Intesis Modbus Server for Hisense Air Conditioning Gateway integration of VRF Systems User Manual
- June 8, 2024
- Intesis
Table of Contents
- 1.1Introduction
- Integration of Hisense’s compatible systems into Modbus systems
- 1.1 Functionality
- 1.2 Capacity of Intesis
- 2. Modbus interface
- 1.3 Functions supported
- 1.4 Modbus RTU
- 1.5 Modbus TCP
- 1.6 Modbus Address Map
- IntesisTM Modbus Server – HISENSE VRF
- IntesisTM Modbus Server – HISENSE VRF
- IntesisTM Modbus Server – HISENSE VRF
- 3. Connections
- IntesisTM Modbus Server – HISENSE VRF
- 1.7 Power device
- 1.8 Connect to Hisense VRF installation
- 4. Set-up process and troubleshooting
- 1.11 Pre-requisites
- IntesisTM Modbus Server – HISENSE VRF
- IntesisTM Modbus Server – HISENSE VRF
- Figure 4.4 Intesis MAPS Hisense configuration tab
- IntesisTM Modbus Server – HISENSE VRF
- Figure 4.8 Intesis MAPS Signals tab
- IntesisTM Modbus Server – HISENSE VRF
- IntesisTM Modbus Server – HISENSE VRF
- IntesisTM Modbus Server – HISENSE VRF
- IntesisTM Modbus Server – HISENSE VRF
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Hisense Air Conditioning Gateway for the integration of Hisense VRF systems into Modbus (RTU and TCP) systems
USER MANUAL
Issue date: 11/2018 r1.0 ENGLISH
Important User Information Disclaimer
The information in this document is for informational purposes only. Please
inform HMS Industrial Networks of any inaccuracies or omissions found in this
document. HMS Industrial Networks disclaims any responsibility or liability
for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with
its policy of continuous product development. The information in this document
shall therefore not be construed as a commitment on the part of HMS Industrial
Networks and is subject to change without notice. HMS Industrial Networks
makes no commitment to update or keep current the information in this
document.
The data, examples and illustrations found in this document are included for
illustrative purposes and are only intended to help improve understanding of
the functionality and handling of the product. In view of the wide range of
possible applications of the product, and because of the many variables and
requirements associated with any particular implementation, HMS Industrial
Networks cannot assume responsibility or liability for actual use based on the
data, examples or illustrations included in this document nor for any damages
incurred during installation of the product. Those responsible for the use of
the product must acquire sufficient knowledge in order to ensure that the
product is used correctly in their specific application and that the
application meets all performance and safety requirements including any
applicable laws, regulations, codes and standards. Further, HMS Industrial
Networks will under no circumstances assume liability or responsibility for
any problems that may arise as a result from the use of undocumented features
or functional side effects found outside the documented scope of the product.
The effects caused by any direct or indirect use of such aspects of the
product are undefined and may include e.g. compatibility issues and stability
issues.
Gateway for the integration of Hisense VRF systems into Modbus (RTU and TCP) systems.
1.1Introduction
This document describes the integration of Hisense VRF air conditioning
systems into Modbus compatible devices and systems using using gateway the
Intesis Modbus Server to Hisense VRF communication gateway.
The aim of this integration is to monitor and control Hisense air conditioning
systems, remotely, from a Control Center using any commercial SCADA or
monitoring software that includes a Modbus Master driver (RTU and/or TCP). To
do it so, Intesis performs as a Modbus Server, allowing poll and write
requests from any Modbus master device.
Intesis makes available the Hisense air conditioning system indoor units’
datapoints through independent Modbus registers.
Up to 64 indoor units supported, depending on product version.
This document assumes that the user is familiar with Modbus and Hisense
technologies and their technical terms.
Integration of
Integration of Hisense’s compatible systems into Modbus systems
1.1 Functionality
IntesisTM continuously monitors Hisense VRF network for all configured signals
and keeps the updated status of all of them in its memory, ready to be served
when requested from the Modbus master.
Commands toward the indoor units are permitted.
Each indoor unit is offered as a set of MBS objects.
