″ (25mm) all around the vent pipe on all vertical runs to combustibles is required except for clearances in appliances enclosures. Vertical vent sections within enclosures require a minimum clearance of 1″ (25mm) around the vent pipe.
28
W415-4121 / D-0 / 05.22.24
rough framing – before appliance installation EN
4.1.1 minimum clearance to combustible enclosures note:
Shaded components (finish framing) must be non-combustible materials.
1″ [25mm] minimum all sides for sections of vertical venting.
When passing through a ceiling, use firestop spacer W500-0028 (not supplied)
3″ [76mm] (minimum all sides for sections of horizontal venting) outside of
enclosure.
6″ [152mm] minimum (inside enclosure)
3″ [76mm] top (outside of enclosure)
2″ [51mm] sides / bottom (outside of enclosure)
0″ to non-combustible finishing such as brick and stone
When passing through
a wall, use firestop
spacer W615-0162
(supplied with W010-
4178 firestop spacer
L
assembly)
0″ to back standoffs
0″ to side standoffs
1/2″ finishing flange
0″ to bottom of the appliance
Horizontal vent sections: A minimum clearance of 3″ (76mm) on the top outside
of the enclosure and 2″ (51mm) on the sides and bottom outside of the
enclosure all around the vent pipe on all horizontal runs to combustibles is
required. Horizontal vent sections
minimum clearance
within enclosures require a minimum clearance of 6″ (152mm) at the top of the vent pipe. Vertical vent sections: The first 22″- 30″ (55.8cm) of vertical vent pipe is shielded. A 1″ (25mm) clearance to the shield is required.
Ref
TLV50
TLV62
TLV74
L
73″ (1854mm)
91″ (2311mm)
note:
The TLV series requires a minimum enclosure/ceiling height, as illustrated
(dimension L), measured from the bottom of the appliance. For temperature
requirements, this area must be left unobstructed. Some venting configurations
that require more vertical rise will require a larger enclosure to provide
minimum vertical clearance between vent pipes and combustibles.
W415-4121 / D-0 / 05.22.24
29
EN rough framing – before appliance installation
see-through
note:
Shaded components (finish framing) must be
non-combustible materials.
1″ [25mm] minimum all sides for sections of vertical venting.
When passing through a ceiling, use firestop spacer W500-0028 (not supplied)
3″ [76mm] (minimum all sides for sections of horizontal venting) outside of
enclosure.
14″ (356mm)
min.
6″ [152mm] minimum (inside enclosure)
3″ [76mm] top (outside of enclosure)
2″ [51mm] sides / bottom (outside of enclosure)
0″ to non-
combustible finishing
such as brick and
stone
When passing
through a wall, use
firestop spacer
L
W615-0162 (supplied with W010-
4178 firestop spacer
assembly)
0″ to side standoffs
SAFETY BARRIER
1/2″ finishing flange (4 sides)
0″ to base of the appliance
Horizontal vent sections: A minimum clearance of 3″ (76mm) on the top outside
of the enclosure and 2″ (51mm) on the sides and bottom outside of the
enclosure all around the vent pipe on all horizontal runs to combustibles is
required. Horizontal vent sections within enclosures require a minimum
clearance of 6″ (152mm) at the top of the vent pipe. Vertical vent sections: A
minimum of 1″ (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliances enclosures.
Vertical vent sections within enclosures require a minimum clearance of 1″
(25mm) around the vent pipe.
minimum clearance
Ref
TLV50_2
TLV62_2
TLV74_2
L
73″ (1854mm)
91″ (2311mm)
note:
The TLV series requires a minimum enclosure/ceiling height, as illustrated (dimension L), measured from the bottom of the appliance. For temperature requirements, this area must be left unobstructed. Some venting configurations that require more vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and combustibles.
30
W415-4121 / D-0 / 05.22.24
rough framing – before appliance installation EN
Before framing your appliance, determine vent requirements before deciding the
final location of the appliance. After rough framing, place the appliance in
its final position.
single-sided
Before framing an appliance, ensure to install the firestop first.
L
EF J
note:
The TLV series requires a minimum enclosure/ceiling height, as illustrated
(dimension L), measured from the bottom of the appliance. For temperature
requirements, this area must be left unobstructed. Some venting configurations
that require more vertical rise will require a larger enclosure to provide
minimum vertical clearance between vent pipes and combustibles.
minimum framing
Ref
TLV50
TLV62
TLV74
E
20 1/8″ (511mm)
F
65 13/16″ (1672mm) 77 13/16″ (1976mm) 89 13/16″ (2281mm)
J
Optional – Appliance does not need to be elevated above floor
L*
73″ (1854mm)
91″ (2311mm)
see-through
Before framing a see-through appliance, ensure to install the firestop first as it will not fit between the studs if installed after framing.
L
EF
note:
The TLV series requires a minimum enclosure/ceiling height, as illustrated
(dimension L), measured from the bottom of the appliance. For temperature
requirements, this area must be left unobstructed. Some venting configurations
that require more vertical rise will require a larger enclosure to provide
minimum vertical clearance between vent pipes and combustibles.
J
minimum framing
Ref
TLV50_2
TLV62_2
TLV74_2
E
16 3/16″ (411mm)
F
65 13/16″ (1672mm) 77 13/16″ (1976mm) 89 13/16″ (2281mm)
J
Optional – Appliance does not need to be elevated above floor
*L
73″ (1854mm)
91″ (2311mm)
*Minimum enclosure/ceiling height may be higher depending on venting configuration (See minimum clearance to combustibles).
W415-4121 / D-0 / 05.22.24
31
EN rough framing – before appliance installation
4.2 front frame installation
Remove screws from appliance, add the front frame, and reinstall the screws.
5.0 venting installation ! WARNING
· Ensure to unpack all loose materials from inside the firebox prior to
connecting the gas and electrical supply · If your appliance is supplied with
a remote, ensure the remote receiver is in the “OFF” position prior
to connecting the gas and electrical supply to the appliance. · For safe and
proper operation of the appliance, follow the venting instructions exactly. ·
The appliance exhaust flue collar must be sealed using Mill Pac. All exhaust
and intake vent pipe joints
must be sealed using red RTV high temp silicone sealant (W573-0002) (not
supplied) or black high temp Mill Pac (W573-0007) (not supplied). · If using
pipe clamps to connect rigid vent components, a minimum of 3 screws must also
be used to ensure the connection cannot slip off. · Do not clamp the flexible
vent pipe. · Risk of fire, explosion, or asphyxiation. Improper support of the
entire venting system may allow vent to sag and separate. Use vent run
supports and connect vent sections per installation instructions. · Risk of
fire, do not allow loose materials or insulation to touch the vent pipe.
Remove insulation to allow for the installation of the attic shield and to
maintain clearances to combustibles. · Do not fill the space between the vent
pipe and enclosure with any type of material. Do not pack insulation or
combustibles between ceiling firestops. Always maintain specified clearances
around venting and firestop systems. Install wall shields and firestops as
specified. Failure to keep insulation or other materials away from vent pipe
may cause fire. · For gas stoves only: If the appliance is installed directly
on carpeting, vinyl tile, or other combustible material other than wood
flooring, the appliance shall be installed on a metal or wood panel extending
the full width and depth, unless otherwise tested.
For optimum performance, it is recommended that all horizontal runs have a
minimum of 1/4″ (6mm) rise per foot using flexible venting. note: The vent
shield is telescopic and must be adjusted to shield the first 30″ (76.2cm) of
vertical vent when applicable.
For vent shield installation, see “vent shield installation” section.
Power vent system are available with reduced vent pipe diameter and longer
vent runs.
32
W415-4121 / D-0 / 05.22.24
venting installation EN
5.1 firestop spacer assembly
1. Install standoffs onto the firestop spacer (Fig. 1). 2. Install one vent shield onto the standoff on one side of the firestop spacer (Fig. 2). 3. Install the other vent shield on the opposite side of the firestop spacer (Fig. 3).
Type 1 (x18)
Firestop spacer / Espaceur coupe-feu
Standoff / Espaceur
Dimples / Fossettes
Side view
Standoff / Espaceur
Fig. 1
Fig. 2
Fig. 3
4. Roll the vent sleeve as shown and ensure to clip the ends together (Fig. 4). 5. Ensure both ends line up and secure ends with clip and fasteners (Fig. 5).
Fig. 4
Fig. 5
W415-4121 / D-0 / 05.22.24
33
EN venting installation
6. Insert the vent sleeve tabs into the firestop spacer slots then bend the
tabs over to secure to the firestop spacer along with 4 supplied fasteners
(Fig. 6).
note: Note orientation of dimples and standoffs.
Fig. 6
5.2 horizontal installation
! WARNING
· The firestop assembly must be installed with the vent shield to the top. ·
Terminals must not be recessed into a wall or siding more than the depth of
the return flange of the mounting
plate.
