Panasonic S-180ME2E5 E2 Type High Static Ducted Owner’s Manual

June 12, 2024
Panasonic

Indoor Unit / E2 Type
E2 TYPE
High Static Ducted Concealed duct / Air conditioning mode

S-180ME2E5 E2 Type High Static Ducted

High static and large airflow ducted for exceptional installation flexibility.

S-180ME2E5 / S-224ME2E5 / S-280ME2E5

Optional accessory

| Self-diagnosis Function
---|---
| Automatic Fan Operation
| Dry mode
| Automatic Restart Function

Technical focus

  • Design flexibility thanks to high static pressure and large air volume
  • DC motor equipped
  • Power input 45% less (compared to E1 type)
  • Discharge air temperature control to reduce cold drafts during heating operation
  • Configurable air temperature control
  • Available Fresh Air Intake mode (See page 80-81)

3-step static pressure set up
You can select between the three Static Pressure modes of 270 Pa/140 Pa/60(72*) Pa for extra installation flexibility.

Max. 270 Pa static pressure setting
A maximum static pressure setting of a high 270 Pa enables the use of long ducts for installation in a wide range of spaces. Ideal for large-scale offices, restaurants and other facilities.

Sensible cooling 5-10% improved
New heat exchanger with Ø7mm pipe that increases the heat transfer surface to improve sensible cooling (5-10% improvement)

No Rap Valve Kit required
Thanks to improved performance, a Rap Valve Kit (CZ-P160RVK2) is no longer required.

Discharge air temperature control

  • Equipped with 4 sensors (Intake/ Discharge)
  • Able to control discharge air temperature for accurate room temperature control.
  • Possible to reduce cold drafts during heating operation.
Model Name S-180ME2E5 S-224ME2E5 S-280ME2E5
Power source 220/230/240 V, 1 phase – 50 Hz, 220/230 V, 1 phase – 60 Hz
Cooling capacity kW 18.0 22.4
BTU/h 61,400 76,400 95,500
Heating capacity kW 20.0 25.0
BTU/h 68,200 85,300 107,500
Power input Cooling kW 0.400
Heating kW 0.400 0.440
Running current Cooling A 2.40/2.30/2.20
Heating A 2.40/2.30/2.20 2.55/2.45/2.35
Fan Type Sirocco fan Sirocco fan
Air flow rate (H/M/L) m³/h 2,940/2,640/2,340 3,360/3,060/2,640

4,320/3,780/3,180
L/s| 817/733/650| 933/850/733| 1,200/1,050/883
Motor output| kW| 0.560 x 2| 0.560 x 2| 0.750 x 2
External static pressure| Pa| 140 (60/270)| 140 (60/270)| 140 (72/270)
Sound power level (H/M/L)| dB| 76/74/72| 77/75/73| 81/79/75
Sound pressure level (H/M/L)| dB(A)| 44/42/40| 45/43/41| 49/47/43
Dimensions        H x W x D| mm| 479 x 1,453 x 1,205| 479 x 1,453 x 1,205| 479 x 1,453 x 1,205
Pipe connections| Liquid| inches (mm)| Ø9.52 (3/8)| Ø9.52 (3/8)| Ø9.52 (3/8)
Gas| inches (mm)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø22.22 (7/8)
Drain piping| VP-25| VP-25| VP-25
Net weight| kg| 102| 102| 106
GLOBAL REMARKS| Rated conditions:| Cooling| Heating
---|---|---|---
Indoor air temperature
Outdoor air temperature| 27˚C DB / 19˚C WB
35˚C DB / 24˚C WB| 20˚C DB
7˚C DB / 6˚C WB

E2 TYPE HIGH STATIC DUCTED Dimensions

  1. Refrigerant piping (liquid pipes) Ø9.52
  2. Refrigerant piping (gas pipes) 180 & 224 type: Ø19.05, 280 type: Ø22.22
  3. Power supply outlet (Ø25 grommet, rubber)
  4. Power supply outlet (spare) (Ø30 knock-out)
  5. Optional outlet for piping
  6. Drain port 25 A, male thread
  7. Duct connection for suction
  8. Duct connection for discharge

E2 TYPE
Energy Saving
High Fresh Air Ducted

Concealed duct high-static pressure
High static and large airflow ducted for exceptional installation flexibility.

S-224ME2E5 / S-280ME2E5

Optional accessory

| Self-diagnosis Function
---|---
| Automatic Fan Operation
| Automatic Restart Function

Technical focus

  • 100% fresh air intake for ventilation purpose
  • Design flexibility with high static pressure and large air volume
  • DC motor equipped
  • Power input 45% less (compared to H1 type)
  • Discharge air temperature control to reduce cold drafts during heating operation
  • Configurable air temperature control

High Fresh System

High Fresh System enables delivery of fresh outside air at almost the same temperature and humidity as indoor air without putting a burden on air conditioning.

  • Capable of treating outdoor air only. Indoor air conditioner units are required to adjust indoor air temperature.

Mix operation unit with standard indoor units
Possible to combine High Fresh Air ducted indoor unit and standard air ducted indoor units.
When other indoor units are connected in same circuit, keep following capacity ratio.
E2 type/Outdoor unit < 30%, and Total of indoors(incl. E2)/outdoor <100%

Discharge air temperature control

  • Equipped with 4 sensors (Intake/ Discharge)
  • Able to control discharge air temperature for accurate room temperature control.
  • Possible to reduce cold drafts during heating operation.

Remark For High Static Ducted Series

Model Name S-224ME2E5 S-280ME2E5
Power source 220/230/240 V, 1 phase – 50 Hz, 220/230 V, 1 phase – 60 Hz
Cooling capacity kW 22.4
BTU/h 76,400 95,500
Heating capacity kW 21.2
BTU/h 72,300 90,400
Power input Cooling kW
Heating kW 0.290
Running current Cooling A
Heating A 1.90/1.85/1.80
Fan Type Sirocco fan
Air flow rate m³/h 1,700
L/s 472 583
Motor output kW 0.560 x 2
External static pressure Pa 200
Sound power level dB 75
Sound pressure level dB(A) 43
Dimensions        H x W x D mm 479 x 1,453 x 1,205
Pipe connections Liquid inches (mm)
Gas inches (mm) Ø19.05 (Ø3/4)
Drain piping VP-25 VP-25
Net weight kg 102

GLOBAL
REMARKS| Rated conditions:| Cooling| Heating
---|---|---|---
Outdoor air temperature| 33˚C DB / 28˚C WB| 0˚C DB / -2.9˚C WB

Specifications are subject to change without notice.

E2 TYPE HIGH STATIC DUCTED Dimensions

  1. Refrigerant piping (liquid pipes) Ø9.52
  2. Refrigerant piping (gas pipes) 224 type: Ø19.05, 280 type: Ø22.22
  3. Power supply outlet (Ø25 grommet, rubber)
  4. Power supply outlet (spare) (Ø30 knock-out)
  5. Optional outlet for piping
  6. Drain port 25 A, male thread
  7. Duct connection for suction
  8. Duct connection for discharge