1.2 Capacity of Intesis
Element | Max. | Notes |
---|---|---|
Number of indoor units | 64 * | Number of indoor units that can be |
controlled through Intesis
- There are different models of Intesis MBS – Hisense VRF each one with different capacity. The table above shows the capacity for the top model (with maximum capacity).
Their order codes are:
▪ INMBSHIS016O000: Model supporting up to 16 indoor units
▪ INMBSHIS064O000: Model supporting up to 64 indoor units
2. Modbus interface
In this section, a common description for all Intesis Modbus series gateways is given, from the point of view of Modbus system which is called from now on internal system. Connection with the Hisense VRF system is also called from now on external system.
1.3 Functions supported
This part is common for Modbus RTU and TCP.
Modbus functions 03 and 04 (Read Holding Registers and Read Input Registers)
can be used to read Modbus registers.
Modbus functions 06 and 16 (Single Multiple Holding Registers and Write
Multiple Holding Registers) can be used to write Modbus registers.
Configuration of poll records is possible between Modbus addresses 0 and
20000. Addresses that are not defined in section 2.2 (Modbus map of the
device) are read-only and will always report 0.
Modbus error codes are supported, they will be sent whenever a non-valid
Modbus address is queried.
All registers are 16-bit signed integer, in standard Modbus Big Endian
(MSB/LSB) format.
Intesis supports Modbus RTU and Modbus TCP and both interfaces can be used
simultaneously.
1.4 Modbus RTU
Both EIA485 and EIA232 physical layers are supported. Only the lines RX, TX
and GND of the EIA232 connector are used (TX and RX for EIA485).
Baud rate can be selected between 1200, 2400, 4800, 9600, 19200, 38400, 56700
and 115200. Parity (none, even or odd) and stop bits (1 or 2) can be selected
as well. Modbus slave number must be configured and the physical connection
(RS232 or RS485) can also be selected
1.5 Modbus TCP
TCP port to use (default is 502) and keep alive period must be configured.
IP settings of Intesis (DHCP status, own IP, net mask and default gateway)
must be configured as well.
1.6 Modbus Address Map
Modbus address from the formula is expressed in link layer format. This is, first register address is 0.
© HMS Industrial Networks S.L.U – All rights reserved
This information is subject to change without notice
IntesisTM Modbus Server – HISENSE VRF
© HMS Industrial Networks S.L.U – All rights reserved
This information is subject to change without notice
IntesisTM Modbus Server – HISENSE VRF
IntesisTM Modbus Server – HISENSE VRF
3. Connections
Find below information regarding the Intesis connections available.
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied
is within the range admitted (check table below). The power supply can be
connected to earth but only through the negative terminal, never through the
positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not
connect any of the terminals of the AC power supply to earth, and make sure
the same power supply is not supplying any other device.
Ethernet / Modbus TCP (TCP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the
building, contact the network administrator and make sure traffic on the port
used is allowed through all the LAN path (check the gateway user manual for
more information). Default IP is 192.168.100.246. DHCP is enabled by default.
PortA / H-Link Hisense
Connect the H-Link terminals (TB2) of Hisense Outdoor Unit to the connectors
A3 and A4 of gateway’s PortA.
There is no polarity to be respected.
PortB / Modbus-RTU RS485
Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of
gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of
1200 meters, maximum 32 devices connected to the bus, and in each end of the
bus it must be a termination resistor of 120 Ω. Bus biasing and termination
resistor for EIA485 can be enabled for PortB by means of a dedicated DIP:
SW1:
ON: 120 Ω termination active
OFF: 120 Ω termination inactive (Default setting).
SW2+3:
ON: Polarization active
OFF: Polarization inactive (Default setting).
If the gateway is installed in one bus end, make sure that termination is active.
IntesisTM Modbus Server – HISENSE VRF
1.7 Power device
The first step to perform is to power up the device. To do so, a power supply working with any of the voltage range allowed is needed (check section 5). Once connected the ON led will turn on.
