Honeywell MAXON PSCHECK Partial Stroke Technology with Series 8000 Pneumatic Safety Shut-off Valve User Guide
- June 7, 2024
- Honeywell
Table of Contents
MAXON PSCHECK™
Partial Stroke Technology with Series 8000 Pneumatic Safety Shut-off
Valve
Selection Guide
Safety First.
Efficiency First.
Success First.
|
---|---
Choose the configuration that’s right for your system.
Features | Panel Options |
---|
LED Indicator Lights
No display has buttons and indicator lights
| LCD Touchscreen Display
Display only, easy-to-use interface
| DCS Integration The plain panel connects through the system
CONFIGURATION| | 1-5 Valve Systems| 1-9 Valve Systems| 1-9 Valves
Systems
Z Partial Stroke Test verification of test pass/fail| •| •| •
Data logging| | •|
Valve degradation error detection| | •| •
Export of valve trending information| | •|
RATING| SIL 2| | Optional| Optional
Class I Division 1 (Z-Purge via pressurized panel)| | Special Order| Special
Order
Class I Division 2| | Optional| Optional
General-purpose Type 12 enclosure| Optional| Optional| Optional
Type 4x enclosure| Optional| Optional| Optional
SOFTWARE| Date valve built (manufacturer setting)| Factory set| Factory
set|
Date valve is installed and commissioned| Factory set| •|
Valve identification/location| | •|
Trending of valve performance| | •|
Compare valve historical trending data| | •|
View alarm history| | •|
Manual test| Keyed access| •| •
Automatically run partial stroke tests| •| •| •
Set frequency of test| Factory set| •|
Set limits on hard and soft alarms| | •|
SPECIALS| User authorization| Keyed access| •|
Panel heater| Special Order| Special Order| Special Order
Panel cooler| Special Order| Special Order| Special Order
HARDWARE
PANEL ADD-ON| Pressure transducer – air line pressure measurement| |
Special Order| Special Order
Inlet panel voltage options:| 24VDC,
110-240VAC
or24VAC| 24VDC,
110-240VAC
or24VAC| 24VDC,
110-240VAC
or24VAC
Communications options –
•Ethernet • Modlous 1761-NET
• Modbus AIC+
•Non-safety communications| | •| •
Panel Sizes
Non-SIL, Type 12, Type 4X panel sizes:
1-2 Valve Systems | 20″H x 20″W x 8″D |
---|---|
3-5 Valve Systems | 24″H x 24″W x 8″D |
6-9 Valve Systems | 36″H x 30″W x 10″D |
SIL, Type 4X panel size:
1-9 Valve Systems | 36″H x 36″W x 12″D |
---|
Explanation of features
CONFIGURATION
Partial Stroke Test verification of test pass/fail – The partial stroke
test can be run manually or automatically at pre-set times. Depending on the
system capabilities, the valve’s health status will be conveyed either by LED
indicator lights on the panel, via an icon on the touch screen display or via
direct communication to the DCS.
Data logging – Valve health trending data is captured in non-volatile
microprocessor memory and will retain all of the valve health information for
up to 10 years or longer
dependent on how many times a year the valve partial stroke test is run.
Valve degradation error detection – Tests performed by MAXON PSCHECK
systems will identify a soft or hard failure (on the 8000 pneumatic SSOV) by
checking the amount of time required for the valve to ‘trip’, signaling a
capability to either open or close. The longer time it takes to trip the valve
indicates potential performance issues. If the valve is degrading it will
signal a soft failure alert, if the valve fails it will indicate a failure.
Export of valve trending information – It is simple to export the valve
health trending data via a supplied Compact Flash (CF) drive. The information
is presented in a . CSV format that can be modified for analysis, audits, and
for presentation to regulatory or insurance authorities.
SOFTWARE
Date valve built – A factory build date will be established in permanent
memory. Date valve installed and commissioned – During the commissioning
process, the customer will be required to set the date the system is installed
which will also establish the baseline for the valve’s health.
Valve identification/location – The customer has the ability to set a
custom number for each valve to help identify its location.
Trending of valve performance – Diagnostics captures the valve testing
information and tracks the overall health of the 8000 pneumatic safety shut-
off valve by plotting this information on a touch screen display showing the
valve’s health trending over the life of the valve. This trending information
or predictive indicator shows a linear relationship between the initial
installation health data vs. the degradation of the valve’s performance over
the life of the valve. This trending data is used to indicate when the valve
may require maintenance, replacement or that it will potentially fail.
Compare valve historical trending data – Ability to switch between three
different screens changing the number of captured data points enabling better
short and long
term viewing of the trending information.
View alarm history – Captures all alarms, the dates of the alarms, and
valve testing information when either a soft ‘alert’ alarm or a hard ‘failure’
alarm is triggered. The system will track all alarm instances over the life of
the valve.
Manual test – Ability to start an immediate manual test on the valves by
pushing a button on the panel, an icon on the touch screen display or
initiated via the DCS dependent on the configuration ordered. The test will
return immediate results on the valve’s performance and will not interfere
with any pre-set automatic tests nor will it interfere with any of the valve
or burner management functions.
Automatic test – The unit will ship from the factory with all systems
pre-set to a monthly partial stroke test schedule. In systems with the touch
screen display or via DCS connection, the customer will have the option to
change the frequency of the test timing to daily, weekly, monthly, quarterly,
bi-annually, annually or a custom set test rate.
Set limits on hard and soft alarms – The unit will ship with factory-set
limits on when a hard or soft alarm will trigger indicating that the valve’s
performance is degrading and maintenance should be scheduled or that the valve
has failed the test. Both can be changed by the customer during the
commissioning process or at a later date. These limits can be increased
meaning the valve will run longer without any warnings or alerts or can be
lowered meaning the system will alarm out, indicating the valve’s degradation
sooner.
User authorization – For systems with a touch screen display, enables
password protected access to limit who can modify the settings and to limit
general access to the trending and tracking information. For manual units with
LED indicator lights, a key is provided to conduct a manual test.
The MAXON PSCHECK technology is an IEC 61511 SIL2 certified diagnostic system that along with Maxon’s Series 8000 valves helps meet SIL3 compliant Safety Instrumented System (SIS) performance requirements.
Commercial & Industrial Combustion (C&IC)
Honeywell
MUNCIE, INDIANA, USA
Maxon
201 East 18th Street
P.O. Box 2068
Muncie, IN 47307-0068
Tel: 765.284.3304
Fax: 765.286.8394| GOLDEN VALLEY, MINNESOTA, USA
Honeywell Automation and Control Solutions
1985 Douglas Drive North
Golden Valley, MN 55422-3992
www.honeywell.com
---|---
Follow us on Twitter: @honeywellcpro
Sales Offices & Representatives Worldwide
www.maxoncorp.com
customer.honeywell.com
02-00019 PR
July 2014
© 2014 Honeywell International Inc.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>