Honeywell Micro Switch VPX Series Installation Guide
- June 7, 2024
- Honeywell
Table of Contents
Micro Switch VPX Series
Installation Instructions for the MICRO SWITCH VPX Series Valve Position Indicator for Hazardous Locations
Issue M
32312068
2813
Multiple language versions of installation instructions and other documents
are available on Honeywell’s website. To access:
1. Go to http://sensing.honeywell.com/hazardousareaswitches 2. Select the
product’s instructions from the installation instruc-
tion section. Installationsanweisungen und andere Dokumente stehen in mehreren
Sprachen auf der Honeywell-Website zur Verfügung. So greifen Sie darauf zu:
1. Gehen Sie auf die Webseite http://sensing.honeywell.de/
hazardousareaswitches
2. Wählen Sie im Bereich “Installationsanweisungen” die zum entsprechenden
Produkt gehörenden Anweisungen aus.
Versiones de las instrucciones de instalación y otros documentos se encuentran
disponibles en el sitio de internet de Honeywell en múltiples idiomas. Para
acceder:
1. Vaya a http://sensing.honeywell.com/hazardousareaswitches 2. Seleccione
las instrucciones del producto en la sección de
instruccions de instalación. Les instructions d’installation et d’autres
documents sont disponibles dans plusieurs langues sur le site Web d’Honeywell.
Procédure d’accès :
1. Accédez à la page http://sensing.honeywell.com/hazardousareaswitches
2. Sélectionnez les instructions relatives au produit qui vous intéresse dans
la section « Installation Instructions
mWARNING
PERSONAL INJURY
DO NOT USE these products as safety or emergency stop devices or in any other
application where failure of the product could result in personal injury.
Failure to comply with these instructions could result in death or serious
injury.
mWARNING
IMPROPER CONDUIT THREAD USE
DO NOT USE any other conduit thread than the one identified on the product.
Verify that the mating threaded fitting is identical with the conduit thread
marked near the conduit opening (see Figure 6).
Failure to comply with these instructions could result in death or serious
injury.
mWARNING
To maintain ATEX/IECEx protection methods, an Ex cable gland or Ex conduit
sealing device, rated Ex db IIC Gb IP66, Ex tb IIIC Db IP66 shall be
installed. For Intrinsically Safe models, cable glands must have a minimum
service temperature of 80oC.
mWARNING
Enclosure contains aluminum. Care must be taken to avoid hazard due to impact
or friction
mWARNING
To reduce the risk of ignition in hazardous atmospheres, conduit runs must
have a sealing fitting connected within 18 inches of enclosure.
Sul sito Web di Honeywell sono disponibili istruzioni per l’installazione in
più lingue e altra documentazione. Per accedere:
1. Andare a http://sensing.honeywell.com/hazardousareaswitches
2. Selezionare le istruzioni per il prodotto nella sezione istruzioni per
l’installazione.
As versões em diversos idiomas das instruções de instalação e outros
documentos estão disponíveis no site da Honeywell. Para acessar:
1. Vá para http://sensing.honeywell.com/hazardousareaswitches
2. Selecione as instruções do produto na seção de instruções de instalação.
1. http://sensing.honeywell.com/hazardousareaswitches 2.
– Honeywell . . 1. http://sensing.honeywell.com/
hazardousareaswitches 2.
.
mWARNING
Substitution of components may impair intrinsic safety.
mWARNING
OPENING PRODUCTS HAZARD
DO NOT OPEN these products when energized or in a flammable gas atmosphere.
Failure to comply with these instructions could result in death or serious
injury.
mWARNING
RISK TO LIFE OR PROPERTY
Never use this product for an application involving serious risk to life or
property without ensuring that the system as a whole has been designed to
address these risks, and that this product is properly rated and installed for
the intended use within the overall system.
Failure to comply with these instructions could result in death or serious
injury.
mWARNING
This equipment has a non-conducting coating and may generate an ignition-
capable level of electrostatic charges under certain extreme conditions. The
user should ensure that the equipment is not installed in a location where it
may be subjected to external conditions (such as high pressure steam) which
might cause a build up of electrostatic charges on non-conducting surfaces.
Additionally, cleaning of the equipment should be done with a damp cloth.
