STEALTH SC-09W-HP230 PINNACLE Multi-Zone Series High Wall Ductless Air Conditioning and Heating System Instruction Manual
- June 4, 2024
- STEALTH
Table of Contents
- STEALTH SC-09W-HP230 PINNACLE Multi-Zone Series High Wall Ductless Air
- Installation Site Instructions
- SYSTEM REQUIREMENTS
- SUGGESTED TOOLS
- Installation Schematic
- INSTALLATION SITE INSTRUCTIONS
- INDOOR UNIT INSTALLATION
- Installation of Mounting Bracket
- INDOOR UNIT INSTALLATION
- PIPING INSTALLATION
- Refrigerant Piping
- How to Relocate Drain Hose from Left to Right Side if required
- Indoor Drain Piping
- POWER AND WIRING INSTALLATION
- Indoor Unit Wire Connections
- Indoor Disconnect Switch If required
- TESTING AND INSPECTION
- Pipe Testing
- Additional Charge
- Oil Return Bend
- Condensate Drain Pipe Testing
- Start up Checklist
- TROUBLESHOOTING
- DIAGNOSTIC CODE
- DIAGNOSTIC CODES
- CARE AND CLEANING
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
STEALTH SC-09W-HP230 PINNACLE Multi-Zone Series High Wall Ductless Air
Conditioning and Heating System
SAFETY PRECAUTIONS
This is the safety alert symbol. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and CAUTION. These words are
used with the safety alert symbol.
- DANGER identifies the most serious hazards which will result in severe personal injury or death.
- WARNING signifies hazards which could result in personal injury or death.
- CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage
- NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
This appliance is not intended for use by children without responsible
adult supervision. Proper care should be taken to ensure safety. Heat pumps,
air conditioners & heating equipment should be installed, started up, and
serviced only by qualified installers and service technicians. Air
conditioning, heat pump and refrigeration systems are hazardous due to high
voltage electrical components, high refrigerant pressures, and moving parts.
NOTE
Your actual air conditioning & heating system and related devices may differ
from the images.
CAUTION
The unit should be installed and serviced only by trained, qualified
installers and service technicians. Untrained personnel can perform basic
maintenance functions such as
cleaning coils. All other operations should be performed by trained service
personnel. Owner should be cautioned that children should not play with the
appliance.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, servicing or modifying the system, the main electrical
disconnect switch must be in the OFF position. There may be more than one
disconnect switch. Lock out and tag all switches with a warning label.
General Safety Precautions
- A dedicated power supply circuit should be used in accordance with local electrical safety regulations and National Electrical Codes (NEC).
- Ensure that the entire system is properly grounded.
- Use a properly sized circuit breaker to protect equipment against short circuit and overload conditions.
- The system must be positioned at least 5 feet from combustible surfaces.
- Observe all local codes and regulations.
Installation Site Instructions
A proper installation site is vital for correct and reliable operation of the system. Avoid the following installation location
- High heat sources, vapors, flammable gas or volatile liquids.
- High frequency electro-magnetic waves, generated by radio equipment, welders or medical equipment.
SYSTEM REQUIREMENTS
PIPE SIZE in (mm)
Unit Size BtuH | Voltage | Liquid Line | Suction/Gas Line |
---|
9,000
12,000
18,000
24,000
36,000
| 208/230v – 1ph 60hz 208/230v – 1ph 60hz 208/230v – 1ph 60hz 208/230v – 1ph 60hz 208/230v – 1ph 60hz| 1/4 (6)
1/4 (6)
1/4 (6)
1/4 (6)
1/4 (6)
| 3/8 (9.5)
1/2 (12)
5/8 (16)
5/8 (16)
5/8 (16)
REFRIGERANT LINE LENGTHS ft (m)
Unit Size BtuH| Voltage| Min Line Length| Pre-Charge Line Length| Max Line
Length| Max Elevation
---|---|---|---|---|---
9,000| 208/230v – 1ph 60hz| 10 (3)| 25 (7.5)| 50 (15)| 33 (10)
12,000| 208/230v – 1ph 60hz| 10 (3)| 25 (7.5)| 66 (20)| 33 (10)
18,000| 208/230v – 1ph 60hz| 10 (3)| 25 (7.5)| 82 (25)| 33 (10)
24,000| 208/230v – 1ph 60hz| 10 (3)| 25 (7.5)| 82 (25)| 33 (10)
36,000| 208/230v – 1ph 60hz| 10 (3)| 25 (7.5)| 98 (30)| 33 (10)
Main power wire from electrical panel to outdoor unit.