WARNING! In order to avoid earth loops that can damage the gateway, and/or any other equipment connected to it, we strongly recommend:
- The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a DC power supply with the positive terminal connected to earth.
- The use of AC power supplies only if they are floating and not powering any other device.
1.8 Connect to Hisense VRF installation
Use the PortA connector in the top corner of the Intesis device in order to
connect H-Link bus to the Intesis. Remember to follow all safety precautions
indicated by Hisense.
Connect the Hisense H-Link/TB2 bus to connectors A3 and A4 of gateway’s PortA.
Bus is not sensitive to polarity.
1.9 Connection to Modbus
1.9.1 Modbus TCP
The gateways Ethernet port connection is used for Modbus TCP communication.
Connect the communication cable coming from the network hub or switch to the
Ethernet port of Intesis. The cable to be used shall be a straight Ethernet
UTP/FTP CAT5 cable.
TCP port to use (default 502) and keep alive period must be configured.
IP settings of the gateway (DHCP status, own IP, netmask and default gateway)
must be configured as well.
1.9.2 Modbus RTU
Connect the communication cable coming from the motbus network to the port
marked as Port B of the Intesis. Connect the EIA485 bus to connectors B1 (-),
B2 (+) and B3 (SNGD) of gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of
1200 meters, maximum 32 devices (without repeaters) connected to the bus, and
in each end of the bus it must be a termination resistor of 120 Ω. The gateway
has an internal bus biasing circuit that incorporates the termination
resistor. Bus biasing and termination resistor for EIA485 can be enabled for
PortB by means of a dedicated DIP switch.
1.10 Connection to PC (Configuration tool)
This action allows the user to have access to configuration and monitoring of the device (more information can be found in the configuration tool User Manual). Two methods to connect to the PC can be used:
- Ethernet: Using the Ethernet port of Intesis.
- USB: Using the console port of Intesis, connect a USB cable from the console port to the PC.
4. Set-up process and troubleshooting
1.11 Pre-requisites
It is necessary to have the Modbus RTU or TCP master/client device (BMS side
device) operative and properly connected to the corresponding port of the
gateway and the Hisense VRF installation connected to their corresponding
ports as well.
Connectors, connection cables, PC for the Configuration Tool usage and other
auxiliary material, if needed, are not supplied by Intesis for this standard
integration.
Items supplied by HMS Networks for this integration are:
- Intesis gateway.
- Link to download the configuration tool.
- USB Console cable to communicate with Intesis.
- Product documentation.
1.12 Intesis MAPS. Configuration & monitoring tool for Intesis Modbus series
1.12.1 Introduction
Intesis MAPS is a Windows® compatible software developed specifically to
monitor and configure Intesis new generation gateways.
The installation procedure and main functions are explained in the Intesis
MAPS User Manual. This document can be downloaded from the link indicated in
the installation sheet supplied with the Intesis device or in the product
website at www.intesis.com
In this section, only the specific case of Hisense VRF to Modbus systems will
be covered. Please check the Intesis MAPS User Manual for specific information
about the different parameters and how to configure them.
1.12.2 Connection
To configure the Intesis connection parameters press on the Connection button
in the menu bar.
Figure 4.1 MAPS connection
IntesisTM Modbus Server – HISENSE VRF
1.12.3 Configuration tab
Select the Configuration tab to configure the connection parameters. Three
subsets of information are shown in this window: General (Gateway general
parameters), Modbus Slave (Modbus interface configuration) and Hisense
(Hisense interface parameters).
Figure 4.2 Intesis MAPS configuration tab
1.12.4 Modbus Slave configuration
Set parameters of Modbus Slave interface of Intesis.
IntesisTM Modbus Server – HISENSE VRF
Figure 4.3 Intesis MAPS Modbus configuration tab
-
Modbus Configuration
1.1. Modbus type selection. Select RTU, TCP or simultaneous RTU and TCP communication. -
TCP Configuration.
2.1. Modbus TCP Port: Modbus TCP communication port setting. Default port 502.
2.2. Keep Alive. Set the time of inactivity to send a keep Alive message. Default 10 minutes. -
RTU Configuration.