This application occurs when venting through an exterior
wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall, as illustrated, to accommodate the firestop assembly. Dry
VENT
SHIELD CAULKING
fit the firestop assembly before proceeding to ensure the brackets on the rear surface fit to the inside surface of the
horizontal framing.
FIRESTOP
The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2″ (215.9mm)
SPACER
thick but the vent shield must extend the full depth of the
combustible wall.
CAULKING
note:
Do not fill the air space between the firestop spacer and the exterior wall with any type of insulating material (i.e. spray foam).
ADD (31H64E.8I1Gc/H2m”T)
FINISHING MATERIAL
13A1D/D8″ (3W3.I3DcTmH )
DETERMINE THE CORRECT HEIGHT
A. Apply a bead of caulking (not supplied) around the outer edge of the hole of the firestop assembly, fit the firestop assembly to the hole and secure using 4 screws.
note: The above is for illustration purposes only. Vents do not always pass through center of frame.
B. Once the vent pipe is installed in its final position, apply red RTV silicone (W573-0002) (not supplied) between the pipe and the firestop.
34
W415-4121 / D-0 / 05.22.24
5.3 vertical installation
venting installation EN
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor.
See the “accessories” section to order specific kits required.
A. Determine the air terminal location, cut and frame a square opening, as
illustrated, in the ceiling and the roof to provide the minimum 1″ (25mm)
clearance between the vent pipe and any combustible material. Try to center
the vent pipe location midway between two joists to prevent having to cut
them. Use a plumb bob to line up the center of the openings. A vent pipe
shield will prevent any materials such as insulation, from filling up the 1″
(25mm) air space around the pipe. Nail headers between the joist for extra
support.
10 3/4″ 10 3/4″ (273mm) (273mm)
Firestop underside
of joist
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a finished
ceiling), and secure over the opening in the ceiling. A firestop must be
placed on the bottom of each framed opening in a roof or ceiling that the
venting system passes through. Apply a bead of caulking all around and place a
firestop spacer over the vent shield to restrict cold air from being drawn
into the room or around the fireplace. Ensure that both spacer and shield
maintain the required clearance to combustibles. Once the vent pipe is
installed in its final position, apply red RTV silicone (W573-0002) (not
supplied) between the pipe and the firestop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of
the shield and tighten. This will prevent any materials, such as insulation,
from filling up the 1″ (25mm) air space around the pipe.
Vent Pipe Shield
Caulking
Vent Pipe Shield
Vent Pipe Collar
note:
When the venting passes vertically through a ceiling, you may use either Wolf
Steel firestops or the venting manufacturer’s firestops for rigid venting,
provided they follow the required clearances listed in the appliance
installation manual. For Wolf Steel flexible venting, you MUST use the Wolf
Steel firestops listed below. For 4″/7″ appliances: When using flex venting,
use firestop assembly W500-0292 (not supplied). When using rigid venting, use
firestop assembly 4DFS (not supplied). For 5″/8″ appliances: When using flex
venting, use firestop assembly W500-0028 (not supplied). When using rigid
venting, use firestop assembly 5DFS (not supplied).
W415-4121 / D-0 / 05.22.24
35
EN venting installation
5.4 using flexible vent components
! WARNING
· Do not allow the inner flex pipe to bunch up on horizontal or vertical runs
and elbows. Keep it pulled tight. · Spacers are attached to the inner flex
pipe at predetermined intervals to maintain an even air gap to the outer
flex pipe. This gap is required for safe operation. A spacer is required at
the start, middle, and end of each elbow to ensure this gap is maintained.
These spacers must not be removed.
Elbow
Spacers
For safe and proper operation of the appliance, follow the venting
instructions exactly. The vent system must be supported approximately every 3
feet (0.9m) for both vertical and horizontal runs. Use Wolf Steel Ltd. support
ring assembly or equivalent noncombustible strapping to maintain the minimum
clearance to combustibles for both vertical and horizontal runs. All inner
flex pipe and outer flex pipe joints may be sealed using high temperature red
RTV silicone W573-0002 (not supplied) or the high temperature sealant W5730007
Mill Pac (not supplied). However, the high temperature sealant W573-0007 Mill
Pac (not supplied) must be used on the joint connecting the inner flex pipe
and the exhaust flue collar.
Use only approved flexible vent pipe kits marked:
“Wolf Steel Approved Venting” or “E2″ as identified by the stamp only on the flex pipes.
5.4.1 horizontal air terminal installation
Type 1 (x6)
36
A.
Stretch the inner flex pipe to the required length taking
into account the additional length needed for the finished wall surface. Apply a heavy bead of the red RTV silicone
ADD FASTTypEeN2E(xR4) TYPE
(W573-0002) (not supplied) to the inner sleeve of the air
terminal. Slip the vent pipe a minimum of 2″ (50.8mm)
over the inner sleeve of the air terminal and secure with a
minimum of 3 screws.
Caulking
B.
Using the outer flex pipe, slide over the outer combustion
air sleeve of the air terminal and secure with a minimum
InnePripFelex
of 3 screws. Seal using red RTV silicone (W573-0002) (not supplied).
Outer Flex Pipe 2″ (50.8mm) Overlap
C.
Insert the vent pipes through the firestop maintaining
the required clearance to combustibles. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing
Red RTV Silicone Screws
(SuppliAedD) D GRAPHIC
with caulking (not supplied).
D.
If more vent pipe needs to be used to reach the fireplace, Red RTV Silicone
couple them together, as illustrated. The vent system
must be supported approximately every 3 feet (0.9m) for
Screws Inner Coupler Outer Coupler
both vertical and horizontal runs. Use non-combustible
strapping to maintain the minimum clearance to
Outer Flex
combustibles.
E.
Stove Appliances Only: From inside the house, using
Outer Flex Pipe
Inner Flex Pipe
Pipe
Red RTV Silicone (W573-0002) (not supplied), seal
between the vent pipe and the firestop. Then slide the black trim collar over the vent pipe up to the
firestop.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return flange.
W415-4121 / D-0 / 05.22.24
5.4.2 vertical air terminal installation
! WARNING
venting installation EN
· Maintain a minimum 2″ (51mm) space between the air inlet base and the storm collar.
note: Fastening hardware provided with appropriate roof terminal and liner kits.
A. Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case, the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
B. Stretch the inner flex pipe to the required length. Slip the inner flex pipe a minimum of 2″ (51mm) over the inner pipe of the air terminal connector and secure with a minimum of three screws, when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws when using 8/10 or 8/11 venting. Seal using a heavy bead of red RTV silicone sealant (W573-0002) (not supplied).
Roof Support
C. Repeat using the outer flex pipe, using a heavy bead of red RTV silicone sealant (W573-0002) (not supplied) and a minimum of three screws, when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws when using 8/10 or 8/11 venting.
Inner Pipe
D. Thread the air terminal connector / vent pipe assembly down through the roof. The air terminal must be positioned vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the
Air Terminal Connector
top of the air terminal is 16″ (40.6cm) above the highest point that it
Red RTV
penetrates the roof.
Silicone (W572-0002)
E. Remove nails from the shingles, above and to the sides of the air terminal connector. Place the flashing over the air terminal connector leaving a min. 3/4″ (19mm) of the air terminal connector showing above
Inner Flex Pipe Outer Flex Pipe
the top of the flashing. Slide the flashing underneath the sides and
upper edge of the shingles. Ensure that the air terminal connector is
properly centered within the flashing, giving a 3/4″ (19mm) margin all
around. Fasten to the roof. Do not nail through the lower portion of the
flashing. Make weather-tight by sealing with caulking. Where possible,
cover the sides and top edges of the flashing with roofing material.
Air Inlet
F. Aligning the seams of the terminal and air terminal connector, place the 2″ (51mm)
Base
terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with a minimum of three screws, when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws
Caulking Storm Collar
when using 8/10 or 8/11 venting.
Weather
G. Apply a heavy bead of weatherproof caulking 2” (51mm) above the
Sealant
flashing. Install the storm collar around the air terminal and slide down
to the caulking. Tighten to ensure that a weather-tight seal between the
Flashing
air terminal and the collar is achieved.
H. If more vent pipe needs to be used to reach the appliance, see “horizontal
5.4.3 aapirptleiarmnicnealvineAsntDatlclDaotinoFnn”AesceStcitToionnE. NER TYPE
A. Install the inner flex pipe to the appliance. Secure with a minimum of three screws when installing 3″/5″, 4″/7″ or 5″/8″ venting, or six screws when installing 8″/10″ or 8″/11″ venting. Seal the joint and screw holes using Mill Pac sealant (W573-0007) (not supplied).