MICRO SWITCH VPX Series
ISSUE M 32312068
GENERAL INFORMATION
The VPX Valve Position Indicator is designed specifically for use in
potentially hazardous locations where explosive gases or dusts may be present.
To comply with explosion proof requirements the VPX has flame paths within the
housing, which cool any explosion below the ignition temperature before it
reach explosive gases or dusts in the surrounding atmosphere. Flame paths on
the VPX are 1) an extended shaft between the switch cavity and head and 2) the
cover-housing flange joint.
ENVIRONMENTAL PROTECTION
The VPX Valve Position Indicator is often ideal for outdoor use or in
potentially adverse environments. The enclosure is sealed for protection
against corrosion, water, dust and oil as defined in UL 50E to enclosure types
4, 4X, 6, and 13 as well as to IP66 and IP67 as defined in IEC 60529. An
ingress protection rating of IP66 was confirmed according to IEC 60079-0 along
with the hazardous location approvals. A rating of IP67 was confirmed by
Honeywell according to IEC 60529.
The equipment has a non-conducting coating and may generate an ignition-
capable level of electrostatic charges under certain conditions. The user
should ensure that the equipment is not installed in a location where it may
be subjected to external conditions (such as high pressure steam) that might
cause a build up of electrostatic charges on non-conducting surfaces.
Additionally, cleaning of the equipment should be done with a damp cloth.
Figure 1. VPX Valve Position Indicator
Figure 2. Flame Paths
Shaft flame paths
Flange flame paths 2 sps.honeywell.com/ast
HAZARDOUS LOCATION RATINGS
2813
IECEx UL 16.0102X DEMKO 16 ATEX 1733X
Compliance with the Essential Health and Safety Requirements has been assured
by compliance with:
· CENELEC EN 60079-0 EXPLOSIVE ATMOSPHERES PART 0: EQUIPMENT – GENERAL
REQUIREMENTS – Issue Date 2012/08/01 – Revision Date 2013/01/01
· CENELEC EN 60079-1 EXPLOSIVE ATMOSPHERES PART 1: EQUIPMENT PROTECTION BY
ENCLOSURES “d” -Issue Date 2014/10/01- Revision Date 2014/10/23
· CENELEC EN 60079-11 EXPLOSIVE ATMOSPHERES – PART 11: EQUIPMENT PROTECTION BY
INTRINSIC SAFETY “I” – Issue Date 2012/01/01
· CENELEC EN 60079-31 EXPLOSIVE ATMOSPHERES PART 31: EQUIPMENT DUST IGNITION
PROTECTION BY ENCLOSURE “T” – Issue Date 2014/07/01- Revision Date 2014/07/22
· IEC 60079-0 EXPLOSIVE ATMOSPHERES. PART 0: EQUIPMENT GENERAL REQUIREMENTS –
Edition 6 – Issue Date 2011/06/01 – Revision Date 2014/10/01
· IEC 60079-1 EXPLOSIVE ATMOSPHERES. PART 1: EQUIPMENT PROTECTION BY
ENCLOSURES “d” – Edition 7 – Issue Date 2014/06/01 – Revision Date 2014/06/01
· IEC 60079-11 EXPLOSIVE ATMOSPHERES PART 11: EQUIPMENT PROTECTION BY
INTRINSIC SAFETY “I” – Edition 6 – Issue Date 2011/06/01 – Revision Date
2014/10/01
· IEC 60079-31 EXPLOSIVE ATMOSPHERES. PART 31: EQUIPMENT DUST IGNITION
PROTECTION BY ENCLOSURE “T” – Edition 2 – Issue Date 2013/11/01 – Revision
Date 2013/11/01
· EUROPEAN DIRECTIVE ON EQUIPMENT AND PROTECTIVE SYSTEMS INTENDED FOR USE IN
POTENTIALLY EXPLOSIVE ATMOSPHERES (2014/34/EU) commonly referred to as the
ATEX Directive.
