Test Equipment C165 User Guide
- June 7, 2024
- Test Equipment
Table of Contents
99 Washington Street
Melrose, MA 02176
Phone 781-665-1400
Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
C165 QUICK START GUIDE
GETTING STARTED
Press “Power” in the fresh air and allow to countdown for Fresh Air purge.
Rotate selector dial to Flue 1. In fresh air, the O2 reading should be 20.9%
±0.3%.
Rotate selector dial to Flue 2. In fresh air, the CO reading should be zero
(0).
Connect the flue probe thermocouple connector to T1.
Connect flue probe to the water trap.
Connect the optional probe to T2.
BASIC CO/COMBUSTION ANALYSIS
Insert Flue probe into the stack. Adjust cone so the end of the probe is
approximately at the center of the stack.
NOTE: You will have to drill a hole at least 3/8″. Use appropriate
sealing method after testing.
Rotate selector
dial to Flue 1 for CO2, O2, Gross efficiency, Flue temperature, Inlet
temperature. Fuel type can be changed via MENU or STATUS setting
Rotate selector
dial to Flue 2 for CO (ppm), Losses calculated, Excess air %, pressure reading
Fuel type can be changed via
MENU or STATUS setting. Make any adjustments as needed for proper combustion
and wait for the analyzer to display changes in readings. (Repeat as
necessary).
Once complete, remove the probe from the stack, allow the analyzer to purge in
fresh air until CO sensor readings return to ZERO (0) and O2 readings reading
return to 0% to 21%. Continue to the next test or power analyzer off by
pressing On/Off, if finished.
NOTE: Print and store functions may be used at any time during testing.
DIFFERENTIAL TEMPERATURE TEST
Rotate the selector dial to
Pressure/Temperature.
Press “Pump” to ZERO (0) pressure
sensor.
Connect the probe to T1. Connect the probe to T2. Compatible
with any K-Type thermocouple probe or clamp.
Connect thermocouples in test location to start testing
Observe T1, T2, and differential (Delta T).
Press “Print” to print results. Press and Hold results.
DRAFT & STATIC PRESSURE TEST
Rotate the selector dial to Pressure/Temperature.
Press “Pump” to ZERO (0) pressure sensor.
Connect a true draft hose to PI. Connect to P2 for differential. Place probe
tip in the stack to measure draft.
Connect static pressure hose to measure differential pressure.
Place true draft probe tip in the flue to measure draft.
You can also use the combustion probe for measuring pressure.
Press “Print” to print results.
Press and Hold results.
HEAT EXCHANGER TEST
There are many methods to test heat exchanger integrity. One of these is to
observe Excess Air, O2, AND CO readings both before and after the blower turn
on. If the heat exchanger is sealed your O2 and CO readings should remain
fairly stable. A breach in the heat exchanger may allow fresh air to be forced
into the flue after the blower turns on due to a pressure increase in the
plenum. The result may be a rise in the measured O2 in the stack gas and an
increase in the Excess Air. In some sealed systems the fresh air drawn in the
breach may reduce the combustion available leading to an increase in the CO
reading. If either of these situations is present it is probable that there is
a problem with the Heat Exchanger which may require additional testing and
inspection.
NOTE: Many cracks are invisible to borescopes or the naked eye and only
open or separate from pressure or temperature during operation.
Confirm the Fuel Type. Scroll or switch a
different fuel type.
Press to select fuel type.
NOTE: The analyzer will perform a fresh air purge if it did not perform
one on startup. Otherwise, it will skip past the zeroing step to the Blower
Offscreen. See manual for details. Press to continue.
Ensure the analyzer is in fresh air during the
countdown. The screen will automatically advance when complete.
Call for heat.
Observe and wait for O2 readings to stabilize. after the blower turns on,
press the button to start the Post-Blower test.
The analyzer will wait for 60 seconds and then
record the
Post-Blower values for CO,02, and Excess Air.
Test results will automatic-cally be stored to exchange reports. The report includes both Pre and post Blower test segments.
Press to start printing. See the REPORTS section in this guide.