INSERT #8 X 1/2″
Self Drilling Screws
IMAGE HERE 21″1(/540″ .(381m.8mmm) ) Overlap
B. Install the outer flex pipe to the appliance. Secure with a minimum of three screws when installing 3″/5″, 4″/7″ or 5″/”8 venting, or six screws when installing 8″/10″ or 8″/11″ venting. Seal the joints using high temperature red RTV silicone (W573-0002) (not supplied).
Mill-Pac Sealant
Red RTV Silicone
W415-4121 / D-0 / 05.22.24
37
EN venting installation
5.5 restricting vertical vents
Vertical installations may display a very active flame. If this appearance is
not desirable, the exhaust outlet may be restricted with a Wolf Steel approved
restrictor kit. This kit is not recommended for short vertical vent runs.
Depending on the model and/or year of your appliance, mounting holes may not exist.
5.5.1 TLV50 / TLV50_2
A.
If mounting holes exist, remove the screws from the firebox top, align the restrictor plate as illustrated and
secure.
B.
If mounting holes do not exist, align the restrictor plate as illustrated and secure using the two screws
(supplied).
C.
Ensure the plate will pivot at the slot up into the exhaust outlet.
D.
Depending on the amount of restriction desired, the restrictor plate can be left flat for most restriction or
bent up for varying degrees of restriction.
Top view
Mounting screws
Restrictor
Firebox top
Restrictor
Exhaust collar
3 2 1
5.5.2
8x½ hex head sheet metal screw
1. Most restriction 2. Moderate restriction 3. Least restriction
TLV62 / TLV62_2 / TLV74 / TLV74_2
Firebox top
A.
Secure 5″ restrictor to mounting plate using 2 screws (supplied).
B.
Remove baffle by removing 1 screw from firebox. Set screw and baffle aside.
C.
Align mounting plate clearance holes (4) over existing screws protruding into firebox. For ease of access,
ensure restrictor and mounting plate are installed with screws installed in Step A facing upwards
(into exhaust collar).
D.
Install 4 self-drilling screws (supplied) (2 per side).
note: For ease of installation, the mounting plate was designed with 2 fixed holes and 2 slotted holes.
E.
Reinstall baffle using screw removed in step B.
BAFFLE
TOP VIEW
5″ RESTRICTOR
FIREBOX MOUNTING
TOP
PLATE
MOUNTING SCREWS
38
W415-4121 / D-0 / 05.22.24
EXHAUST COLLAR
8 x ½ HEX HEAD SHEET METAL SCREWS
FIREBOX TOP
1. MOST RESTRICTION 2. MODERATE RESTRICTION 3. LEAST RESTRICTION
5.6 vent shield installation
venting installation EN
IMPORTANT: For ease of installation, the front frame can be removed. The front frame must be reinstalled prior to installing the nailing tabs.
note: The vent shield is telescopic and must be adjusted to shield the first 22″ – 30” of vertical vent always used. 1. Unscrew the fasteners on the vent shield assembly. DO NOT DISCARD FASTENERS (Figure 1). 2. Adjust the vent shield to its maximum vertical (Figure 2). 3. Use the fasteners in step 1 to hold the new vent shield height (Figure 3).
Fig. 1
Fig. 2
4. Unscrew the fasteners as shown (Figure 4). DO NOT DISCARD FASTENERS 5. Use
the fasteners in step 4 to secure the vent shield to the appliance (Figure 5).
6. Secure the vent shield with two fasteners (supplied) to the header shield
(Figure 6).
Type 1 (x2)
Fig. 3
Front of appliance
Fig. 4
Fig. 5
FOR SEE-THROUGH APPLIANCES, REPEAT STEPS WITH THE OPPOSITE SIDE (2 vent shields required).
SEE-THROUGH EXAMPLE
W415-4121 / D-0 / 05.22.24
39
EN v6e.0nteinlegcitnrsictallaintifonrmation
6.1 hard wiring connection
It is necessary to hard wire this appliance. Permanently framing the appliance
with an enclosure, requires the appliance junction box to be hard wired. This
appliance must be electrically connected and grounded in accordance with local
codes. In the absence of local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70-1996 National Electrical Code in
the United States.
6.2 receptacle wiring diagram
L1
Power Supply L2
To optional LHAD kit
Cable Connector
Route power supply and optional LHAD kit through the outer firebox to the receptacle mounted on the bottom of the appliance. For optional LHAD kit installation, please refer to the leaflet provided in the kit.
6.3 in the event of a power failure
If the battery holder/switch is equipped with batteries, the appliance will
still have ON/OFF functions during a power failure. Refer to “operation”
section in the Owner’s manual when communications between battery holder/
switch and remote have been lost. The battery holder/switch will emit a “beep”
sound to confirm programming has been successful once power is restored.
During a power failure, if the fireplace was on, the flame height will stay at
the setting prior to the failure. If off when the failure occurs and then
turned on, the flame height will come on at “HI”. The flame height can then be
controlled by the remote.
In most cases, your appliance will operate with simple functions available
until power is restored. All other electrical features / accessories will not
work during a power failure.
40
W415-4121 / D-0 / 05.22.24
6.4 SbAFaETtYteBArRyRIEhR older/switch installation
electrical information EN
ON REMOTE OFF (4) AA Batteries
ON REMOTE OFF (4) AA Batteries
p(mrougsrtabm8tethfomeeaetihanctpegcmpesatlisihdaxseinemicboruelefemmfoorte)
Install the battery holder/switch into a standard electrical switch box.
Determine an appropriate location and install the electrical box.
note:
Ensure the 3 position slider switch is in the “REMOTE” position (middle).
6.5 initializing the battery holder/switch for the first time
note: The initializing process must be completed within 10 seconds of pressing
the reset / program (PRG).
A.
Install the 4 AA batteries into the battery holder, note the polarity of the batteries and insert as indicated
on the cover (+/-).
B.
Ensure the 3 position slider switch is switched to the “REMOTE” position (middle position).
C.
Press the reset/programming button, use a small object such as a paper clip in order to reach the button
marked PRG, as shown in the illustration below.
D.
The battery holder will beep 3 times to indicate that it’s ready to synchronize with the remote.
E.
Install the 3 AAA batteries into the remote, as shown in the photograph below, then press the ON button,
The battery holder will beep 4 times to indicate that the remote’s command is accepted.
Battery Holder
Remote
(4) AA Batteries
Slider Switch
Reset / Program Button (PRG)
W415-4121 / D-0 / 05.22.24
41
EN electrical information
6.6 access panel
! WARNING
· Do not use this appliance if any part has been under water. Call a qualified
service technician immediately to have the appliance inspected for damage to
the electrical circuit.
· Risk of electrical shock or explosion. Do not wire 110V to the valve or to
the appliance wall switch. Incorrect wiring will damage controls.
· All wiring should be done by a qualified electrician and shall be in
compliance with local codes. In the absence of local codes, use the current
CSA22.1 Canadian Electric Code in Canada or the current National Electric Code
ANSI/NFPA NO. 70 in the United States.
· Always light the pilot whether for the first time or if the gas supply has
run out, with the glass door opened or removed.
Before finishing in the appliance, test the operation using the remote
control, cycling it through all of its different modes, see owner’s manual.
Once finished in, access to the control components can only be done through
the inside of the appliance.
6.7 wiring
TLV50 Illustrated
! WARNING
· Do not wire 110 volts to the valve or wall switch.
note: This appliance is equipped with a three-prong (grounding) plug for
protection against shock hazard and should be connected into a properly
grounded circuit. Do not cut or remove the grounding prong from the plug.
6.8 eFIRE application controller
When fully equipped, the eFIRE application allows you to create every
imaginable color, selecting the one that fits your current mood, or your décor
with ease, the simple colour wheel tool swiftly scrolls through the full color
spectrum. Napoleon’s eFIRE app controls every function of your fireplace
including; on/off, flame height and a timer to create a schedule for your
fireplace that works for you.
Using the instructions on the eFIRE controller application website
http://napoleon.com/efire, install the app and enjoy the features the eFIRE
Controller app offers.
note: The remote control is considered the master control for the appliance
and can always be used to turn the appliance off (for example, in the event
the user who’s eFIRE controller app was controlling the appliance leaves the
home).