· UL 1203 Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use
in Hazardous (Classified) Locations, 5th Edition, Revision 2013-11-22
· CSA C22.2 No. 30 Explosion-proof enclosures for use in class I hazardous
locations, 3rd Edition, Reaffirmed 2012
· CSA C22.2 No. 25 Enclosures for Use in Class II Groups E, F, and G Hazardous
Locations, Reaffirmed 2014
MICRO SWITCH VPX Series
ISSUE M 32312068
The explosion-proof ratings per these standards are:
II 2 G, II 2 D
Ex db IIC T6 Gb Ex tb IIIC T85°C Db Ta -40 °C to +50 °C (Switch Code 4A or 4B)
Ta -40 °C to +60 °C (Switch Code 2A or 2B)
CL 1 DIV 1 Groups B, C, D CL II DIV 1 Groups E, F, G
In addition, versions of the VPX with proximity switches carry an
intrinsically safe rating:
II 1 G, II 1 D
Ex ia IIC T4 Ga Ex ia IIIC 135°C Da Ta -40 °C to 80 °C (Switch Code 2C)
Honeywell ensures all the elements, requirements and provisions adopted comply with the product’s Ex certificate and technical documentation. As detailed in section 5.1 of EN/IEC 60079-1 the requirements of the flamepath joints are met as follows:
Table 1. Flame Path Measurements
Flame Path Comments
Shaft & bearing Cylindrical spigot joint 0,06 mm maximum gap
Cover to base
Flanged joint, 9,5 mm min. surface mate at any location within the joint, 0,038 mm max. clearance between cover and base
North America Hazardous location ratings per UL 1203:2013 and CSA C22.2 No. 30:2003 and CSA C22.2 No. 25:1966 are: · Division 1, Class I, Groups B, C, D · Division 1, Class II, Groups E, F, G
NEPSI RATING
1. :
Ex d C T6 GbEx tD A21 IP66 T85 Ta -40 to +50 (Switch Code 4A or 4B) Ta -40 to
+60 (Switch Code 2A or 2B) 2. NAMUR: Ex ia C T4 GaEx iaD 20 T135 Ta -40 to +80
(Switch Code 2C)
- 2. P+FNCB2V3N0
GB3836.12010 GB3836.42010 GYJ16.1394X GYJGYJ16.1394X 3. 32312068205MPa
1
NAMUR8.2V<1mA>3mA 150VAC/15A250VAC/10A250VDC/0.5A 2 Ex ia C T4 GaEx iaD 20
T135 GYJGYJ16.1394X 3 Ex ia C T4 Ga 4 5 6 GB3836.132013″13 “GB3836.152000″
15″ GB3836.162006” 16 “GB155772007” “GB12476.22010” 2 “GB502572014″ ”
SAFETY INTEGRITY LEVEL (SIL)
SIL 3 per IEC 61508-2 as evaluated by Sira Certification Service.
SAFETY FUNCTION The safety function of the certified equipment is: To provide indication of a monitored valve position upon rotation of the shaft via switches or proximity sensors and a visual indicator.’ UNDETECTABLE DANGEROUS FAILURE
If an undetected dangerous failure of the VPX
Valve Position Indicator were to occur it would fail to respond and would give
an incorrect indication of valve position. However this would only ever occur
if both the switches or sensors and visual indicator were to have failed’.
PROOF TEST REQUIREMENTS A maximum proof test interval of 1 year is recommended
for the VPX products. The proof test procedure must be carried out by a
competent person who is trained in safety operations and is familiar with the
VPX product. A generic proof test procedure can be found in Table 2, however
depending on application may vary.
MATERIALS OF CONSTRUCTION
The following materials are used in the VPX Valve Position Indicator: aluminum
housing, buna-N seals, polycarbonate indicator and indicator cover and
stainless steel shaft and fasteners. The suitability of these materials for
the application environment is solely up to the customer.
ELECTROMECHANICAL SNAP ACTION SWITCHES
The electrical ratings of the VPX with snap-action switches are · 15 A @ 150
Vac, 10 A @ 250 Vac, 0.5 A @ 250 Vdc
Advanced Sensing Technologies 3
MICRO SWITCH VPX Series
ISSUE M 32312068
Table 2. Proof Test Procedure Step Action 1 Bypass safety PLC and/or take alternative actions to avoid false trip. 2 Visually inspect the VPX Valve Position Indicator for signs of wear or damage. 3 Perform the proof test by manually operating the valve being monitored and perform a full stroke. 4 Monitor the visual indication and switch outputs and record test results as per local procedure. 5 Remove the safety PLC bypass and restore the safety system for normal operation.