3.1. RTU bus connection type. Select the RTU connection type serial bus RS485 or 232.
3.2 Baudrate. Set the RTU bus communication speed. Default: 9600 bps.
• Available values: 1200, 2400, 4800, 9600,19200, 38400, 57600, 115200 bps.
3.3 Data Type. Set the Data-bit/parity/stop-bit. Default: 8bit/None/1.
• Available selection: 8bit/None/1, 8bit/Even/1, 8bit/Odd/1, 8bit/None/2.
3.4 Slave Number. Set the Modbus Slave address. Default slave address: 1.
• Valid address: 1..255.
IntesisTM Modbus Server – HISENSE VRF
1.12.5 Hisense configuration
Set parameters for connection with Hisense’s installation.
Figure 4.4 Intesis MAPS Hisense configuration tab
In Units Configuration section you need to enter, for each unit:
- Active. If it’s active (checkbox at Unit xx), ranging from 1 to 64 indoor units that will be integrated (maximum number of units will depend on Intesis model)
- IU address. Address 1..64 of Unit in Hisense H-Link bus.
- OU address. Address 1..64 of Outdoor Unit in Hisense H-Link bus.
- Description. Descriptive name to easy identification of the unit (for example, ‘living room floor 1 unit’, etc).
Additional to manual entry of each unit, autodiscover of present units in an H-Link installation is possible. To do so, click button Scan. Following window will appear:
IntesisTM Modbus Server – HISENSE VRF
Figure 4.5 Intesis MAPS Scan Hisense Units window
By pressing Scan button, connected Hisense H-Link bus will be scanned for
available units. Error window will appear if there is a problem in the
connection with H-Link bus (units not powered, bus not connected, …).
A progress bar will appear during the scan, which will take up to a few
minutes. After scan is complected, detected units will be shown in available
units as follows:
Figure 4.6 Intesis MAPS Scan Hisense Units window with scan results
IntesisTM Modbus Server – HISENSE VRF
Select with its checkbox units to add (or replace) in installation, according
to selection Replace Units / Add Units.
After units to be integrated are selected, click button Apply, and changes
will appear in previous Units Configuration window.
Figure 4.7 Intesis MAPS Hisense configuration tab after importing scan results
1.12.6 Signals
All available Modbus registers, its corresponding description and other main
parmaters are listed in the signals tab.
Figure 4.8 Intesis MAPS Signals tab
1.12.7 Sending the configuration to Intesis
When the configuration is finished, follow the next steps.
- Save the project (Menu option Project->Save) on your hard disk (more information in Intesis MAPS User Manual).
- Go to tab ‘Receive / Send’ of MAPS, and in Send section, press Send button. Intesis will reboot automatically once the new configuration is loaded.
Figure 4.9 Intesis MAPS Receive/Send tab
After any configuration change, do not forget to send the configuration file to the Intesis using the Send button in the Receive / Send section.
1.12.8 Diagnostic
To help integrators in the commissioning tasks and troubleshooting, the
Configuration Tool offers some specific tools and viewers.
In order to start using the diagnostic tools, connection with the Gateway is
required.
The Diagnostic section is composed by two main parts: Tools and Viewers.
-
Tools
Use the tools section to check the current hardware status of the box, log communications into compressed files to be sent to the support, change the Diagnostic panels’ view or send commands to the gateway. -
Viewers
In order to check the current status, viewer for the Internal and External protocols are available. It is also available a generic Console viewer for general information about communications and the gateway status and finally a Signals Viewer to simulate the BMS behavior or to check the current values in the system.
IntesisTM Modbus Server – HISENSE VRF
More information about the Diagnostic section can be found in the Configuraion Tool manual.
1.12.9 Set-up procedure
-
Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by the Installation wizard.
-
Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
-
If using Modbus RTU, connect the communication cable coming from the EIA485 port of the Modbus RTU installation to the port marked as Port B of Intesis (More details in section 3).
If using, Modbus TCP, connect the communication cable coming from the Ethernet port of the Modbus TCP installation to the port marked as Ethernet Port of Intesis (More details in section 3). -
Connect the communication cable coming from the Hisense VRF installation to the port marked as Port A of Intesis (More details in section 3).