Notes
System must be on a single dedicated circuit.
- Main power is supplied to the outdoor unit.
- Use table above to size over current protection.
- Follow all local building codes and NEC (National Electrical Code) regulations.
- Interconnecting Cable: Recommended cable – 14/4 AWG stranded bare copper conductors THHN 600V unshielded wire
Note
Use shield cable if installation is in close proximity of RF and EMI
transmitting devices. Condensate Drain Size: 5/8-in OD 7/16-in ID
SUGGESTED TOOLS
- Standard Wrench
- Adjustable/Crescent Wrench
- Torque Wrench
- Hex Keys or Allen Wrenches
- Drill & Drill Bits
- Hole Saw
- Pipe Cutter
- Screw drivers (Phillips & Flat blade)
- Manifold and Gauges
- Level
- R410A Flaring Tool
- Clamp on Amp Meter
- Vacuum Pump
- Safety Glasses
- Work Gloves
- Refrigerant Scale
- Micron Gauge
Installation Schematic
Indoor unit
Installation Components
- Front Panel
- Aux. Button
- Filter
- Horizontal Louver
- Remote Controller
- Inter-Connecting Wire
- Drain Hose
- Refrigerant Lines
Outdoor unit
INSTALLATION SITE INSTRUCTIONS
Indoor Unit
Select a site that allows for the following:
- Ensure the installation complies with the installation minimum dimensions and meets the minimum and maximum connecting piping length and maximum change in elevation.
- Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room.
- Condensate can be easily and safely drained.
- All connections can be easily made to outdoor unit.
- Indoor unit is out of reach of children.
- A mounting wall strong enough to withstand four times the full weight and vibration of the unit.
- Filter can be easily accessed for cleaning.
- Leave enough free space to allow access for routine maintenance.
- Install at least 10 ft. (3 m) away from the antenna of TV set or radio.
- Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak.
- An amplifier may be required for the affected device.
- Do not install in a laundry room or by a swimming pool due to the corrosive environment.
Minimum Indoor clearances
INDOOR UNIT INSTALLATION
INDOOR UNIT DIMENSIONS in (mm)
Model | A | B | C |
---|---|---|---|
SC-09W-HP230 | 33.4 |
848
| 11.4
290
| 8.2
208
SC-12W-HP230| 33.4
848
| 11.4
290
| 8.2
208
SC-18W-HP230| 38.2
970
| 11.8
300
| 8.8
224
SC-24W-HP230| 42.4
1077
| 12.8
325
| 9.7
246
SC-36W-HP230| 53.1
1349
| 12.8
325
| 10
254
| | |
Installation of Mounting Bracket
- Attach the mounting bracket to the indoor unit.
- Find the horizontal center of the indoor unit.
- Mark the center of the indoor unit on mounting bracket for future reference.
NOTE
The center of the mounting bracket is not the center of the indoor unit.
Remove the mounting brackets from the indoor unit and position the mounting
bracket on the wall in desired location. Use centering mark on mounting
bracket for centering the indoor unit on the wall. Mounting bracket must be
installed horizontally and level right to left. Condensate drain pan has
built-in pitch for proper drainage. Secure mounting bracket to wall with a
minimum of five screws, evenly spaced to properly support indoor unit weight.
It is recommended to install screw anchors for sheet rock, concrete block,
brick and such type of walls.
INDOOR UNIT INSTALLATION
Mounting Bracket Diagrams and Dimensions
9,000 and 12,000 Units
PIPING INSTALLATION
Refrigerant Piping
Drill Hole in Wall
If indoor unit refrigerant piping is going to exit from the rear
- It is recommended that the refrigerant pipe flare connectors extend through the wall to the outside. In some situations field-fabricated piping extensions will be required to extend the indoor unit refrigerant flare connections to the outside of the wall.
- Use mounting bracket diagrams and dimensions to find and mark the proper location for the wall hole.
If refrigerant piping is going through the right or left side of front
pane
Carefully cut hole in the side of the front panel for piping to enter indoor unit. Find and mark the proper location for the wall hole. Use table below to determine recommended wall hole size for your unit size.