42
W415-4121 / D-0 / 05.22.24
4 3
W415-4121 / D-0 / 05.22.24
electrical information EN
PILOT
W010-4895 NG W010-4896 P
W660-0204 HIGH LIMIT SWITCH
W750-0424 WIRE HARNESS
W750-0276 WIRE HARNESS
W750-0294
W405-0096 ACCENT LIGHTS
W750-0429
W750-0423
6.8.1 TLV50 / TLV50_2 wiring diagram
W750-0317 (EXTENSION)
BATTERY HOLDER COMPLETE WITH PROGRAM BUTTON
W350-0655
RESET BUTTON
LAMP COMFORT FAN
GROUND
W707-0019
W190-0177 (RECEIVER)
BLUETOOTH (W190-0090)
W750-0358 (LIGHT/BLOWER/
PIGTAIL) W190-0125
LED CONTROLLER COMMAND SENSE LED WIRE 8 LED WIRE MV
W750-0435 BT, WIRE HARNESS
LED LIGHTS W750-0433
W750-0401 TRANSFORMER (W707-0019)
W415-4121 / D-0 / 05.22.24
44
W660-0204 HIGH LIMIT SWITCH
PILOT
W010-4895 NG W010-4896 P
W750-0424 WIRE HARNESS
W750-0276 WIRE HARNESS
W750-0317 (EXTENSION)
BATTERY HOLDER COMPLETE WITH PROGRAM BUTTON
W350-0655
RESET BUTTON
W750-0294 ACCENT LIGHTS
W405-0096
GROUND
BLUE CONNECTORS W707-0027
W750-0422 LIGHT WIRE HARNESS
TERMINAL BUS W060-0008
RED CONNECTORS
LAMP COMFORT FAN
W190-0177 (RECEIVER)
BLUETOOTH (W190-0090)
W750-0358 (LIGHT/BLOWER/
PIGTAIL) W190-0125
LED CONTROLLER COMMAND SENSE LED WIRE R LED WIRE L
W750-0435 BT, WIRE HARNESS
LED LIGHTS W750-0433
W750-0401 TRANSFORMER (W707-0019)
EN electrical information
6.8.2 TLV62 / TLV62_2 / TLV74 / TLV74_2 wiring diagram
ele7c.0trigcasl iinnfsotramllation EN ! WARNING
· Risk of fire, explosion, or asphyxiation. Ensure there are no ignition
sources such as sparks or open flames. · Support gas control when attaching
gas supply pipe to prevent damaging gas line. · Always light the pilot whether
for the first time or if the gas supply has run out with the glass door opened
or removed. Purging of the gas supply line should be performed by a qualified
service technician. Ensure that a continuous gas flow is at the burner before
closing the door. Ensure adequate ventilation. For gas and electrical
locations, see “dimensions” section. · All gas connections must be contained
within the appliance when complete (gas fireplaces only). · High pressure will
damage valve. Disconnect gas supply piping before testing gas line at test
pressures above 1/2 PSIG. · Valve settings have been factory set, do not
change.
Installation and servicing to be done by a qualified installer. · Move the
appliance into position and secure. · If equipped with a flex connector, the
appliance is designed to accept a 1/2″ (13mm) gas supply. Without the
connector, it is designed to accept a 3/8″ (9.5mm) gas supply. The appliance
is equipped with a manual shut off valve to turn off the gas supply to the
appliance. · Connect the gas supply in accordance to local codes. In the
absence of local codes, install to the current CAN/CSA-B149.1 Installation
Code in Canada or to the current National Fuel Gas Code, ANSI Z223.1 / NFPA 54
in the United States. · When flexing any gas line, support the gas valve so
that the lines are not bent or kinked. · The gas line flex-connector should be
installed to provide sufficient movement for shifting the burner assembly on
its side to aid with servicing components. · Check for gas leaks by brushing
on a soap and water solution. Do not use open flame.
note:
Connect the gas supply to the 1/2″ (13mm) shut off and flex connector
(supplied). Ensure gas supply is secured.
After installing the electrical wiring and gas lines, ensure to test the
appliance before finishing the framing and finishing the appliance.
Before finishing in the appliance test the operation using the remote control,
cycling it through all of its different modes, see “operation” section in the
Owner’s manual. Should troubleshooting be required, access to the controls can
be made through the pre-finishing access panel.
W415-4121 / D-0 / 05.22.24
45
EN e8.le0ctorpicearlaitniofonrmation
! WARNING
· If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury, or loss of life.
· If applicable, always light the pilot whether for the first time or if the
gas supply has run out with the glass door opened or removed.
Ensure that a continuous gas flow is at the burner before installing the door. When lit for the first time, the appliance will emit an odor for a few hours. This is a normal temporary condition caused by the “burn-in” of paints and lubricants used in the manufacturing process and will not occur again. After extended periods of non-operation, such as, following a vacation or warm weather season, the appliance may emit a slight odor for a few hours. This is caused by dust particules in the heat exchanger burning off. In both cases, open a window to sufficiently ventilate the room.
FOR YOUR SAFETY READ BEFORE LIGHTING
· Do not turn on if children or other at risk individuals are near the
appliance. · This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the
pilot by hand. · Before operating, smell all around the appliance area for gas
and next to the floor because some gas is
heavier than air and will settle on the floor. · Do not use this appliance if
any part has been under water. Immediately call a qualified service technician
to inspect the appliance and replace any part of the control system and any
gas control which has been underwater.
WHAT TO DO IF YOU SMELL GAS
· Turn off all gas to the appliance. · Open windows. · Do not try to light any
appliance. · Do not touch any electric switch; do not use
any phone in your building
· Immediately call your gas supplier from a neighbour’s phone. Follow the gas
supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.
LIGHTING INSTRUCTIONS
note: This appliance is equipped with an ignition device which automatically
lights the pilot. Do not try to light the pilot by hand.
A. Stop! Read the above safety information on this label. B. Remove batteries
from the transmitter and set thermostat to lowest setting, if
equipped. C. Turn off all electrical power to the appliance. D. Open the glass
door, if equipped. E. Turn the manual shut-off valve clockwise to the “OFF”
position. (Shut-off valve is
located on the flex connector). F. Wait five (5) minutes to clear out any gas.
If you smell gas including near the
floor, STOP! Follow the instructions above in the “WHAT TO DO IF YOU SMELL
GAS” section. If you don’t smell gas; close the glass door and go to the next
step. G. Turn the manual shut-off valve counter clockwise to the “ON”
position. H. Turn on all electrical power to the appliance and re-install the
batteries into the transmitter. Set thermostat to desired setting, if
equipped. I. Turn on the remote wall switch to the appliance. J. If the
appliance will not operate, follow instructions “TO TURN OFF GAS” and call
your service technician or gas supplier.
TO TURN OFF GAS A. Set thermostat to lowest setting, if equipped. B. Turn off
the remote wall switch to the appliance. C. Turn off all electric power to the
appliance if service is to be performed. D. Turn manual shutoff valve
clockwise to the “OFF” positon. Do not force.
add gas knob
OS
MANUAL SHUT-OFF (SHOWN IN OFF POSITION)
AB
add gas valve
PILOT SCREW
46
W415-4121 / D-0 / 05.22.24
8.1 pilot-on-demand
operation EN
This appliance is equipped with an “On Demand” intermittent pilot ignition system (IPI) which also includes a continuous pilot ignition (CPI) mode with an integrated seven day timer. This system minimizes your appliance’s carbon footprint as well as reducing its annual fuel consumption and operating costs.
In IPI mode, the pilot will ignite prior to the main burner, when the appliance is turned on using a switch, remote or from a call for heat with the thermostat (if equipped). Once the appliance is turned off (or the call for heat is satisfied), the main burner and pilot flame will shut down.
The continuous (CPI) mode is intended to enhance the performance of the appliance during the startup phase in colder climates and extreme weather by keeping the system warm when the main burner is not in use. However, the timer feature provides the convenience that the appliance automatically switches off the pilot when the appliance has not been used for seven days to save unnecessary fuel consumption.
When the CPI function is turned on, the pilot will remain on after the main burner is turned off. A timer will then begin the countdown for approximately seven days before shutting off the pilot if the appliance is not used. This countdown will reset anytime the appliance main burner is used. Therefore, if the appliance is regularly used day to day, the pilot will remain on. However, this system does not require the user to remember to turn the pilot off as summer approaches and avoids unnecessary fuel consumption while still readily turned back on when the cold weather returns.
Your appliance may be equipped with an ACS or remote control device (Fig. 1) which enables you to select IPI or CPI modes.
If your appliance is equipped with an ACS switch, it has the option to change
modes: Fig. 2: Flipping the switch ON turns on the continuous pilot with timer and flipping
(Fig. 1)
the switch OFF turns on the intermittent pilot ignition.
Fig. 3: If installed with the blue wire facing up, flipping the switch UP turns on the continuous pilot with timer
and flipping the switch DOWN turns on the intermittent pilot ignition. If installed with the white wire facing up, the
opposite is true.
If your appliance is equipped with a remote control device capable of selecting IPI / CPI modes, refer to remote operating instructions.
In order to start your pilot, turning the main burner on with the switch, remote or thermostat and then turning it off will reactivate the continuous pilot mode and reset the seven day timer.
For further information, refer to www.napoleon.com/pilotondemand.
(Fig. 2)
(Fig. 3)
W415-4121 / D-0 / 05.22.24
47
EN n9a.0ilinngaitlianbgintasbtailnlastiaolnlation
IMPORTANT: If the front frame was removed, it must be reinstalled prior to
installing the nailing tabs.
