Intesis DALI to Modbus Server gateway Installation Guide
- June 7, 2024
- Intesis
Table of Contents
Intesis DALI to Modbus Server gateway
SAFETY INSTRUCTIONS
WARNING
Follow carefully these safety and installation instructions. Improper work
may lead to serious harm to your health and also may damage seriously the
Intesis gateway and/or any other equipment connected to it.
The Intesis gateway must be installed by an accredited electrician or similar
technical personnel, following all the safety instructions given here and in
accordance always with the country legislation for installation of electric
equipment.
The Intesis gateway cannot be installed outdoors or exposed to direct solar radiation, water, high relative humidity, or dust.
The Intesis gateway must only be installed in a restricted access location.
In case of wall mount, fix firmly the Intesis device on a not vibrating
surface following the instructions next.
In the case of the DIN rail, the mount fixes the Intesis device properly to the DIN rail following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to the earth is recommended.
Disconnect always a power of any wires before manipulating and connecting them to the Intesis gateway.
A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV rated is to be used.
Respect always the expected polarity of power and communication cables when connecting them to the Intesis device.
Supply always a correct voltage to power to the Intesis gateway, see details of voltage range admitted by the device in the technical characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries according to the instructions. Battery replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without routing to the outside plant, all communication ports are considered indoor only.
This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with static levels above 4 kV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting switches, etc.) typical anti-static precautions should be observed before touching the unit.
Safety instructions in other languages can be found at: https://intesis.com/docs/manuals/v6-safety
CONFIGURATION
Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at:
https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection or the Console Port (mini USB type B connector
included) for communication between the gateway and the configuration tool.
See CONNECTIONS below and follow instructions of the user’s manual for more
details.
INSTALLATION
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the Intesis
device.
Disconnect the power of any bus or communication cable before connecting it to
the Intesis gateway.
Mount the Intesis device on the wall or DIN rail following the instruction
given below, respecting the safety instructions given above.
Connect an NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply to the Intesis gateway, respect the polarity of DC power or Line and
Neutral if AC power. Apply always a voltage within the range admitted by the
Intesis device and of enough power (see technical characteristics).
Circuit-breakers must be used before the power supply. Rating 250V6A.
Connect the communication cables to the Intesis device, see details on the
user’s manual.
Power the Intesis gateway and the rest of the devices connected to it.
Wall Mount
- Separate the fixing clips in the bottom of the box, pushing them to the outside until hearing the “click” which indicates that now the clips are in position for wall mount, see in the figure below.
- Use the holes of the clips to fix the box in the wall using screws. Use the template below for the wall wholes.
DIN Rail Mount
With the clips of the box in their original position, insert first the box in the upper edge of the DIN rail and later insert the box in the down part of the rail, using a small screwdriver and following the steps in the figure below.
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV-rated power supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table below). The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
Ethernet / Modbus TCP / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the
building, contact the network administrator and make sure traffic on the port
used is allowed through all the LAN path (check the gateway user manual for
more information). With factory settings, after powering up the gateway, DHCP
will be enabled for 30 seconds. After that time, if no IP is provided by a
DHCP server, the default IP 192.168.100.246 will be set.
PortA / DALI
Connect the DALI bus to connectors A4 (+), A3 (-) of the gateway’s PortA. The
Intesis gateway provides 16VDC (+/-2%) DALI voltage to the bus.
PortB / Modbus RTU
Connect the EIA485 bus to connectors B1 (+), B2 (-), and B3 (SNGD) of the
gateway’s PortB. Respect the polarity. Remember the characteristics of the
standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices
connected to the bus, and at each end of the bus it must be a termination
resistor of 120. The gateway has an internal bus biasing circuit that
incorporates the termination resistor. If you install the gateway in one of
the ends of the bus, then do not install an additional termination resistor in
that end.
Connect the serial cable EIA232 coming from the external serial device to the
EIA232 connector of the gateway’s PortB. This is a DB9 male (DTE) connector in
which only the lines TX, RX, and GND are used. Details of the pinout can be
seen in the user’s manual. Respect the maximum distance of 15 meters.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow
communication between the Configuration Software and the gateway. Remember
that Ethernet connection is also allowed. Check the user manual for more
information.
USB
Connect a USB storage device (not an HDD) if required. Check the user manual
for more information.
ELECTRICAL & MECHANICAL FEATURES
This marking on the product, accessories, packaging, or literature (manual) indicates that the product contains electronic parts and they must be properly disposed of by following the instructions at https://intesis.com/weee- regulation
Rev.1.0
© HMS Industrial Networks S.L.U – All rights reserved
This information is subject to change without notice