MCTF Mechanical Life(Cycles) MCTF Electrical Life(Cycles)
Highest SIL
S.NO
Catalog
Value
Reference
Value
Reference SIL Level HFT1 SC2 PTI3
PT4
VPX Series – Electro- > 500,000 with
25,000 with
1
mechanical snap-
Single Sided
SIRA TA Single Sided SIRA TA
action switches loaded Confidence Limit 16002/01 Confidence 16001/01
SIL 3
at 16 A, 250 Vac
of 100%.
Limit of 50%
0 SC 3 1 year Type A
VPX Series – Electro- > 500,000 with
10,000 with
2
mechanical snap-
Single Sided
SIRA TA Single Sided SIRA TA
action switches loaded Confidence Limit 16002/01 Confidence 16001/01
SIL 3
at 0.5 A, 250 Vdc
of 100%.
Limit of 100%.
0 SC 3 1 year Type A
3
VPX Series – Intrensically safe proximity
switches
500,000 with Single Sided
Confidence Limit of 100%.
SIRA TA 16004/01
50,000 with Single Sided Confidence Limit of 100%.
SIRA TA 16003/01
SIL 3
0 SC 3 1 year Type A
Notes: 1 HFT: Hardware Fault Tolerance; 2 SC: Systematic Capability; 3 PTI: Proof Test Interval; 4 PT: Product Type
Staandard Reference
IEC 61508-2:
2010
SIRA FSP 16005/00
IEC 61508-2:
2010
SIRA FSP 16005/00
IEC 61508-2:
2010
SIRA FSP 16005/00
Figure 3. Intrinsically Safe Zone Diagram VPX VALVE POSITION INDICATOR
SWITCHING AMPLIFIER
Proximity Switch #1
Proximity Switch #2
Ui = 16V Ii = 25 mA Pi = 34 mW Ci = 100 nF Li = 100 µH
Ui = 16V Ii = 25 mA Pi = 34 mW Ci = 100 nF Li = 100 µH
Switch 1 L+ Switch 1 LSwitch 2 L+ Switch 2 L-
A certified associated apparatus with zone and group approval and with entity
parameters:
Uo Ui Io Ii Po Pi Co Ci + Ccable Lo Li + Lcable
Zone 0, 1, 2 HAZARDOUS (CLASSIFIED) LOCATION
NON-HAZARDOUS LOCATION
INTRINSICALLY SAFE PROXIMITY SWITCHES
A VPX equipped with proximity switches is considered intrinsically safe when
used with an appropriate switching amplifier, also referred to as an
associated apparatus, which complies with EN 60947-5-6:2000 or IEC
60947-5-6:1999. The amplifier contains a dc source to supply the control
circuit and is controlled by the variable internal resistance of the proximity
switch. This amplifier is placed outside of the hazardous area. A diagram of
the typical installation is shown in Figure 3.
Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci,
must be less than the marked capacitance, CO, shown on any associated
apparatus used. The same applies for 4 sps.honeywell.com/ast
inductance (Lcable, Li and Lo, respectively). Where the cable capacitance and
inductance per foot are not known, the following values shall be used: Ccable
= 200 pF/m., Lcable = 1 H/m.
The associated apparatus output current must be limited by a resistor such
that the output voltage-current plot is a straight line drawn between open-
circuit voltage and short-circuit current. The associated apparatus must be
installed in accordance with its manufacturer’s control drawing. When required
by the manufacturer’s control drawing, the associated apparatus must be
connected to a suitable ground electrode per local installation codes, as
applicable. The resistance of the ground path must be less than 1 Ohm.
Associated apparatus must not be
MICRO SWITCH VPX Series
ISSUE M 32312068
used in combination unless permitted by the associated apparatus certification. Control equipment must not use or generate more than 250 V rms or dc with respect to earth. Where multiple circuits extend from the same piece of intrinsically safe equipment to the associated apparatus, they must be installed in separate cables or in one cable having suitable insulation. Installation must be done in accordance with all local codes.
Figure 5. Terminal Strip Location
, ATTENTION
The following additional previous editions of Standards noted under the
“Standards” section of this Certificate where applied to integral Components
as itemized below. There are no significant safety related changes between
these previous editions and the editions noted under the “Standards” section.