1
2
Remove the screws from the appliance. DO NOT DISCARD.
3 Type 1 (x2)
Align the nailing tab with the holes on the appliance, secure with the screws in step 1.
4
TOP VIEW
XX
Secure to the upper front frame using 2 screws (supplied).
XX
XX XX
note:
See “venting”, “electrical information” and “gas installation” sections prior
to finish framing.
IMPORTANT: Do NOT remove the knockouts unless installing Dynamic Heat
ControlTM/Ducted Heat ManagementTM. If damaged or removed without Dynamic Heat
ControlTM/Ducted Heat ManagementTM, appliance will overheat and will cause a
fire hazard.
48
W415-4121 / D-0 / 05.22.24
10.0 finish framing – after appliance installation EN
10.1 framing with non-combustibles
single-sided flush
note:
Shaded components (finish framing) must be
non-combustible materials.
Finish framing must be built after the appliance has been placed in its final position and venting connected.
Ceiling
L
K J
E F
Drywall
minimum framing
Ref
TLV50
TLV62
TLV74
K
48 3/16″ (1224mm)
E
20 1/8″ (511mm)
Insulation
F
65 13/16″ (1672mm) 77 13/16″ (1976mm) 89 13/16″ (2281mm)
J
Optional – Appliance does not need to be elevated above floor
L
73″ (1854mm)
91″ (2311mm)
note:
The TLV series requires a minimum enclosure/ceiling height, as illustrated
(dimension L), measured from the bottom of the appliance. For temperature
requirements, this area must be left unobstructed. Some venting configurations
that require more vertical rise will require a larger enclosure to provide
minimum vertical clearance between vent pipes and combustibles.
W415-4121 / D-0 / 05.22.24
49
EN finish framing – after appliance installation
recessed
note:
Finish framing must be built after the appliance has been placed in its final
position and venting connected.
Ceiling
This configuration also requires recess area to use non-combustible facing due to close proximity to vent.
L M*
J
K
F
E
Drywall
minimum framing
Ref
TLV50
K
TLV62 48 3/16″ (1224mm)
TLV74
Insulation
E
20 1/8″ (511mm)
F
65 13/16″ (1672mm) 77 13/16″ (1976mm) 89 13/16″ (2281mm)
J
Optional – Appliance does not need to be elevated above floor
L
83″ (2108mm)
91″ (2311mm)
M*
3″ (76mm)
*Can only be increased to 4″ max by building a protrusion.
note: The TLV series requires a minimum enclosure/ceiling height, as
illustrated (dimension L), measured from the bottom of the appliance. For
temperature requirements, this area must be left unobstructed. Some venting
configurations that require more vertical rise will require a larger enclosure
to provide minimum vertical clearance between vent pipes and combustibles.
50
W415-4121 / D-0 / 05.22.24
finish framing – after appliance installation EN
see-through flush
note:
Shaded components (finish framing) must be non-combustible materials.
Ceiling
Finish framing must be built after the appliance has been placed in its final position and venting connected.
K
L
Drywall
E F
Insulation
J
minimum framing
Ref
TLV50_2
TLV62_2
TLV74_2
K
48 3/16″ (1224mm)
E
16 3/16″ (411mm)
F
65 13/16″ (1672mm) 77 13/16″ (1976mm) 89 13/16″ (2281mm)
J
Optional – Appliance does not need to be elevated above floor
L
73″ (1854mm)
91″ (2311mm)
note:
The TLV series requires a minimum enclosure/ceiling height, as illustrated
(dimension L), measured from the bottom of the appliance. For temperature
requirements, this area must be left unobstructed. Some venting configurations
that require more vertical rise will require a larger enclosure to provide
minimum vertical clearance between vent pipes and combustibles.
W415-4121 / D-0 / 05.22.24
51
EN 1fi1n.i0shfinigshing ! WARNING
· Risk of fire! · Never obstruct the front opening of the appliance. · The
front of the appliance must be finished with any non-combustible materials
such as brick, marble, granite,
etc., provided that these materials do not go below the specified dimension,
as illustrated. · Do not strike, slam, or scratch. Do not operate appliance
with glass removed, cracked, or scratched. · Facing and/or finishing material
must never overhang into the appliance opening. · The glass door assembly is a
safety device designed to pivot forward when relieving excess pressure that
might occur. Finishing or other materials must not be located in the opening
surrounding the door as this will interfere with the doors ability to relieve
pressure. · If applicable, drywall dust will penetrate into the blower
bearings, causing irreparable damage. Care must be taken to prevent drywall
dust from coming into contact with the blower or its compartment. Any damage
resulting from this condition is not covered by the warranty policy.
11.1 fastener placement restriction
2″
Gas Valve
1 1/2″
6″ 8″
No fasteners permitted.
No fasteners permitted with greater than 3/4″ penetration into appliance.
When securing non-combustibles, we suggest using high temperature construction
adhesive within 2″ (5.08cm) above and to the sides from the appliance opening
and 8″ (20.3cm) below the appliance opening. DO NOT SCREW IN THE RESTRICTED
AREA AS THIS COULD DAMAGE THE INTERNAL COMPONENTS OF THE APPLIANCE THAT CAN
CAUSE INJURY OR DEATH.
Maximum screw length to be used outside the restricted screw area is 3/4″
greater than finishing material thickness.(i.e. no fastener permitted that
penetrates the appliance more than 3/4″
52
W415-4121 / D-0 / 05.22.24
11.2 finishing with non-combustibles
finishing EN
Non-combustible
finishing is
Q
required.
7″ (179mm)
15 5/8″ (397mm)
26 1/2″ (673mm)
minimum non-combustible
TLV50 / TLV50_2 TLV62 / TLV62_2 TLV74 / TLV74_2
Q
66 9/16″ (1691mm)
78 9/16″ (1991mm)
90 9/16″ (2300mm)
SHADED AREA MUST BE NON-COMBUSTIBLE MATERIALS. Recessed installation requires recess material to use noncombustible facing due to close proximity to vent.
W415-4121 / D-0 / 05.22.24
53
EN finishing ! WARNING
· Non-combustible finishing material tight to the frame around the safety
barrier (PSB) frame must not project more than 4″ (10cm) from the face of the
safety barrier (above the door and sides only). If greater projections are
needed, increase the clearance to the sides and top by 2″ (51mm) for every 1″
(25mm) projection.
SAFETY BARRIER
4″ (10cm) Maximum protrusion (must not encroach on finishing flange)
Non-combustible protrusion
2″ 51mm
SIDE VIEW 4″
10cm
1″ 25mm
Max
finishing flange all around
SAFETY BARRIER
54
W415-4121 / D-0 / 05.22.24
11.3 installing non-combustible board
! WARNING
finishing EN
· The surface above the appliance gets very hot. If proper finishing materials are not used, cracking can occur. · See fastener placement restrictions. Longer screws may damage gas line and/or internal components.
1. Align the top non-combustible panel against the appliance and secure in place with the drywall screws. 2. Align the side non-combustible panels against the appliance and secure in place with the drywall screws.
No fasteners permitted
No fasteners permitted with greater than 3/4″ penetration into appliance.
2″ 1 1/2″
note: The 15 5/8″ (39.7cm) above and the 7″ (178mm) on either side of the
appliance opening must not be finished with any combustible materials.
Joint Compound where required Joint compounds such as Durabond 90 and tapes
that are resilient to heat and cracking should be used when taping and mudding
seams.
Setting tiles and grouting We recommend you use tiles with a dry butt joint to
be installed using a two-part mortar with an acrylic latex additive, such as
Mapei Kerabond/Kerlastic, to allow for slight movement in the normal operation
of the appliance. If grout is used between the tiles, a polymer-based grout,
such as Mapei Ultracolour plus, is recommended.
Primer/Paint For a painted surface, use a 100% acrylic latex primer and finish
coat. Light coloured paints may discolour.
note: We recommend using high temperature adhesive and clamping to adhere
drywall to lower access panel. Secure with fasteners no longer than 3/4″, see
“fastener placement restriction” section. Once adhesive has cured, remove
sharp edge of fastener to allow access.
W415-4121 / D-0 / 05.22.24
55
EN finishing
11.4 minimum combustible mantel clearances
! WARNING
· Risk of fire. Maintain all specified air space clearances to combustibles.
Failure to comply with these instructions may cause a fire or cause the
appliance to overheat. Ensure all clearances (i.e. back, side, top, vent,
mantel, front, etc.) are clearly maintained.
· When using paint or lacquer to finish the mantel, the paint or lacquer must
be heat resistant to prevent discolouration.
· Installing a television or other electronics above the appliance may cause
discolouration, melting, or damage to the electronics. Use clearances as
guidelines and refer to your TV manufacturer’s instructions for further
information.
