SAMSUNG AE140BXYDGG Eco Heat Pumps User Manual
- June 16, 2024
- Samsung
Table of Contents
SAMSUNG AE140BXYDGG Eco Heat Pumps
Mechanical Schematic
Pre-plumbed cylinder
Pumps
With Samsung heat pump we sell Grudnfos OEM pumps as the primary pumps. These pumps take an external speed control signal from the Samsung board to optimise pump flow rate for heat pump performance
Grundfos UPM4 5 & 8kW
The Grundfos UPM4 pumps we sell have a 60W motor and 7.5m nominal head. When
you’re using a buffer they are good for 5 and 8kW heat pumps. They will be
powerful enough for some direct systems, but you need to carry out some
calculations to be sure.
Grundfos UPM4XL 12kW
The Grundfos UPM4L pumps we sell have a 60W motor and 9m nominal head. When
you’re using a buffer they are good for 5 and 8kW heat pumps and often for
12kW heat pumps with shorter pipe runs. They will be powerful enough for some
direct systems with volumisers and bypass valves, but you need to carry out
some calculations to be sure.
Wilo Yonos PICO 25/1-8 – 180 long
Secondary Pump
The Wilo Yonos PICO has a 60W motor. It is perfect as a secondary pump for
moving water around your heating system. Secondary pumps are only required
when there is a buffer vessel or header.
Additional Components
IntaKlean
An IntaKlean is a filtration system that keeps the heat pump safe from any
debris. The intention is that you install them as close as possible to one
another so the minimum amount of fluid is lost when you clear out the
strainer. This can also be replaced with a strainer if desired.
Expansion Vessel
The 18 litre expansion vessel covers you for the vast majority of heating
systems. A sealed system kit can be used on a pre-plumbed if desired to get a
slimline expansion vessel.
Safety Relief Valve
This valve attaches to the expansion vessel to allow pressure release. It
comes with a gauge to show the pressure in the expansion vessel.
Flush-fill valve
We supply a flush-fill valve in the kit to make it easier to flush, fill and
drain the system, it needs to be installed on the primary pipework. Best not
to flush through the heat pump though – make a U-loop of pipe to put in the
system in place of the heat pump or install a flushing bypass before the heat
pump isolation valves.
Red and blue valves
A red and blue valve are each connected to the hoses going into the heat pump,
this allows the flow into and out of the heat pump to be locked off. The
colour denotes whether it is the hot or cold feed.
Main Power Diagram
Wiring Diagram
Set the time
Where you go to set the time on the controller is: User Mode then Wired remote
controller then you can set the Current Time.
Accessing service mode
To get into service mode for testing and setting up the heat pump you need to
press and hold up and down for 5 seconds. The controller will then ask you to
enter the PIN which is 0 2 0 2
Check the flow-rate
Enter Service Mode, go to Indoor Zone Option then Indoor Zone Status
Information and it will show a value for flow sensor in litres per minute.
Samsung Thermostat
The heat pump control is a bit more clever when you use the Samsung controller as the thermostat. This is the ideal option if you can find a route for the cable to a sensible thermostat location. To use the Samsung LCD controller as the thermostat enter service mode and go to:
Indoor Zone Option
and set
Standard Temperature to Indoor
Now the controller is set up to act as the thermostat with the temperature
setting via the Samsung LCD.
External Thermostat
If you need to use an external, 3rd party thermostat with a Samsung heat pump
this needs to be wired up as shown below. Permanent live is B20, switched live
is B22.
Then set the heat pump to use it as the signal to heat or not by setting FSV 2091 – External Thermostat Application #1 (Floor) to Use(Signal ON/OFF) or WL Interlink OFF(Water Pump3).
Heating – Weather Compensation
Samsung’s name for weather compensation is “water law”. You need to set up the water law before the heat pump will perform weather compensation properly. On a Samsung, you set a warm weather point and a cold weather point and then the unit interpolates between them to provide the flow temperature asked for. To do this you need to enter service mode, “Field Setting Value” and input the settings.
Note: the two numbers inside the green boxes are the design condition, in this case shown as flow temp of 45°C at air temp of -3°C but you should use the temperatures you have designed to.
Hot water settings (FSV)
- 3011 – Domestic Hot Water Tank – Use(Hysteresis Thermo ON/OFF state)
- 3025 – Max DHW Operation Time – you want to give your heat pump a decent chance of heating the water up in one go here, but not let the house get cold while you do it. If it’s a well-insulated house you can set this time fairly long, if it’s a poorly insulated house you can set it shorter. 90 minutes is a reasonable starting point for most cases. 3032 – Delay time – This is how long the heat pump tries to do the hot water using the heat pump before it kicks in the immersion heater to help. You don’t want this to happen often so set this to 60 minutes.
- 3042 – This is the day that the legionella cycle happens. The best idea is to set it mid-week probably Tuesday or Wednesday.
- 3043 – Legionella start time – Set this to a time when the water should already be hot anyway to minimise the energy used for this cycle, maybe 4am.
- 3044 – Target temp – This is how hot the heat pump goes in the legionella cycle – 60°C is a good setpoint normally. If the occupants are older you might want to go for 65°C to be extra safe.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>