Inductive Proximity Sensor, Part No. NCB2-V3-N0 manufactured by Pepperl+Fuchs
GmbH
IEC 60079-0:2004, IEC 60079-11:2006
INSTALLATION INSTRUCTIONS
1. DO NOT OPEN the VPX when energized or in a flammable atmosphere.
2. Mount VPX using (4) M6 x 1 screws or (4) M8 x 1.25 screws into the tapped
holes at the base of the product. Mounting dimension drawings for the hole
locations are shown in Figure 17. Fasten M6 screws to 18 Nm ±2 Nm [13.3 ft-lb
±1.5 ft-lb]. Fasten M8 screws to 6 Nm ±1 Nm [53 in-lb ±9 in-lb]. Accessory
brackets are available that mate directly to the base of the VPX. Proper
alignment of the shaft of the VPX to the mating valve actuator or coupling is
essential in order to ensure smooth rotary motion of the VPX shaft as well as
to avoid premature wear.
3. After mounting the VPX, remove the (4) socket head cap screws that fasten
the cover to the base using a 6 mm hex wrench.
4. Remove the cover and refer to circuit diagram on the inside of the cover,
or refer to document 32325422. The diagram depicts the available connections
of each switch inside the VPX. A terminal strip is labeled for each switch
connection.
Figure 4. Circuit Diagram Location
Terminal strip connections
5. For installations utilizing the UL or cUL certifications, use Class I,
Division 1, Class II, Division 1, and Class III wiring methods in accordance
with the National Electrical Code (NEC), Canadian Electrical Code (CEC), or
other code(s) where applicable. For installations utilizing the ATEX/IEC Ex
certifications, use applicable requirements from EN/IEC 60079-14, EN/IEC
60079-17, and EN/IEC 60079-19 as required by local codes and regulations.
Figure 6. Conduit Size ID Locations
Conduit thread identification locations
6. Insert the wires through the conduit openings so that they are accessible
inside the VPX. Ensure enough wire is available to reach each terminal strip
location.
7. Wire should be stripped back to 4 mm ±1 mm [0.16 in ±0.04 in]. Wire sizes
should be chosen to comply with local codes and practices and capable of
carrying the rated load. The terminal strip will accept 0,1 mm2 to 4 mm2
[26-12 AWG] wire. Insert the stripped ends of the wire to each connection and
tighten the screws to 0,4 Nm ±0,1 Nm [3.5 in-lb ±1 in-lb].
8. Ground screws are located both inside and outside the enclosure, suitable
for wire sizes up to 4 mm2 [12 AWG]. Fasten all M4 grounding screws to 1,6 Nm
±0,3 Nm [14 in-lb ±2.7 in-lb]. The internal grounding terminal must be used
for the equipment grounding connection and the external terminal is for
supplementary bonding connection where local codes or authorities permit or
require such connections. See Figure 7. Advanced Sensing Technologies 5
MICRO SWITCH VPX Series
ISSUE M 32312068
Figure 7. Ground Screw Locations
9. Spare terminal strip positions are available for making junction
connections for accessories such as pneumatic solenoid valves. The terminal
strip will accept 0,5 mm2 to 4 mm2 [20-16 AWG] wire. Insert the stripped ends
of the wire to each connection and tighten the screws to 0,4 Nm ±0,1 Nm [3.5
in-lb ±1 in-lb].
12. It may be desirable to adjust the cams of the product at this point to
set the switch points. See the adjustment, repair and maintenance section for
instructions on how to adjust the cams.
13. Reassemble cover, making sure to align the arrows on the cover and the
base, per Figure 9. Fasten the (4) socket head cap screws that fasten the
cover to the base using a 6 mm hex wrench to 18 Nm ±2 Nm [13.3 ft-lb ±1.5 ft-
lb]. Screw minimum yield strength: 205 MPa. Confirm with a shim or “feeler”
gauge that the gap between the cover and the base does not exceed 0,038 mm
[0.0015 in].
, CAUTION
Cover joints must be cleaned before replacing the cover. Use care when
reassembling the cover in order to prevent damage to the switch assembly or to
the flange surface.
Figure 9. Cover to Base Alignment
Figure 8. Spare Terminal Block Locations
Cover fits only one orientation. Use arrows on base and cover for alignment
Spare terminal blocks
10. For installations utilizing the UL or cUL certifications, install conduit
plugs in unused openings. For installations utilizing the ATEX/IEC Ex
certifications, install blanking elements rated Ex db IIC Gb IP66 and Ex tb
IIIC Db IP66 in unused openings. Conduit size is marked on the inside of the
housing near the conduit openings. See Figure 6.