Table of Wall Hole Size per Unit Size
Unit Size BtuH | Wall Hole Size Diameter |
---|---|
in | mm |
9,000 | 2 1/4 |
12,000 | 2 1/4 |
18,000 | 2 3/4 |
24,000 | 2 3/4 |
36,000 | 2 3/4 |
- Cut the wall hole with a 5° to 10° downward slant to the outdoors.
- Insert a wall sleeve into hole to prevent damage to refrigerant pipes, insulation, condensate drain hose and wiring.
- Proper weather proofing of the wall surface and wall sleeve is essential to assure a trouble-free installation.
- Apply sealant, caulking or equivalent weather
proofing material around the perimeter of the wall sleeve (interior & exterior) to eliminate outdoor air and water leaks into the living space.
NOTE
Expandable foam insulation may be added to fill large wall gaps.
Refrigerant Piping
CAUTION
Use refrigeration grade piping ONLY. Uses of other piping will void the
Manufacturer’s Warranty.
Piping Preparation
- Do not open service valves or remove protective caps on pipes until all connections are made.
- Keep tubing free of dirt, sand, moisture and contaminants.
- Insulate each refrigerant pipe and condensate hose with minimum 3/8 (10 mm) wall thermal pipe insulation.
- Bind refrigerant pipes, the condensate hose and interconnecting cable together with cable ties at 12-inch intervals.
Piping Connections to Indoor Unit
NOTE
For maximum serviceability, it is recommended to have refrigerant piping and
drain connections on the outside.
- Feed refrigerant pipes, drain hose and interconnecting wires assembly through wall hole from outdoor to the indoor unit.
- Adjust the length and carefully bend refrigerant pipes to meet indoor unit refrigerant pipe connections with proper tools to avoid kinks.
- Apply a small amount of refrigerant oil to the flare connection on the refrigerant pipes.
Pipe Diameter inch (mm)| Nut Size inch (mm)| Tightening Torque
ft-lbs N-m
---|---|---
1 /4 (6.35)| 1/4 (17)| 10 to 13| 14 to 18
3/8 (9.5)| 3/8 (22)| 25 to 30| 34 to 42
1/2 (12.7)| 1/2 (25)| 36 to 45| 49 to 61
5/8 (15.9)| 5/8 (29)| 50 to 60| 68 to 82
How to Relocate Drain Hose from Left to Right Side if required
- Locate drain plug on right side of the drain tray.
- Firmly grab it and remove from drain tray.
- Locate drain tube on the left side of drain tray.
- Twist drain tube counter-clockwise and gently pull to remove from the drain tray.
- Position drain tube on the right side over the drain fitting.
- Push drain tube onto fitting and rotate clockwise to lock.
- Verify drain tube is secure to prevent leaks.
- Insert drain plug into left side of drain tray fitting.
- Verify plug is fully seated to prevent leaks.
Indoor Drain Piping
The Stealth indoor wall unit uses a gravity drain system. There is no internal condensate pump. The drain hose must slope downward with no kinks, raises or fluctuations.
- Connect the field supplied drain hose to the outlet pipe of indoor wall unit. A field supplied transition or adapter may be required.
- Apply pipe insulation to the entire drain line and joints to prevent sweating.
- The through-wall hole for the drain hose must be lower than the indoor wall unit drain outlet for a functional gravity drain system.
- Install field supplied drain hose with a downward slope from the Indoor wall unit drain outlet to the drain hose outlet.
Route the condensate drain hose in the safety location to dispose of the condensate water.
POWER AND WIRING INSTALLATION
System Wiring Diagrams
Indoor Unit
9,000 and 12,000 BtuH 230V Models
18,000 and 24,000 BtuH 230V Models
36,000 BtuH 230V Models
Indoor Unit Wire Connections
WARNING
Disconnect all electrical power to indoor and outdoor units including disconnects, fuses and circuit breakers. Lockout and tag all disconnect switches.
- Open front cover of indoor unit and remove field wiring terminal block cover.
- Pull interconnecting wires up from back of indoor unit and position in close to theterminal block on indoor unit.
NOTE
Record wire colors and terminal references for uses with Outdoor Unit wire
connections. Connect wiring to indoor unit per system wiring diagram.
NOTE
The indoor unit is powered from the outdoor unit, depending on local code a
disconnect switch may need to be installed to a power supply circuit. Replace
field wiring cover and close front cover of indoor unit.