-
Power up Intesis. The supply voltage can be 9 to 36 Vdc or just 24 Vac. Take care of the polarity of the supply voltage applied.
WARNING! In order to avoid earth loops that can damage Intesis and/or any other equipment connected to it, we strongly recommend:
- The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a DC power supply with the positive terminal connected to earth.
- The use of AC power supplies only if they are floating and not powering any other device.
IntesisTM Modbus Server – HISENSE VRF
6. If you want to connect using IP, connect the Ethernet cable from the
laptop PC to the port marked as Ethernet of Intesis (More details in section
3).
If you want to connect using USB, connect the USB cable from the laptop PC to
the port marked as Console of Intesis (More details in section 3).
7. Open Intesis MAPS, create a new project selecting a copy of the one named
INMBSHIS—O000.
8. Modify the configuration as desired, save it and download the
configuration file to Intesis as explained in the Intesis MAPS user manual.
9. Visit the Diagnostic section, enable COMMS () and check that there is
communication activity, some TX frames and some other RX frames. This means
that the communication with the Centralized Controller and Modbus Master
devices is OK. In case there is no communication activity between Intesis and
the Centralized Controller and/or Modbus devices, check that those are
operative: check the baud rate, the communication cable used to connect all
devices and any other communication parameter.
Figure 4.11 Enable COMMS
5. Electrical & Mechanical Features
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 90x88x56 mm
Recommended space for installation (dxwxh): 130x100x100mm
Color: Light Grey. RAL 7035
Mounting
Wall.
DIN rail EN60715 TH35.
Terminal Wiring (for power supply and low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with ferrule)
- core: 0.5mm2… 2.5mm2
- cores: 0.5mm2… 1.5mm2
- cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
Power
1 x Plug-in screw terminal block (3 poles)
9 to 36VDC +/-10%, Max.: 140mA.
24VAC +/-10% 50-60Hz, Max.: 127mA
Recommended: 24VDC
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Port A
1 x H-Link Plug-in screw terminal block orange (2 poles)
1500VDC isolation from other ports
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Switch A
x DIP-Switch for PORTA configuration:
Reserved for future use (leave OFF, default)
PORT B
1 x Serial EIA232 (SUB-D9 male connector)
Pinout from a DTE device
1500VDC isolation from other ports
(except PORT B: EIA485)
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
(except PORT B: EIA232)
Switch B
1 x DIP-Switch for serial EIA485 configuration:
Position 1:
ON: 120 Ω termination active
Off: 120 Ω termination inactive (default)
Position 2-3:
ON: Polarization active
Off: Polarization inactive (default)
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Console Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Push Button
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Push Button
Button A: Not used
Button B: Not used
Operation Temperature
0°C to +60°C
Operational Humidity
to 95%, no condensation
Protection
IP20 (IEC60529)
LED Indicators
10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
6. Dimensions
Recommended available space for its installation into a cabinet (wall or DIN rail mounting), with space enough for external connections
7. AC Unit Types compatibility
A list of Hisense unit model references compatible with INMBSHIS—O000 and
their available features can be found in:
https://www.intesis.com/docs/compatibilities/inxxxhis001r000_compatibility
IntesisTM Modbus Server – HISENSE VRF
8. Error codes for Indoor and Outdoor Units
This list contains all possible values shown in Modbus register for “Error
Code” for each indoor unit and outdoor unit.
It must be taken into account that Outdoor Units are only able to reflect a
single error for each indoor / outdoor unit in the system. Thus, a unit having
two or more active errors from that list will only report a single error code
– the one of the first error that has been detected.
IntesisTM Modbus Server – HISENSE VRF
IntesisTM Modbus Server – HISENSE VRF
Read More About This Manual & Download PDF:
Intesis Modbus Server for Hisense Air Conditioning Gateway integration of VRF
Systems User Manual – Download [optimized]
Intesis Modbus Server for Hisense Air Conditioning Gateway integration of VRF
Systems User Manual – Download
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>