11. For installation utilizing the UL or cUL certifications, install a
conduit seal suitable for Class I Groups B, C and D or Class II Groups E, F or
G within 450 mm [18 inches] of every conduit opening. For installations
utilizing the ATEX/ IEC Ex certifications, if an Ex conduit sealing device is
used, it must be installed immediately at each entry. If an Ex cable glad is
used, it must be installed per the manufacturer’s instructions.
14. Perform functional tests. 15. Actuate the VPX switch several times to
ensure smooth
actuation.
6 sps.honeywell.com/ast
MICRO SWITCH VPX Series
ISSUE M 32312068
VISUAL INDICATOR ADJUSTMENT
The visual indicator can be adjusted in two ways, either by rotating the
window through which the indicator is visible or actually repositioning the
indicator to swap the OPEN and CLOSED positions.
is adjustable in 90° increments. Finally, reposition the indicator cover to the desired orientation and tighten the set screws by 4 ½ turns again until the face of the set screw is flush to the cover. Tighten to 0,15 Nm [1.3 in- lb] max. Do not over tighten these screws as it may impact the ingress protection of this cover.
To rotate the window, loosen the two set screws of the indicator cover (See Figure 10) by 1 turn each using a 2 mm hex wrench, rotate the cover and then tighten the set screws one turn again until the face of the set screw is flush to the cover. Tighten to 0,15 Nm [1.3 in-lb] max. Do not over tighten these screws as it may impact the ingress protection of this cover.
Figure 11. Indicator Adjustment
Figure 10. Indicator Cover Alignment
Loosen set screws. Lift off cover.
Lift off indicator. Rotate to desired position.
Set screws
CAM ADJUSTMENT
The switch points of each switch are factory set relative to the shaft
position. See VPX Series Chart 1 drawing for these set points, as they vary by
model. The switch points can be adjusted by repositioning the cams inside the
product.
mWARNING
DO NOT OPEN the VPX when energized or in a flammable atmosphere
Indicator cover rotated 90°
To reposition the indicator, loosen the two set screws of the indicator cover
by 4 ½ turns using a 2 mm hex wrench and lift this cover off the VPX. Next,
lift the indicator off and rotate it to the desired orientation and position
it back in place. The indicator
1. DO NOT OPEN the VPX when energized or a flammable atmosphere.
2. To access the cams, remove the (4) socket head cap screws that fasten the
cover to the base using a 6 mm hex wrench.
3. Each cam mates with the shaft disc. Move cam axially to disengage teeth on
wheel from teeth on shaft disc.
Advanced Sensing Technologies 7
MICRO SWITCH VPX Series
Figure 12. Cam Adjustment
Shaft disc
Figure 14. Spacer
ISSUE M 32312068
Spacer
Cam
4. Turn cam to desired position. Each notch on the shaft disk represents an
operating point change of 4°. Arrows on the cam indicate the high point as a
reference for alignment to the switch or to align one cam with another.
Figure 13. Cam Detail
7. When cam adjustment is complete reassemble cover and torque the (4) socket
head cap screws that fasten the cover to the base using a 6 mm hex wrench to
18 Nm ±2 Nm [13.3 ft-lb ±1.5 ft-lb].
SPECIAL CONDITIONS FOR SAFE USE
· Aluminum enclosure – Care should be taken to minimize the risk of ignition
due to impact or friction.
· Potential electrostatic discharge – Clean product only with a damp cloth.
Arrows on cam indicate high point
5. In versions that use the snap action switches, you will hear an audible
click with the switch actuates or releases.
6. When cam has been rotated to desired location, release cam to engage with
mating shaft disc.
, CAUTION
During the cam adjustment it may be desirable to remove the spacer part (see
Figure 14). Make sure to reassemble this piece after adjustment as it is a
necessary part to ensure the maximum internal volume of the VPX meets agency
requirements.
LEVER POSITIONING
Various levers can be attached to the VPX products equipped with the knurled
shaft option. See 7CX Series Chart 1, 2 and 3 drawings for a list of lever
accessories. To install or reposition a lever, loosen the screw with a 9/64
inch hexagon key wrench, move the lever to the desired position and securely
tighten the screw until the “teller tab” can no longer be moved by hand. Then
tighten the screw another 1/8 to 1/4 turn to assure that the lever is tight on
the shaft. Hexagon key wrenches are provided in adjusting tool set LSZ4005 for
this purpose.