Combustible mantel clearance can
MANTEL DEPTH
vary according to the mantel depth.
Use the graph to determine the
clearance needed.
24
22
Installing a mantel between this
20
appliance and electronics or other
18
materials that may be sensitive to heat, will reduce the effect of direct heat on them. Ensure mantel is properly sized (width & depth) to suit the object being mounted above.
MH AE NI TG EH
16
14 12 10 8
LT 6
MANTEL HEIGHT
Follow mantel height restrictions for proper clearance according to the depth of the mantel.
4 2
0 1 2 3 4 5 6 7 8 9 10 11
Top of finishing
flange
A non-combustible mantel is considered a non-combustible protrusion, see “finishing” for protrusion restrictions.
MANTEL DEPTH
33 7/8″ (A860mm)
Optional
2″ (51mm)
Bottom of finishing flange
hearth
extension
Bottom of the
appliance
56
W415-4121 / D-0 / 05.22.24
11.5 TV mounting restrictions (without DHCTM)
finishing EN
Flush installation without mantel
TV bracket
Partially recessed installation with mantel
6″ min. TV bracket
Enclosure
Appliance
Top of finishing flange (fireplace opening)
2.5″ min. 2″ min. (3″ max. recommended)
A Enclosure
Top of finishing flange (fireplace opening)
Appliance
Recessed installation with protrusion
6″ min. TV bracket
Flush installation with mantel
6″ min. TV bracket
2.5″ min. 2″ min. (3″ max. recommended)
Enclosure
Top of finishing flange (fireplace opening)
Appliance
See “minimum clearance A to mantle” section
(installation manual).
The volume of air must be added to the enclosure to accomodate the recessed area.
2.5″ min. 2″ min. (3″ max. recommended)
A Enclosure
Appliance
Top of finishing flange (fireplace opening)
note:
· These are recommended minimum clearances only and are in supplied in good
faith and not a guarantee of compliance with TV manufacturers’ maximum
allowable operating temperatures. Always comply to TV manufacturers’
requirements.
· TV temperatures must be validated at the time of installation as air flow
characteristics within the room can vary and maximum acceptable operating
temperatures can vary from appliance to appliance. TVs cannot be used where
the TV temperature exceeds the manufacturer’s maximum allowable operating
temperatures (see TV manufacturer’s specifications).
· Mantel height and depth must conform to mantel clearance requirements
specified in this manual, see “minimum clearance to combustible mantel”
section in installation manual.
· Dimension “A” the gap between the top of the finishing flange and the bottom
of the TV are taken from the top of the fireplace opening.
· TV temperatures may be further reduced by increasing the horizontal distance
between the front of the TV and the front edge of the mantel or by increasing
dimension “A”. However, increasing the gap between the top of the mantel and
the bottom of the TV beyond the maximum recommended figure, typically results
in higher temperatures. Minimum clearance between the mantel and bottom of the
TV should be maintained to allow air circulation below and behind the TV.
W415-4121 / D-0 / 05.22.24
57
EN finishing
11.6 safety barrier installation / removal
A.
To remove the safety barrier from the appliance carefully lift it up and off the shoulder screws.
SAFETY BARRIER
SAFETY BARRIER
B.
Place the safety barrier onto the appliance by lifting it up and hooking onto the side shoulder screws.
Adjust to fit snug against the finish material. Ensure safety barrier is installed correctly.
11.7 firebox glass door installation / removal
! WARNING
· Do not insert fingers in the gap between the door and the door frame, or
between the spring latches & door. there is a risk of injury due to the spring
mechanism. Do not insert fingers in the spring door latch mechanism.
Side view
Door trim
Door frame
Door trim
TLV50 Illustrated
A.
Remove the safety screen assembly, refer to the “safety screen installation / removal” section for details
B.
Remove the door trim by carefully lifting it up and off from behind the bottom frame of the glass door.
C.
For door removal, locate the top and bottom door latches. Pull latches forwards and away to disengage
door latches.
note: Ensure to leave one hand on the glass door during entire door removal.
D.
Tilt the top of the door forwards 90 degrees, then lift it up and out of the door latches.
E.
Reverse these steps to re-install the door, ensure the top and bottom door latches are properly
engaged prior to releasing the door.
58
W415-4121 / D-0 / 05.22.24
note: Ensure the door opens freely and closes sealed.
finishing EN
TLV50 Illustrated
IMPORTANT: Once latches are engaged, test to make sure that the door is
sealed.
W415-4121 / D-0 / 05.22.24
59
EN finishing
11.8 media installation / removal
! WARNING
· Clean the glass media prior to installation. Before applying the cleaned
glass, ensure that it is dry. · If replacing, use only the replacement glass
media available from your local authorized dealer / distributor. · Glass media
over the burner ports may cause flame lifting and sooting problems. Adjust as
necessary. · Do not place any media (glass or vermiculite) in or around the
pilot opening and/or on the burner ports. This
will interfere with the pilot operation. Cleaning Glass Media Glass media may
have a fine oil residue that needs to be cleaned prior to installation. Clean
the glass with mild dish soap, drain, rinse thoroughly and dry before placing
over the burner.
note: Do not use more media than what was supplied with the appliance. Do not
place media directly onto the burner (NG models only).
Media should be installed across the burner tray and a small to moderate
amount of media placed on the burner itself and, if necessary, adjusted to
achieve a pleasing flame appearance. Never place excessive media on the burner
as this can result in carboning or an unappealing flame characteristic. For
smaller units, it is recommended not to put media on the burner ports
themselves as the difference in flame pattern can be particularly noticeable.
Never place media in the pilot housing or over the pilot. Ensure no glass or
media falls into the pilot opening. If this happens, insert a clean bag into
your vacuum cleaner and vacuum out the media. Replacement media can be
purchased from your local dealer / distributor. Always check that the
appliance ignites smoothly across the entire burner to ensure media placement
does not compromise performance. Pay particular attention when using power
vents to ensure media placement does not affect ignition or flame
characteristics. Adjust the air shutter according to the table under “venturi
adjustment”. Undesirable differences in the flame pattern result from
excessive or inconsistent / incorrect placement of media on the burner.
Pilot Area
Natural gas illustrated.
note: Do not place media directly over peaks, see “flame characteristics”
section for more information.
60
W415-4121 / D-0 / 05.22.24
11.9 adjusting the finishing trim
finishing EN
To adjust your finishing trim, loosen the 4 screws and pull outward. Re- tighten the screws once desired depth has been achieved (see below).
W415-4121 / D-0 / 05.22.24
61
EN 1a2d.j0usatmdjeunsttsments
12.1 restricting vertical vents
Vertical installations may display a very active flame. If this appearance is
not desirable, the vent exit in the appliance must be restricted using a
restrictor vent kit. Refer to the “replacements” section of the owner’s manual
for the appropriate kit. This will reduce the velocity of the exhaust gases,
slowing down the flame pattern and creating a more traditional gentle flame
appearance. Specific instructions are included with the kit.
12.2 venturi adjustment
This appliance is equipped with an externally adjustable air shutter that is
not preset from factory. Any adjustments made to the shutter must be done with
the burner and all media installed into the appliance. It is important to
operate the appliance and verify that the air shutter is opened to the correct
amount to prevent either flame lifting or carbonizing. To open or close the
shutter, pull the rod away from the appliance or push the rod towards the
appliance respectively. Small adjustments on the shutter can have a drastic
effect on the flame appearance; it is recommended to adjust the shutter in
1/8″ increments.
Air Shutter Adjustment
OPEN
CLOSE
! WARNING
· Air shutter adjustment must be done by a qualified installer.
Regardless of air shutter location, closing the air shutter will cause a more
yellow flame, but can lead to carbonization. Opening the air shutter will
cause a more blue flame, but can cause flame lifting from the burner ports.
The flame may not appear yellow immediately, allow 15 to 30 minutes for the
flame colour to be established.
62
W415-4121 / D-0 / 05.22.24
12.3 pilot burner adjustment
adjustments EN
Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.
Check Pressure Readings: Inlet pressure can be checked by turning screw (A) counterclockwise 2 or 3 turns and then placing pressure gauge tubing over the test point. Gauge should read as described on the chart below. Check pressure with main burner operating on “HI”.
AB
Outlet pressure can be checked the same as above using screw (B). Gauge should read as described on the chart below. Check pressure with main burner operating on “HI”.
INSERT PILOT ASSEMBLY
After taking pressure readings, be sure to turn screws clockwise firmly to
reseal. Do not overtorque.
Leak test with a soap and water solution.
PILOT SCREW
Prior to pilot adjustment, ensure that the pilot assembly has not been painted. If overspray or painting of the pilot assembly has occurred remove the paint from the pilot assembly, or replace. Fine emery cloth or a synthetic scrub pad (such as Scotch-BriteTM) can be used to remove the paint from the pilot hood, electrode and flame sensor.