CO ROOM TEST
Great for checking ambient CO and back drafting situations
No probes or hose connections are required for this test.
Rotate selector dial to ROOM CO. Press “Print” to start the GENERAL
test.
Press Flue 2 to start the test.
CO readings will be logged every 2 minutes for a 30-minute time span.
Readings will be stored once the 30-minute test is completed.
Press to print results.
Test results will automatically be stored in ROOM CO reports. See the
REPORTS section in this guide.
AUX SETTING
Programmable Auxiliary screen allows for Tech selectable test parameters to
be chosen.
Rotate selector dial to Menu. Scroll or to Screen. Press “Print” to
select.
Scroll or customize any Line. Press to
select. [Line 5 shown]
Scroll or select
the parameter for this line. Press to select. [Pressure shown]
Rotate selector dial to AUX to view.
Custom selections will now display in A U X mode.
REPORTS: PRINTING & VIEWING
Print and Log easily from the following test screens: Aux, Flue 1, Flue 2,
Commission Test, Pressure/Temperature, Exchange Test, and Room CO
Press **“Print” to start printouts of results from any test screen. Press
during printing to cancel.
Press and hold to log current readings. Align
printer above Analyzer.
To view test results,
rotate the dial to Menu. Scroll **or to Report Press to select.
Scroll or type of test wanted. Press to select. [Exchange shown] Press to
select View.
Press to select
report log number. When indicator lights blink, use or scroll through logged
reports. Press to view a selected report log.
**HIGH CO ALERT
**
At 1000 ppm CO the screen will display HIGH CO and an indicator light will flash and the analyzer will beep several times. Above 2000 ppm the purge pump starts.
MAIN MENU
| SUBMENU|
OPTIONS / COMMENTS
---|---|---
SETUP| LANGUAGE| English
SET TIME| HH:MM: SS format
e.g. 7 am = 07:00:00, 7 pm =19:00:00
SET DATE| MM/DD/YY format
PRINTER| KM IRP KANE IRP•2
WIRELESS lif installed)
SERIAL
PASSKEY| 1111(wait 5 secs after entering the last digit)
BACK|
UNITS| FUEL TYPE| NAT GAS, TOWN GAS, COKE GAS, PROPANE, BUTANE, LPG,
LIGHT OIL, BIO-OIL. WOOD PELLETS, BIOGAS, USER 1 to 5
FUEL ORIGIN| UK, FRANCE, SPAIN, N AMERICA, BELGIUM, NETHERLAND
EFFICIENCY| GROSS. NET. GROSS COND. NET
COND
PRESSURE| FILTER: OFF = normal response. ON = slower (damped) response
RESOLUTION: LOW = e.g. 0.00i inH20 resolution. HIGH = displays roan extra
decimal place
UNITS: mbar, Pa, PSI, mmHg, hPa, inH20, mmH20, kPa, psi
TIME: Test units not available in North American market
BACK:
GAS| PPm. PPal(n), mg/m3, mg/m3(n), mg/kWh, mg/kWh(n)
| TEMP| C. F
02 REF| Up/down to set value (3% default)
NOx CALC| Up/down to set value 15% default)
BACK|
SCREEN| CONTRAST| The factory setting is 14
BACKLIGHT| 0 to 300 secs
AUX| Enables users to customize the parameters on the AUX display: LINE 1,
LINE 2, LINE 3. LINE 4, LINE 5, LINE 6, BACK
BACK|
REPORT| AUX| Stored AUX tests VIEW, DEL ALL, BACK
COMBUSTION| Stored combustion tests: VIEW, DEL ALL, BACK
COMMISSION| Stored commission tests: VIEW, DEL ALL, BACK
PRS/TEMP| Stored pressure tests: VIEW, DEL ALL, BACK
EXCH| Stored exchange tests: VIEW, DEL ALL, BACK
ROOM CO| Stored room CO tests:
VIEW, DEL ALL, BACK
HEADER| LINE 1
LINE 2
BACK
BACK|
SERVICE| CODE| Password protected for authorized service agents only.
Leave set to 000000.