Figure 15. Lever Adjustment
8 sps.honeywell.com/ast
Lever locking screw
Teller tab
MICRO SWITCH VPX Series
ISSUE M 32312068
To order replacement levers, order the part number which is metal stamped on
either the lever or the hub. Only non-sparking levers can be used to retain
the explosion-proof properties.
ACCESSORIES
A mounting bracket kit is available as an accessory, Honeywell part number
VPZB1.
Figure 16. Accessory Bracket
80,0 [3.15]
30,0 [1.18]
130,0 [5.12]
30,0 [1.18]
47 ±10 [1.8 ±0.3]
47 ±10 [1.8 ±0.3]
In addition, conduit plugs are available in the following sizes:
Table 3. Conduit Plug Accessories
Size
Honeywell Part Number
1/2-14 NPT VPZPA
3/4-14 NPT VPZPB
M20 x 1.5
VPZPC
M25 x 1.5
VPZPD
Tightening Specification Hand tight and then 1 to 2 full turns using a wrench Hand tight and then 1 to 2 full turns using a wrench Hand tight and then 1/4 to 1 full turn using a wrench Hand tight and then 1/4 to 1 full turn using a wrench
Advanced Sensing Technologies 9
MICRO SWITCH VPX Series
Figure 17. Mounting Dimensions
ISSUE M 32312068
29,0 [1.14]
Ø 105,8 [Ø 4.16] CLOSED
75 [3.0] min. to remove cover
95,8 [3.77]
65,0 [2.56]
52,0 [2.05] 4,5 [0.18]
Conduit Position “B”
Conduit Position “A”
57,15 35,36 [2.25] [1.392] 4 X M6 x 1 8 4 X M8 x 1.25 8
10 sps.honeywell.com/ast
57,15 [2.25] 140,0 [5.51]
Conduit Position “C”
Conduit Position “D”
140,0 [5.51] 35,36 [1.392]
2 X 32,5 [1.28]
MICRO SWITCH VPX Series
ISSUE M 32312068
Advanced Sensing Technologies 11
MICRO SWITCH VPX Series
Warranty/Remedy Honeywell warrants goods of its manufacture as being free of
defective materials and faulty workmanship during the applicable warranty
period. Honeywell’s standard product warranty applies unless agreed to
otherwise by Honeywell in writing; please refer to your order acknowledgement
or consult your local sales office for specific warranty details. If warranted
goods are returned to Honeywell during the period of coverage, Honeywell will
repair or replace, at its option, without charge those items that Honeywell,
in its sole discretion, finds defective. The foregoing is buyer’s sole remedy
and is in lieu of all other warranties, expressed or implied, including those
of merchantability and fitness for a particular purpose. In no event shall
Honeywell be liable for consequential, special, or indirect damages.
While Honeywell may provide application assistance personally, through our
literature and the Honeywell web site, it is buyer’s sole responsibility to
determine the suitability of the product in the application.
Specifications may change without notice. The information we supply is
believed to be accurate and reliable as of this writing. However, Honeywell
assumes no responsibility for its use.
Honeywell serves its customers through a worldwide network of sales offices,
representatives and distributors. For application assistance, current
specifications, pricing or name of the nearest Authorized Distributor, contact
your local sales office or:
E-mail: info.sc@honeywell.com Internet: sps.honeywell.com/ast Phone and Fax:
USA/Canada +1-800-537-6945
International +1-815-235-6847;
+1-815-235-6545 Fax
ISSUE M 32312068
Honeywell Sensing and Control a division of Honeywell International Inc. 11 West Spring Street Freeport, IL 61032
Honeywell Advanced Sensing Technologies
830 East Arapaho Road
Richardson, TX 75081 sps.honeywell.com/ast
32312068-M-EN | M | 05/21 © 2021 Honeywell International Inc. All rights reserved.
References
- Products - Advanced Sensing Technologies | Honeywell
- Safety and Productivity Solutions | Honeywell
- Safety and Productivity Solutions | Honeywell
- MICRO SWITCH Hazardous Area Switch Installation Instructions
- Products - Advanced Sensing Technologies | Honeywell
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>