Indoor Disconnect Switch If required
Local codes may require a disconnect switch within sight of the indoor unit. Use a DFS.Disconnect Switch Accessory Kit (Part No: DFS-SWITCH-A) to break wires going to the N(1), 2, 3, terminals on the indoor unit, as shown in the wiring diagram below
TESTING AND INSPECTION
Leaking Test
- Connect regulated nitrogen to manifold. Attach hose to service port.
- Open manifold valve to add nitrogen to a pressure of 500 lbs.
- Maintain applied pressure for 30 minutes, leak-test flare fittings with soap bubbles.
- If no leak is detected, release nitrogen.
CAUTION
Use vacuum pump, rather than refrigerant, to discharge air when installing
the unit.
Vacuum Procedure
Important
Use a quality Micron Gauge to measure and validate the system vacuum achieved.
Do not rely on the scale of a“bourbon tube”type gauge set to validate the
depth and quality of the vacuum.
- Remove the caps of the liquid valve, gas valve and service port.
- Connect gauge manifold and micron gauge to the service ports provided at the liquid and suction service valves.
- Connect a vacuum pump to the manifold gauge.
- Open the lower pressure side of the manifold valve assembly and start the vacuum pump.
- The switch at the high pressure side of the manifold valve assembly should be kept closed, or evacuation does not fail.
- Operate vacuum pump until a vacuum of 500 microns or less is achieved.
- The evacuation duration depends on the vacuum pump size and unit’s capacity, generally 20 minutes for the 9,000 BtuH units, to 1 hour for a larger 36,000 BtuH unit.
- Close the manifold valves and shut off the pump.
- If vacuum holds below 700 microns for 15 minutes, the system can be considered dry and leak free. Go to step 5.
- If vacuum increases to 800 microns or greater, this is an indication of moisture in system or a leak exist. Identify leak and repair as necessary, after which repeat steps 4 and 5.
- If moisture is suspect, purge system use triple evacuation method using dry nitrogen.
Confirm that manifold valves are closed and disconnect the vacuum pump. Open the service valves to the fully ‘back-seat’ position to let the refrigerant flow to the indoor unit and balance the pressure in system.
Important
Do not allow air to enter the connection pipe when removing the hose. Replace
service valve caps and tighten.
Pipe Testing
Additional Charge
The outdoor unit contains enough refrigerant charge for up to 25 feet from the factory. When the piping is greater than 25 feet, additional charging is necessary. For the additional amount, see the table below.
Model | Add’l Refrigerant Amount for Extra Pipe |
---|---|
9,000 -18,000 | 0.21 oz/ft |
24,000 – 36,000 | 0.54 oz/ft |
Oil Return Bend
When the outdoor unit is more than 30 feet above the indoor unit, an oil return bend must be added for every 20 feet of connection pipe.
Condensate Drain Pipe Testing
Carefully and slowly add 8-10 ounces of water to the indoor unit drain pan.
- Verify the water drains easily out the condensate drain hose.
- If water does not drain easily from the drain hose, then remove kinks, increase drain pitch, or add an auxiliary condensate drain pump.
Start up Checklist
- Turn on main power to indoor and outdoor units.
- Verify the system is not displaying an error code on the indoor unit display.
- Add batteries and press the ON button on the remote controller.
- Verify the remote controller display turns ON and the indoor unit display is ON.
- Press the Mode button to Cooling.
- Adjust the room setpoint to bring the system on in cooling mode.
- The system should start cooling mode within 3-5 minutes.
- Verify the outdoor fan and compressor are operating.
- Verify the indoor fan is operating.
- Verify the indoor discharge air is cooling the room.
- Press the Mode button to Heating. djust the room setpoint to bring the system on in cooling mode.
- The system should start heating mode within 3-5 minutes.
- Verify the outdoor fan and compressor are operating.
- Verify the indoor fan is operating.
- Verify the indoor discharge air is cooling the room.
- Press the OFF button on the remote controller.
- Verify remote controller display turns OFF and the system shuts OFF.
TROUBLESHOOTING
PROBLEM | CAUSE/SOLUTION |
---|---|
System does not restart. | Cause: The system has a built-in three-minute delay |
to prevent short and/or rapid cycling of the compressor.
Solution: Wait three minutes for the protection delay to expire.
Indoor unit emits unpleasant odor when started| Cause: Typically unpleasant odors are the result of mold or mildew forming on the coil surfaces or the air filter.
Solution: Wash indoor air filter in warm water with mild cleaner. If odors persist, contact a qualified service professional to clean the coil surfaces.
