Site Supervisor 10.1-Inch Display
Quick Start Guide
The Site Supervisor 10.1-Inch Display (P/N 818-7240) is a remote user
interface for the Site Supervisor that connects to the controller using the
Ethernet network through the Ethernet port. The Site Supervisor UI allows
users to perform critical actions in the controller quickly.
Functions such as lighting override, controlling heating and cooling stages,
status information, and viewing alarms can all be performed using the
10.1-Inch Display.
General Warnings and Safety Precautions
-
The Display should not be used for purposes different from those described in this guide.
It cannot be used as a safety device. -
When using an external power supply, it is necessary to separate the power of the device from the rest of the electrical devices connected inside the electrical panel.
-
Disconnect all electrical connections before any kind of maintenance is performed.
-
Do NOT open the Site Supervisor Display. Do NOT open the panel rear cover when power is applied.
-
Check that the supply voltage is correct before connecting.
-
Do not expose to water or moisture: use the controller only within its operating limits to avoid sudden temperature changes with high atmospheric humidity to prevent condensation.
-
Wire polarity must be observed: a wrong connection may cause possible malfunctioning and damage to the controller or Display.
For a copy of the full Site Supervisor Guide (P/N 026-1800), go to
http://www.climate.emerson.com or contact Emerson
Customer Service at 770-425-2724.
Display Connections
Display Connections
Specifications
10.1-Inch Display for Site Supervisor
Screen Size| 10.1 Inch
Screen Type| Capacitive Multi-Touch
Resolution| 1280 x 800
Material| ABS Black
Mounting Type| 75mm x 75mm Mount
CPU| 1.8 GHZ quadcore
Memory| RAM 2GB, HDD 16GB
Network| 1 RJ54 Ethernet Port
WIFI| Optional
Bluetooth| Optional
Unit Size| 10.257″ x 7.029″ x 1.004″ (260.54mm x 178.54mm x 25.50mm)
Rating| Commercial
Temp Rating| -4°F to 140°F (-20°C to 60°C)
Power Supply| 12VDC 2A max
Table 1 – Product Specifications
Mounting Dimensions
75mm x 75mm Mount
Direct Connect to Site Supervisor
-
Connect the power supply to the Display.
-
Connect one end of the network cable to ETH1 of the Site Supervisor and the other to the Ethernet port of the 10.1-Inch Display.
Direct Connect Display to Site Supervisor -
Once you have connected the network cable to the Site Supervisor and 10.1-Inch Display, press the menu icon and then press the browser icon . You will now have access to the Site Supervisor through the Display.
Note: If the Site Supervisor has already been set up, you can skip steps 4-6 and log into your Site Supervisor. If this is the initial setup of the Site Supervisor, continue following the steps to set up the Site Supervisor. -
Once you have accessed the Site Supervisor via the 10.1-Inch Display, you will be prompted to log in.
The username will be “user” and the password will be “pass.”
Note: Look at the lower right of the screen to see the version of the Site Supervisor. If the version is 2.06 or above, you will be prompted to change the password. -
Once you have changed the password, you will be on the Localization menu in the Setup Wizard.
Press the Next arrow key at the top right of the screen. -
This will take you to the General Setup Parameter where you will need to enter a Site Name. Once the Site Name has been entered, you will be able to log into the Site Supervisor.
Part Number | Description |
---|---|
818-7240 | Site Supervisor Display10-Inch, Display Only |
818-7243 | Kit, 10-Inch Display, mount, and screws |
Document Part # 026-4045 Rev 2
This document may be photocopied for personal use.
Visit our website at http://www.climate.emerson.com for the latest technical
documentation and updates.
Join Emerson Technical Support on Facebook
http://on.fb.me/WUQRnt
For Technical Support call 770-425-2724
or email
ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only
and they are not to be construed as warranties or guarantees, express or
implied, regarding the products or services described herein or their use or
applicability.
Emerson Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”),
reserves the right to modify the designs or specifications of such products at
any time without notice.
Emerson does not assume responsibility for the selection, use, or maintenance
of any product.
Responsibility for proper selection, use, and maintenance of any product
remains solely with the purchaser and end-user.
Emerson is a trademark of Emerson Electric Co.
©2020 Emerson Retail Solutions, Inc.
All rights reserved.
EMERSON.CONSIDER IT SOLVED™.
Documents / Resources
|
EMERSON Site Supervisor 10-Inch
Display
[pdf] User Guide
Site Supervisor, 10-Inch Display
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>