Honeywell Home Prestige IAQ Programmable Commercial Thermostat User Guide
- June 7, 2024
- Honeywell Home
Table of Contents
Honeywell Home Prestige
IAQ Programmable Commercial Thermostat
FOR MULTISTAGE CONVENTIONAL AND HEAT PUMP SYSTEMS
GUIDE SPECIFICATION
OVERVIEW
Prestige IAQ is a 7-day programmable thermostat with auto changeover that is designed for single-stage and multistage control of conventional and heat pump equipment such as rooftop units and split systems. Prestige IAQ consists of a thermostat and equipment interface module. The thermostat and equipment interface module communicates using Resideo’s proprietary RedLINK wireless technology. The thermostat controls up to 3 heat / 4 cool conventional systems and up to 4 heat / 2 cool heat pump systems. The thermostat controls humidification, dehumidification, ventilation, an economizer, and a lighting panel. Universal sensor inputs are used with a remote indoor air temperature sensor(s), an outdoor air temperature sensor, a discharge air temperature sensor, a return air temperature sensor, an occupancy sensor for the remote setback, and dry contact devices for displaying alerts.
- The thermostat is equipped with a 16:9 touchscreen TFT color display (WQVGA – 480 X 272 pixels).
- Provides a USB port to upload Dealer Information, Custom Reminders, Custom Event Schedules, Holiday Schedule, and Software Updates and to download Data Logs.
- Provides remote access to the thermostat when used with the RedLINK internet gateway.
- Provides control using optional remote temperature and humidity sensors.
- Thermostat integrates with the Niagara-AX framework.
QUALITY ASSURANCE
The thermostat shall be manufactured within a certified ISO-9001 facility and is FCC Compliant with part 15 of the FCC rules.
SEQUENCE OF OPERATION
The heating and cooling setpoints shall be individually adjustable in the program schedule. The thermostat shall have a minimum deadband of 2 F (no mechanical heating or cooling shall operate within this deadband). Space temperature deviation above the cooling setpoint or below the heating setpoint shall generate a demand signal to control the system as follows:
Heating
The thermostat shall control the heating output based on the demand signal
communicated from the thermostat program, taking into account both space
temperature deviation (proportional gain) and the duration of that temperature
deviation (integral gain).
The thermostat shall energize heating equipment when the space temperature
falls below the heating setpoint.
The thermostat shall have a compressor outdoor lockout and backup heat
outdoor lockout to turn off the heat pump or backup heat based on the outdoor
temperature. When the backup heat differential is set to Comfort, the control
algorithm will use backup heat as needed to maintain the setpoint within +/- 1
F. When the backup heat the differential is set to 2 F or higher and the
backup heat upstage timer is turned on, the indoor temperature must drop to
the backup heat differential setting or the backup heat upstage timer must
expire before turning on the backup heat.
Cooling
The thermostat shall control the cooling output based on the demand signal
communicated from the thermostat program, taking into account both space
temperature deviation (proportional gain) and the duration of that temperature
deviation (integral gain).
The thermostat shall energize cooling equipment when space temperature exceeds
the cooling setpoint.
(Optional Remote Equipment) A solid-state enthalpy changeover control shall
determine the capability of the outdoor air to provide free cooling
(optional). The system shall operate as follows:
- Free cooling available from Outdoor Air: On a call for cooling, the system shall enable the economizer to provide free cooling. If this does not meet the space demand, the system shall call for mechanical cooling to satisfy the programmed setpoint.
- Free Cooling Not Available from Outdoor Air: On a call for cooling, the system shall hold the economizer to minimum position and cooling shall be energized to satisfy the programmed setpoint.
Dehumidification
The thermostat shall control to the desired dehumidification level using one of the methods below:
- Control dehumidification using a dehumidifier.
- Control dehumidification by overcooling and lowering the fan speed. Control dehumidification using reheat.
Economizer Interface
The auxiliary output of the equipment interface module (A-L/A terminal) shall
be connected to the economizer’s power circuit or the Occupied/Unoccupied
signal terminal.