You hear a“water flowing”sound.| Cause: It is normal for the system to make“water flowing”or“gurgling”sounds from refrigerant pressures equalizing when the compressor starts and stops
Solution: The noises should discontinue as the refrigerant system equalizes after two or three minutes.
A thin fog or vapor coming out of the indoor unit when system is running.| Cause: It is normal for the system to emit a slight fog or water vapor when cooling extremely humid warm air.
Solution: The fog or water vapor will disappear as the system cools and dehumidifies the room space.
You hear a slight cracking sound when the system stops or starts.| Cause: It is normal for the system to make “slight cracking” sounds from parts expanding and contracting during system starts and stops.
Solution: The noises will discontinue as temperature equalizes after 2 or 3 minutes.
The system will not run.| Cause: There are a number of situations that will prevent the system from running.
Solution: Check for the following:
Circuit breaker is “tripped” or turned off.
Power button of remote is not turned on.
Batteries in the remote controller are low.
Remote controller is in sleep mode or timer mode.
Otherwise, contact a qualified service professional for assistance.
The unit is not heating or cooling adequately.| Cause: There are a number of reasons for inadequate cooling or heating.
Solution: Check the following:
Remove obstructions blocking airflow into the room.
Clean dirty or blocked air filter that is restricting airflow into the system.
Seal around door or windows to prevent air infiltration into the room.
Relocate or remove heat sources from the room.
Water leakage from the outdoor unit.|
P ROBLEM | CAUSE/SOLUTION |
---|---|
Water leaking from the indoor unit into the room. | Cause: While |
it is normal for the system to generate condensate water in cooling mode, it is designed to drain this water via a condensate drain system to a safe location.
Solution: If water is leaking into the room, it may indicate one of the following.
The indoor unit is not level right to left. Level indoor unit.
The condensate drain pipe is restricted or plugged. All restrictions must be removed to allow continuous drainage by gravity.
If problem persists, contact a qualified service professional for assistance.
Wireless remote controller does not work.| Cause: There are a number of possible reasons
Solution: Check the following:
The remote controller was not matched to the indoor unit. See matching instructions.
The batteries might be low. Change the batteries.
The remote controller must be within 25 ft. (7.5 m) with no obstructions of the indoor unit. If remote controller needs to be replaced, contact a qualified service professional for assistance. In the meantime, use the Aux button to operate the system.
The unit will not deliver air.| Cause: There are a number of system functions that will prevent air flow.
Solution: Check for the following:
• In heating mode, the indoor fan may not start for three minutes if the room temperature is very low. This is to prevent blowing cold air.
In heat mode, if the outdoor temperature is low and humidity is high, the system may need to defrost for up to 10 minutes before beginning a heating cycle.
In dry mode, the indoor fan may stop for up to three minutes during the compressor off delay.
Otherwise, you should contact a qualified service professional for assistance.
Moisture or condensation on the discharge air louvers or outlet vents.| Cause: It is normal for the system to develop condensation or moisture on the discharge air louvers when cooling warm humid air for a long period of time.
Solution: The condensation or moisture will disappear as the system cools and dehumidifies the room space.
DIAGNOSTIC CODE
Troubleshooting
The Stealth System has onboard diagnostics. The outdoor unit will provide status indicators. The indoor wall unit and remote controller will display error codes. The following is a sum-mary of the codes with explanation
Malfunction Name
| Indoor Unit & Remote Display| Outdoor Unit Indicators|
Possible Causes
---|---|---|---
Y ellow| Red
System High Pressure
|
E1
| | | Over charged with refrigerant.
Blocked or dirty outdoor coil .
Extreme outdoor ambient conditions
Indoor Anti-Freeze Protection| E2| 3 flashes and
1 sec Off
| | Low return airflow.
Indoor fan speed is too low.
Indoor coil is blocked or dirty.
Refrigerant Leakage Protection| F0| | 9 flashes and
1 sec Off
| refrigerant leaks.
Indoor coil temperature sensor no calibrated.
Refrigerant flow is restricted exvalve, exv, debris
Compressor High Discharge Temperature Protection| E4| 7 flashes and
1 sec Off
| | Please refer to the malfunction analysis discharge temperature, overload
in servic
Overcurrent Protection| E5| 5 flashes and
1 sec Off
| | Supply voltage is unstable.
Supply voltage is too low and system load is too high.