Natural Gas
Propane
Min. Inlet Gas Supply Pressure
4.5″ w.c. (11mb)
11″ w.c. (27mb)
Max. Inlet Gas Supply Pressure
*7″ w.c. (17mb)
13″ w.c. (32mb)
Manifold Pressure (Under Flow Conditions)
3.5″ w.c. (9mb)
10″ w.c. (25mb)
*Maximum inlet pressure not to exceed 13″
12.4 flame characteristics
It’s important to periodically perform a visual check of the pilot and burner
flames. Compare them to the illustration provided. If any flames appear
abnormal, call a service person.
3/8″ – 1/2″ (9.5mm – 12.7mm)
Flame must envelop upper
3/8″ to 1/2″ (12.7mm – 9.5mm) of
thermocouple
Peak
Valley
TLV50 (NG) Illustrated
W415-4121 / D-0 / 05.22.24
63
EN 1m3a.0intmenaainntceenance ! WARNING
· Turn off the gas and electrical power before servicing the appliance. · Appliance may be hot. Do not service until appliance has cooled. · Do not use abrasive cleaners on glass. · Do not paint the pilot assembly.
This appliance and its venting system (if equipped) should be inspected before
use and at least annually by a qualified service person. The following
suggested checks should be performed by a qualified technician. The appliance
area must be kept clear and free of combustible materials, gasoline, or other
flammable vapors and liquids. The flow of combustion and ventilation air must
not be obstructed.
note:
Caution: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. Verify proper
operation after servicing.
In order to properly clean the burner and pilot assembly, remove the logs, rocks and/or glass to ex-
pose both assemblies.
Keep the control compartment, media, burner, air shutter opening and the area surrounding the appli-
ance clean by vacuuming or brushing, at least once a year.
Check to see that all burner ports are burning. Clean out any of the ports which may not be burning
or are not burning properly.
Check to see that the pilot flame is large enough to engulf the flame sensor and/or thermocouple /
thermopile as well as it reaches the burner.
If your appliance is equipped with a safety barrier, cleaning may be necessary due to excessive lint /
dust from carpeting, pets, etc. simply vacuum using the brush attachment.
If your appliance is equipped with relief doors, ensure the system performs effectively. Check that the
gasket is not worn or damaged. Replace if necessary.
Reinstall the cleaned logs, rocks or glass. Failure to properly position the media may cause carboning
which can be distributed in the surrounding living area, inside the firebox and on exterior surfaces sur-
rounding vent termination.
Check to see that the main burner ignites completely on all ports when turned on. A 5 to 10 second
total light-up period is satisfactory. If ignition takes longer, consult your local authorized dealer / dis-
tributor.
Visually inspect the appliance for carbon build up. Using a small whisk or brush, brush off the carbon
and vacuum up or sweep into garbage.
10. This step is not applicable for Vent Free appliances: Check to see that the appliance is venting correctly. Ensure chimney system is safe and unobstructed. (If for any reason the vent air intake system is disassembled, re-install and re-seal per the instructions provided for the initial installation).
64
W415-4121 / D-0 / 05.22.24
13.1 annual maintenance
! WARNING
maintenance EN
· Annual maintenance should be performed by a qualified service technician ·
The firebox becomes very hot during operation. Let the appliance cool
completely or wear heat resistant
gloves before conducting service. · Never vacuum hot embers. · Do not paint
the pilot assembly
· This appliance will require maintenance which should be planned on an annual
basis. · Service should include cleaning, battery replacement, venting
inspection and inspection of the burner,
media, and firebox. Refer to the door removal section and remove the door as
instructed. · Carefully remove media if necessary (logs, glass, brick panels,
etc.). · Using a vacuum with soft brush attachment, gently remove any dirt,
debris, or carbon build up from the
logs, firebox, and burner. For glass media, follow the installation
instructions for pre-cleaning. · Gently remove any build-up on the pilot
assembly including thermopile, thermocouple, flame sensor, and
igniter (if equipped). note: Clean flame sensor using a fine emery cloth or a
synthetic scrub pad (such as Scotch-BriteTM) to remove any oxides. Clean the
pilot assembly using a vacuum with a soft brush attachment. It is important
that the pilot assembly is not painted.
· Inspect all accessible gaskets and replace as required. · If equipped with a
blower, access the blower and clean using a soft brush and vacuum. · Re-
assemble the various components in reverse order. · Inspect the relief system.
The appliance relieves through the main glass door or through the flaps on the
firebox top. Ensure they open freely, and close sealed. · Check the gas
control valve pilot and Hi / Lo knobs move freely, if equipped. Replace if any
stiffness in
movement is experienced. · Check for gas leaks on all gas connections up and
downstream from the gas valve including pilot tube
connections.
13.2 control access
Access to the control can be done through the firebox by removing the safety
screen, glass door and front trim.
VALVE
CONTROL MODULE
APRCEC-EFSINSISPHAINNEGL
ELECTRICAL BOX
W415-4121 / D-0 / 05.22.24
65
EN maintenance
13.3 burner removal
A.
Remove the safety screen and glass door, refer to the “safety barrier installation / removal” and “door
installation / removal” sections for details.
B.
Remove the media from the appliance.
C.
Remove media tray screws as shown, lift out the burner, mesh and frame (one assembly).
D.
Disconnect the air shutter.
13.4 valve removal
A.
Remove the safety screen and glass door, refer to the “safety barrier installation / removal” and “door
installation / removal” sections for details.
B.
Disconnect the flex connector from the valve. Remove the valve wire connections, labeling each one to
aid with re-connection.
C.
Remove the screws from the valve bracket and remove the valve.
D.
Replace all components before returning the appliance to service.
E.
Check for gas leaks by brushing on a soap and water solution.
66
W415-4121 / D-0 / 05.22.24
13.5 control module removal
maintenance EN
A.
Remove the safety barrier and glass door, refer to the “safety barrier installation / removal” and “door
installation / removal” sections for details.
B.
Remove the two screws holding the control module in place, unplug and remove.
C.
Ensure to identify the wires plugged into the control module. It is critical that wire are reconnected to
the appropriate connectors.
D.
Replace and reinstall components.
CONTROL MODULE
W415-4121 / D-0 / 05.22.24
67
EN maintenance
13.6 LED replacement
This appliance comes equipped with an LED strip. If in the event the LED strip
needs to be replaced, follow these instructions.
A.
Turn off all electrical supply.
B.
Remove the safety screen and glass door, refer to the “safety barrier installation / removal” and “door
installation / removal” sections for details.
C.
Remove the media tray and burner assembly, refer to the “burner removal” section for details.
D.
Unplug the LED strip from the control module.
E.
Remove the LED glass by removing the screws securing the LED frame in place, then lift it up and out of
the appliance.
F.
Remove the LED strip by removing the four securing screws, replace and reinstall components.
68
W415-4121 / D-0 / 05.22.24
LED FRAME LED GLASS LED GASKET LED STRIP
TLV50 Illustrated
13.7 glass / door replacement
maintenance EN
! WARNING
· Do not use substitute materials. · Glass may be hot. Do not touch glass
until cooled. · Care must be taken when removing and disposing of any broken
door glass or damaged components. Be
sure to vacuum up any broken glass from inside appliance before operation. ·
Do not strike, slam, or scratch. Do not operate appliance with glass removed,
cracked, broken, or scratched.
Replacement glass/frame assembly shall be replaced as a complete unit as
supplied by the appliance manufacturer.
13.8 care of glass
! WARNING
· Do not clean glass when hot! Do not use abrasive cleaners to clean glass.
Buff lightly with a clean dry soft cloth to remove accumulated dust or
fingerprints. Clean both sides of the glass after the first 4 hours of
operation with an ammonia-free glass cleaner.
note: Vinegar-based glass cleaners have demonstrated an ability to provide a
clean, streak free glass surface.
Thereafter, clean as required. If the glass is not kept clean permanent
discoloration and / or blemishes may result. Contact your local authorized
dealer / distributor for complete cleaning instructions. Razor blades, steel
wool, or other metallic objects must not be used on both surfaces of the
glass. Doing so can remove a thin layer of metal from the razor blades, steel
wool, or other metallic objects that may then be deposited onto the coating.
This can result in a discoloured stain or scratch-like mark. More importantly,
this can scratch the glass surface, thereby reducing its strength. Do not
operate the appliance with broken glass, as leakage of flue gases may result.
Contact your local authorized dealer / distributor for complete cleaning
instructions. If the glass should ever crack or break while the fire is
burning, do not open the door until the fire is out. Do not operate the
appliance until the glass has been replaced. Contact you local authorized
dealer / distributor for replacement parts. DO NOT SUBSTITUTE MATERIALS.