Occupied Period: The auxiliary output will provide 24 VAC, allowing the
economizer to operate normally and be available for free cooling if outdoor
conditions permit.
Unoccupied Periods: The auxiliary output will cease, defeating either the
economizer operation or the minimum position.
Heating and Cooling Schedule
Initiation of heating setback or cooling setup for each of 7 days shall be
provided by a programmed time schedule manually entered into the thermostat.
The thermostat shall provide two occupied and two unoccupied periods per day.
When all or a portion of a manually programmed schedule is unavailable, the
thermostat shall control the default program schedule.
The thermostat shall provide adjustable recovery ramps for heating and
cooling. The thermostat will begin heating or cooling recovery early to ensure
that the temperature is reached at the scheduled time.
The thermostat requires the current time to be set to follow the user’s
desired program schedule. The thermostat will automatically update the current
time for Day Light Saving time if this option is turned on.
Fan Operation
Fan Operation shall be selectable as follows:
On: Fan is always on.
Auto: Fan runs only when the heating or cooling system is on.
Follow Schedule: Fan controlled by the program schedule. The thermostat will
turn on the fan 1-3 hours before the Occupied period when the Pre-Occupancy
Purge setting is turned on.
Power Interruption
On loss of power, the thermostat shall maintain programmed times and
temperatures for 10 years.
The current time and date shall be maintained for a minimum of 4 years
assuming 2 weeks of power outages each year
Overrides
Temporary Override: After touching the OVERRIDE button from the Home Screen or
adjusting the temperature setpoint, the thermostat shall use a pre-set
occupied temperature. The new temperature will be maintained for 1 hour and
can be adjusted up to the maximum override duration set by the installer.
Holiday Override: Selecting HOLIDAY MODE from the Menu shall allow the user to
set setback temperatures from the current day to a specified date.
Holiday Schedule: Selecting HOLIDAY / EVENT SCHEDULER from the Menu shall
allow the user to set US or Canadian Holidays and Custom Events:
- US or Canadian Holidays: The thermostat shall allow the user to customize temperature settings to be maintained on specified national holidays. The thermostat resumes normal scheduling between selected holidays.
- Custom Events: The thermostat shall allow the user to customize temperature settings to be maintained during a specific event. Up to 25 Custom Events can be set up for a specific date or a day in a month. The thermostat resumes normal scheduling after the event.
Initiate Occupancy: The thermostat shall keep the temperature at an energy-
saving level until the user touches “Press to start occupancy” on the home
screen. The thermostat returns to an energy-saving level after the hold until
time expires or the Occupied period ends.
Remote Setback using an Occupancy Sensor: During an Occupied Period, the
thermostat shall override the program schedule and follow the desired standby
settings when the occupancy sensor detects the room is unoccupied. The
thermostat shall resume the program schedule when the occupancy sensor detects
the room is occupied.
The thermostat provides three levels of keypad lockout to prevent changes to
the thermostat: Unlocked, Partial Lockout, and Full Lockout.
The thermostat provides heating and cooling temperature range stops to limit
temperature setpoint adjustments.
Reminders and Alarms
The thermostat shall provide an alert on the display when the HVAC filter
requires replacement or cleaning.
The thermostat shall provide an alert on the display when maintenance is
required on the humidification, dehumidification, and ventilation equipment.
The thermostat shall provide an alert on the display when the HVAC system
requires service based on Delta T. The thermostat shall provide an alert on
the display when a problem is detected by a dry contact device connected to
the universal sensor inputs.
The thermostat shall provide an alert on the display when service is required
based on the Custom Reminders entered by the installer. Custom Reminders are
displayed based on the date or when the outdoor temperature exceeds a level
selected by the installer.
www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502 68-3106—02 M.S. Rev.
07-21 | Printed in the United States
© 2021 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell
International, Inc. This product is manufactured by Resideo Technologies, Inc.
and its affiliates.