Indoor coil is blocked or dirty.
Communication Malfunction| E6| Continuous On| | 1) Communication cable is mis-wired between indoor and outdoor units.
Indoor or Outdoor control board malfunction.
High Temperature Resistant Protection| E8| 6 flashes and
1 sec Off
| | Incorrect refrigerant charge level.
Refrigerant metering device malfunction.
Compressor malfunction.
EEPROM Memory Malfunction| EE| 11 flashes and
1 sec Off
| | Con trol board malfunction.
System Configuration Malfunction| C5| | | No jumper cap inserted on the
control board.
Incorrect or damaged jumper cap on control board.
Indoor and outdoor units are not compatible.
Pump Down or Gathering Refrigerant Status| Fo| 17 flashes and
1 sec Off
| | Optional Service Mod e
DIAGNOSTIC CODES
__
Malfunction Name
| Indoor Unit Display| Outdoor Unit Indicators|
Possible Causes
---|---|---|---
Yellow| Red
I ndoor Ambient Temperature Sensor Malfunction| F1| | | Loose or bad
connection between sensor and control board.
2Indoor ambient temperature sensor damaged.
Control board malfunction.
Indoor Coil Temperature Sensor Malfunction| F2| | | Loose or bad connection between sensor and control board.
Indoor coil temperature sensor damaged.
Control board malfunction .
Outdoor Ambient Temperature Sensor Malfunction| F3| | 6 flashes and
1 sec Off
| Loose or bad connection between sensor and control board.
Outdoor ambient temperature sensor damaged.
Control board malfunction.
Outdoor Coil Temperature Sensor Malfunction| F4| | 5 flashes and
1 sec Off
| Loose or bad connection between sensor and control board.
Outdoor coil temperature sensor damaged.
Control board malfunction .
Outdoor Discharge Temperature Sensor Malfunction| F5| | 7 flashes and
1 sec Off
| Loose or bad connection between sensor and control board.
Discharge temperature sensor damaged.
Control board malfunction.
High DC Bus Voltage Protection| PH| 13 flashes and
1 sec Off
| | Supply voltage on L1 and N is above 265Vac.
Capacitor on control board malfunction.
Outdoor control board malfunction.
LowDCBusVoltageProtection| PL| 12 flashes and
1 sec Off
| | Supply voltage on L1 and N is below 150Vac.
Capacitor on control board malfunction.
Outdoor control board malfunction.
Compressor Phase Current Protection| P5| | | IPM module malfunction.
Outdoor control board malfunction
Compressor malfunction.
Capacitor Charging Malfunction| PU| | | Capacitor malfunction
Module Temperature Sensor Malfunction| P7| | | Outdoor control board
malfunction
Module Temperature Protection| P8| | | Lack of thermal grease on IPM module.
Heat sink (radiator) not tightly mounted.
Control board malfunction.
Compressor Overload Protection| H3| 8 flashes and
1 sec Off
| | Wiring terminal OVC-COMP is loose.Refer to the malfunction analysis
Malfunction Name
| Indoor Unit Display| Outdoor Unit Indicators|
Possible Causes
---|---|---|---
Yellow| Red
I PM Module Protection| H5| 4 flashes and
1 sec Off
| | IPM module over heating.Improper or Low voltage at the IPM module.
IPM module malfunction.
Indoor DC Fan Motor Malfunction| H6| | | Loose connections between fan motor and control board
Fan motor or blower wheel bearings malfunction.
Control board malfunction.
Compressor De-Synchronized Malfunction| H7| | | Compressor voltage is not balance.
Control board malfunction
Compressor malfunction
Power Factor Correction (PFC) Protection| HC| 14 flashes and
1 sec Off
| | Mis-wiring of the reactor filter and PFC capacitor.
Reactor filter or PFC capacitor malfunction.
Control board malfunction.
Outdoor Fan Motor Malfunction| L3| | 14 flashes and
1 sec Off
| Loose connections between fan motor and control board
Fan motor malfunction.
Control board malfunction.
Incompatible Indoor and Outdoor Units| LP| 16 flashes and
1 sec Off
| | Indoor and outdoor units are not compatible.
Start-Up Malfunction| LC| | | Over charged with refrigerant.
Control board malfunction.
Compressor malefaction.
