LG LV420HHV Vertical Air Handler Unit User Guide

June 6, 2024
LG

LG LV420HHV Vertical Air Handler Unit

Performance

Cooling:

Cooling Capacity (Min~Rated~Max, Btu/h) 16,800 ~ 42,000 ~ 50,000
SEER / EER 19.6 / 12.5

SEER – Seasonal Energy Efficiency Ratio     EER – Energy Efficiency Ratio

Heating:

Heating Capacity (Min~Rated~Max, Btu/h) 18,000 ~ 48,000 ~ 60,000
HSPF 11.0

Max heating @ Indoor 700 DB (Btu/h)
Outdoor 17°F WB| 52,200
Outdoor 5°F WB| 48,000
Outdoor -4°F WB| 38,200
Outdoor -13°F WB| 28,810

HSPF – Heating Seasonal Performance Factor

Cooling Nominal Test Conditions:                Heating Nominal Test Conditions:
Indoor: 80°F DB / 67°F WB                      Indoor: 70°F DB / 60°F WB
Outdoor: 95°F DB / 75°F WB                  Outdoor: 47°F DB / 43°F WB

Electrical

Power Supply1 (V/Hz/Ø) 208-230 / 60 / 1
MOP / MCA (A) 40 / 32
Cooling / Heating Rated Amps (A) 14.9 / 16.4
Compressor(A) 22.0
Fan Motor (IDU + ODU) (A 1.3 + (1.6 x 2)
Cooling Power Input (Min~Rated~Max, kW) 1.19 ~ 3.36 ~ 5.32
Heating Power Input (Min~Rated~Max, kW) 1.34 ~ 3.69 ~ 5.8
Locked Rotor Amps (A) 33

MOP – Maximum Overcurrent Protection             MCA – Minimum Circuit Ampacity

Piping

Installed Liquid Pipe (in., O.D.) 3/8 Flare
Installed Vapor Pipe (in., O.D.) 5/8 Flare
IDU Liquid Connection (in., O.D.) 3/8 Flare
IDU Vapor Connection (in., O.D.) 5/8 Flare
Additional Refrigerant (oz./ft.) 0.43
Min/Max. Pipe Length (ft.) 16.4 / 246
Piping Length (no add’l refrig., ft.) 24.9
Max. Elevation (ft.) 98.4

Features

  • Hot start
  • Inverter (variable speed)
  • Auto restart
  • Control lock
  • W2 terminal connection
  • Group control
  • Timer (on/off)
  • Sleep Mode
  • Optional Wi-Fi Control
  • Built in dry contact
  • ODU Drain Pan Heater
  • Night Quiet Function
  • IDU compatible with Multi F (18k, 24k, 36k models)

Required Accessories (sold separately)

Controller (Any LG wired remote controller)

Optional Accessories

☐ MultiSITE™ CRC1 – PREMTBVC0
☐ MultiSITE CRC1+ – PREMTBVC1
☐ MultiSITE Comm. Mgr. – PBACNBTR0A
☐ AC Smart 5 – PACS5A000
☐ ACP 5 – PACP5A000
☐ Simple Controller – PREMTC00U
☐ Wi-Fi module – PWFMDD200
☐ Remote Temperature Sensor – ZRTBS01
☐ Aux Heater Relay Kit – PRARH1
☐ Dry Contact – PDRYCB320
☐Low Ambient Wind Baffle (cooling operation to -4°F) – ZLABGP04A9
☐ Electric Heater 3kW – ANEH033B113
☐ Downflow Conversion Kit – PNDFK0

Operating Range

Outdoor Unit:

Cooling (°F DB) 5 to 118
Heating (°F WB) -13 to 64

Indoor Unit:

Cooling (°F DB) 57 to 77
Heating (°F WB) 59 to 81

System Data

Refrigerant Type/Control R410A / EEV
Refrigerant Charge (lbs.) 9.26
ODU Sound Pressure Max (Cool / Heat) ±1 dB(A)3 54 / 56
IDU Sound Pressure (H/M/L) ±1 dB(A)3 48 / 45 / 44
ODU Net / Shipping Weight (lbs.) 210.9 / 234.1
IDU Net / Shipping Weight (lbs.) 158.7 / 176.4

Fan

ODU / IDU Fan Type Propeller / Sirocco
Fan Speeds (Fan/Cool/Heat) 3 / 3 / 3
Fan Quantity (ODU + IDU) 2 + 1
Motor/Drive Brushless Digitally Controlled / Direct
Maximum ODU Air Volume (CFM) 4,238
IDU Air Volume (H/M/L) (CFM) 1,260 / 1,100 / 1,000
Dehumidification Rate (pts/hr)10 6.76

IDU External Static Pressure Operating
Range (Min~Default~Max) (in-wg)11| 0.1~ 0.3 ~ 1.0

Notes

  1. Acceptable operating voltage: 187V-253V.
  2. Piping lengths are equivalent.
  3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
  4. All power/communication cable to be minimum 14 American wire gage (AWG), 4- conductor, stranded, shielded or unshielded wire and must comply with applicable local and national code. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
  5. Power wiring cable size must comply with the applicable local and national code.
  6. The indoor unit comes with a dry helium charge.
  7. This data is rated 0 ft. above sea level, with 25 ft. of refrigerant line and a 0 ft. level difference between outdoor and indoor units.
  8. Must follow installation instructions in the applicable LG installation manual.
  9. If the optional low ambient wind baffle (ZLABGP04A) is used, one wind baffle is required for each ODU fan.
  10. Dehumidification rate is based on high speed airflow.
  11. 18k, 24k, and 36k IDU units have ECM fan that automatically adjusts throughout the ESP (External Static Pressure) range. Therefore, there is no default ESP value for these units.
  12. 18k and 24k VAHUs are supplied with socket adapters for pipe transitions.
  13. Electric heater accessory available in 3kW, 5kW, 8kW, 10kW, 15kW, and 20kW capacities. Refer to the engineering manual for details.
  14. Controller not included

Factory Configurations


Field Configurations


Dimensions



For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com