13.9 care of plated parts
If the appliance is equipped with plated parts, you must clean fingerprints or
other marks from the plated surfaces before operating the appliance for the
first time. Use an ammonia-free or vinegar-based cleaner and a towel to clean.
If not cleaned properly before operating for the first time, the marks can
cause permanent blemishes on the plating. After the plating is cured, the
fingerprints and oils will not affect the finish and little maintenance is
required, just wipe clean as needed. Prolonged high temperature burning with
the door ajar may cause discolouration on plated parts.
note: The protective wrap on plated parts is best removed when the assembly is
at room temperature but this can be improved if the assembly is warmed (i.e.
using a hair dryer or similar heat source).
This appliance is factory equipped with 5mm ceramic glass. Use only
replacement parts as supplied by the appliance manufacturer. DO NOT SUBSTITUTE
MATERIALS
W415-4121 / D-0 / 05.22.24
69
EN 1re4p.0larceepmlaecnetms ent parts ! WARNING
· Failure to position the parts in accordance with this manual or failure to
use only parts specifically approved with this appliance may result in
property damage or personal injury.
Contact your dealer for questions concerning prices and policies on
replacement parts. Normally, all parts can be ordered through your Authorized
dealer / distributor.
For warranty replacement parts, a photocopy of the original invoice will be
required to honour the claim. When ordering replacement parts always give the
following information: · Model & Serial Number of appliance · Installation
date of appliance · Part number · Description of part · Finish Parts, part
numbers, and availability are subject to change without notice. Parts
identified as stocked will be delivered within 2 to 5 business days for most
delivery destinations. Parts not identified as stocked will be delivered
within a 2 to 4 week period, for most cases. Parts identified as `SO’ are
special order and can take up to 90 days for delivery.
70
W415-4121 / D-0 / 05.22.24
14.1 overview
SAFETY SCREEN
1
2
replacement parts EN
3
4
5
67
8
9
10
11
Items may not appear exactly as illustrated
REF.#
Description
Part Number
Stocked
TLV50
TLV62
TLV74
1 Safety Screen (Premium)
W565-0351-SER
W565-0352-SER
W565-0353-SER
2 Safety Barrier
W010-6179-SER
W010-6180-SER
W010-6181-SER
Yes
3 Fixed Door Assembly
W010-6163-SER
W010-6168-SER
W010-6176-SER
Yes
4 Door Trim
W715-1144-SER
W715-1124-SER
W715-1123-SER
5 Door Latch Assembly
W010-3554
6* High Limit Switch
W660-0204
7 Napoleon Logo
W385-2010
Yes
8 Porcelain End Panel
W475-7883-BK2GL
9 Porcelain Panel (Rear)
W475-7886-BK2GL-SER W475-7887-BK2GL-SER W475-7888-BK2GL-SER
10 Finishing Trim, Top/Bottom W715-1307-BK1FT
W715-1308-BK1FT
W715-1309-BK1FT
11** Finishing Trim, Sides
W715-1306-BK1FT
- When your appliance is equipped with the optional Ducted Heat Management SystemTM. ** Parts not illustrated.
W415-4121 / D-0 / 05.22.24
71
EN replacement parts
14.2 burner components
1
2
3
45
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Items may not appear exactly as illustrated
72
W415-4121 / D-0 / 05.22.24
replacement parts EN
Ref.
Description
1 Flex Connector (c/w Shut-Off)
2
Valve (NG)
3
Control Board
4 Control Board Wiring Harness
5
Battery Holder (w/ switch)
6
3 Prong Light Pigtail
7
LED Light Assembly
8
LED Glass Assembly
9
LED Cover
10
Burner Assembly (NG)
Burner Orifice (NG) 11
Burner Orifice (P)
12
Media Tray Assembly
13
Manifold (Flex)
Pilot Assembly (NG) 14
Pilot Assembly (P)***
15
Pilot Housing
16
PF2 Wire Harness
17
Media Cover Assembly
18
Connector
19
Transformer
20
LED Wire (Black)
21
LED Wire (White)
22
LED Aux Wire
23
LED Controller
24
Bluetooth Wire Harness
25
Light, Accent (c/w gasket)
26
Terminal
27
Transformer (Night Light)
28
Bluetooth Module
29
Power Cord
30
Pilot Cap
Part Number
TLV50
TLV62
TLV74
W175-0217
W175-0841
W725-0056
W190-0177
W750-0276
W350-0655
W750-0358
W010-3652-SER
W010-4079-SER
W010-4078-SER
W010-3714-SER
W010-4071-SER
W010-4070-SER
W200-0499-SER
W200-0653-SER
W200-0652-SER
W100-0332-SER
W100-0333-SER
W100-0335-SER
W456-0034
W456-0030
W456-0030
W456-0052
W456-0050
W456-0049
W010-6165-SER
W010-6167-SER
W010-6175-SER
W432-0533
W010-4895
W010-4896
W585-1024
W750-0276
W010-6166-SER
W445-0038
W707-0019
W750-0432
W750-0433
W750-0401
W750-0430
W750-0401
W750-0434
W190-0125
W750-0435
W405-0096-SER
N/A
W060-0008
W707-0019
W707-0027
W190-0090
W750-0294
W120-0115
Stocked Yes Yes Yes Yes Yes Yes
Yes
Yes Yes Yes Yes Yes
Yes Yes Yes
W415-4121 / D-0 / 05.22.24
73
EN 1tr5o.u0btlreosuhboleostihnogoting ! WARNING
· Always light the pilot whether for the first time or if the gas supply has
run out, with the glass door open or removed.
· Turn off gas and electrical power before servicing the appliance. ·
Appliance may be hot. Do not service until appliance has cooled. · Do not use
abrasive cleaners
symptom
problem
test solution
Main burner flame is a blue, lazy, transparent flame.
(This is not applicable in outdoor appliances)
Blockage in vent. Incorrect installation.
– Remove blockage. In really cold conditions, ice buildup may occur on the
terminal and should be removed as required. (To minimize this from reoccuring,
the vent lengths that pass through unheated spaces (attics, garages, crawl
spaces) should be wrapped with an insulated mylar sleeve).
– Refer to “venting” section to ensure correct installation.
Flames are consistently Appliance is over-fired or under- – Check pressure readings:
too large or too small.
fired.
Inlet pressure can be checked by turning screw (A) counter-clock-
Carboning occurs.
wise 2 or 3 turns and then placing pressure gauge tubing over the
test point. Gauge should read as described on the chart below.
Check that main burner is operating on `HI’. Outlet pressure can be
checked the same as above using screw (B). Gauge should read as
INSERT
described on the chart below. Check that main burner is operating on `HI’. After taking pressure readings, be sure to turn screws
PHOTO OF VALVE
Pressure
clockwise firmly to reseal. DO NOT OVER TORQUE. Leak test with a soap and water solution.
Natural Gas (inches)
NaAtural GaBs
(millibars)
Propane (inches)
Propane (millibars)
HERE
Inlet
*7″
17.4mb
13″
32.4mb
(minimum 4.5″) (minimum 11.2mb) (minimum 11″) (minimum 27.4mb)
Outlet
3.5″
8.7mb
10″
24.9mb
*Maximum inlet pressure not to exceed 13″ w.c.
PILOT SCREW
Carbon is being deposited on glass, logs, rocks, media, or combustion chamber
surfaces.
White / grey film forms.
Exhaust fumes smelled in room, headaches.
Air shutter improperly adjusted. –
Air shutter is blocked.
–
Flame is impinging on the glass, –
logs, rocks, media or combus-
–
tion chamber.
–
–
Sulphur from fuel is being depos- –
ited on glass, logs, or combus-
tion chamber surfaces.
–
Appliance is spilling.
–
(This is not applicable in outdoor –
appliances).
–
–
Return air shutter to specified opening, see “venturi adjustments” section in
the installation manual.
Ensure air shutter opening is free of lint or other obstructions.
Ensure the media is positioned correctly in the appliance. Open air shutter to
increase the primary air. Check the input rate: check the manifold pressure
and orifice size as specified by the rating plate. Ensure door gaskets are not
broken or missing and the seal is tight. Ensure vent liners are free of holes
and w
References
- Napoleon® Canada | Barbecue Grills, Fireplaces, Heating & Cooling
- eFire Bluetooth Control | Napoleon
- Manufacturer & Distributor of Chimney & Venting | Bernard Dalsin Manufacturing
- Duravent
- Metal-Fab Residential Commercial Venting Products
- Napoleon® Canada | Barbecue Grills, Fireplaces, Heating & Cooling
- Pilot on Demand | Napoleon
- National Fireplace Institute (NFI) – The national certification division of the Hearth, Patio & Barbecue Education Foundation (HPBEF)
- Olympia Chimney – Distributed through Copperfield
- P65Warnings.ca.gov
- Selkirk
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>