Compressor Phase-Current Detection Malfunction| U1| | | Outdoor control board
malfunction
DC Bus Voltage Level Dropping Malfunction| U2| | | Unstable supply voltage
Current Detection Malfunction| U3| | | Outdoor control board malfunction
Reversing Valve Malfunction| U4| | | 1) Voltage to reversing valve is less
than 175V.
Loose connections between reversing valve and control board.
Reversing valve solenoid malfunction.
Zero Crossing Detection Malfunction| U9| | | Outdoor control board malfunction
Defrosting Status| note 1| 16 flashes and
1 sec Off
| |
CARE AND CLEANING
WARNING
Take notice of the following items before cleaning the Stealth Indoor wall
unit. To avoid electric shock or injury, do not attempt to clean the unit
unless it has been turned off and disconnected from the main power supply. Do
not wash the unit with water; this may cause an electric shock During
cleaning, be sure to use a stable standing platform.
Air Filter Cleaning
Changing your air filter on a regular basis prevents many problems. Dirty air filters will affect the performance and the longevity of your unit. It is recommended that air filters be cleaned every three 3 months.
To access and clean the filter
Open Front Panel
Firmly grasp both sides of the front panel and pull upward to about 60 degree
angle. (NOTE: do not force panel open.
Remove Filter
Remove the filter as indicated in the figure at right.
Clean Filter
Use vacuum to clean the filter. When the filter is very dirty, use warm
water (below 110°F) to clean it, and then dry filter before replacing.
Reinstall Filter
Reinstall the filter and then close the panel cover tightly.
LIMITED WARRANTY STATEMENT
STEALTH (1HVAC Energy LLC) warrants this product against failure due to defect
in materials or workmanship under normal use and maintenance as follows.
All warranty periods begin on the date of original installation. If the date
cannot be verified, the warranty period begins one hundred twenty (120) days
from
date of manufacture. If a part fails due to defect during the applicable
warranty period, Company will provide a new or remanufactured part, at
Company’s
option, to replace the failed defective part at no charge for the part. This
limited warranty is subject to all provisions, conditions, limitations and
exclusions
listed below
-
A warranty period of Five (5) years on all parts to the original registered end user.
-
A warranty period of seven (7) years on the compressor.
-
Online registration of this product at (Stealthcomfort.com/warranty-information) extends the warranty as follows – one year unit replacement and
twelve (12) year compressor warranty. -
Warranty applies only to products remaining in their original installation location.
Defective parts must be returned to the distributor.
LIMITATIONS OF WARRANTIES: ALL IMPLIED WARRANTIES AND/OR CONDITIONS (INCLUDING
IMPLIED WARRANTIES OR CONDITIONS OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE OR PURPOSE) ARE LIMITED TO THE DURATION OF THIS LIMITED
WARRANTY, SOME STATES OR PROVINCES DO NOT ALLOW LIMITATIONS ON HOW LONG AN
IMPLIED WARRANTY OR CONDITION LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE
EXPRESS WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED,
ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON, WHATSOEVER.
THIS WARRANTY DOES NOT COVER:
- Labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts, or replacement parts, or new units.
- Product cleaning required prior to warranty service and repair.
- Normal maintenance as outlined in the installation and servicing instructions including filter cleaning and/or replacement and lubrication.
- Failure, damage or repairs due to faulty installation, misapplication, abuse, improper servicing, unauthorized alteration or improper operation.
- Failure to start due to voltage conditions, blown fuses, open circuit breakers, or damages due to the inadequacy or interruption of electrical service.
- Failure or damage due to floods, winds, fires, lightning, accidents, corrosive environments (rust, etc.) or other conditions beyond the control of the Company.
- Failure or damage of coils or piping due to corrosion on installations within one (1) miles of sea coast or corrosive body.
- Parts not supplied or designated by Company, or damages resulting from their use.
- Products installed outside the 48 contiguous United States, except the District of Columbia and Hawaii.
- Electricity or fuel costs, or increases in electricity or fuel costs from any reason whatsoever, including additional or unusual use of supplemental electric heat.
- Any cost to replace, refill or dispose of refrigerant, including the cost of refrigerant.
- Shipping damage or damage as a result of transporting the unit.
- Accessories such as condensate pumps, line sets and so forth are not covered.
- Any special, indirect or consequential property or commercial damage of any nature whatsoever.
- Some states or provinces do not allow the exclusion of incidental or consequential damages, so the above limitation may not apply to you.
- Consumable components, such as air filters, are not covered under parts warranty.