LG LV420HHV Vertical Air Handler Unit User Guide
- June 6, 2024
- LG
Table of Contents
LG LV420HHV Vertical Air Handler Unit
Performance
Cooling:
Cooling Capacity (Min~Rated~Max, Btu/h) | 16,800 ~ 42,000 ~ 50,000 |
---|---|
SEER / EER | 19.6 / 12.5 |
SEER – Seasonal Energy Efficiency Ratio EER – Energy Efficiency Ratio
Heating:
Heating Capacity (Min~Rated~Max, Btu/h) | 18,000 ~ 48,000 ~ 60,000 |
---|---|
HSPF | 11.0 |
Max heating @ Indoor 700 DB (Btu/h)
Outdoor 17°F WB| 52,200
Outdoor 5°F WB| 48,000
Outdoor -4°F WB| 38,200
Outdoor -13°F WB| 28,810
HSPF – Heating Seasonal Performance Factor
Cooling Nominal Test Conditions: Heating Nominal Test
Conditions:
Indoor: 80°F DB / 67°F WB Indoor: 70°F DB / 60°F WB
Outdoor: 95°F DB / 75°F WB Outdoor: 47°F DB / 43°F WB
Electrical
Power Supply1 (V/Hz/Ø) | 208-230 / 60 / 1 |
---|---|
MOP / MCA (A) | 40 / 32 |
Cooling / Heating Rated Amps (A) | 14.9 / 16.4 |
Compressor(A) | 22.0 |
Fan Motor (IDU + ODU) (A | 1.3 + (1.6 x 2) |
Cooling Power Input (Min~Rated~Max, kW) | 1.19 ~ 3.36 ~ 5.32 |
Heating Power Input (Min~Rated~Max, kW) | 1.34 ~ 3.69 ~ 5.8 |
Locked Rotor Amps (A) | 33 |
MOP – Maximum Overcurrent Protection MCA – Minimum Circuit Ampacity
Piping
Installed Liquid Pipe (in., O.D.) | 3/8 Flare |
---|---|
Installed Vapor Pipe (in., O.D.) | 5/8 Flare |
IDU Liquid Connection (in., O.D.) | 3/8 Flare |
IDU Vapor Connection (in., O.D.) | 5/8 Flare |
Additional Refrigerant (oz./ft.) | 0.43 |
Min/Max. Pipe Length (ft.) | 16.4 / 246 |
Piping Length (no add’l refrig., ft.) | 24.9 |
Max. Elevation (ft.) | 98.4 |
Features
- Hot start
- Inverter (variable speed)
- Auto restart
- Control lock
- W2 terminal connection
- Group control
- Timer (on/off)
- Sleep Mode
- Optional Wi-Fi Control
- Built in dry contact
- ODU Drain Pan Heater
- Night Quiet Function
- IDU compatible with Multi F (18k, 24k, 36k models)
Required Accessories (sold separately)
Controller (Any LG wired remote controller)
Optional Accessories
☐ MultiSITE™ CRC1 – PREMTBVC0
☐ MultiSITE CRC1+ – PREMTBVC1
☐ MultiSITE Comm. Mgr. – PBACNBTR0A
☐ AC Smart 5 – PACS5A000
☐ ACP 5 – PACP5A000
☐ Simple Controller – PREMTC00U
☐ Wi-Fi module – PWFMDD200
☐ Remote Temperature Sensor – ZRTBS01
☐ Aux Heater Relay Kit – PRARH1
☐ Dry Contact – PDRYCB320
☐Low Ambient Wind Baffle (cooling operation to -4°F) – ZLABGP04A9
☐ Electric Heater 3kW – ANEH033B113
☐ Downflow Conversion Kit – PNDFK0
Operating Range
Outdoor Unit:
Cooling (°F DB) | 5 to 118 |
---|---|
Heating (°F WB) | -13 to 64 |
Indoor Unit:
Cooling (°F DB) | 57 to 77 |
---|---|
Heating (°F WB) | 59 to 81 |
System Data
Refrigerant Type/Control | R410A / EEV |
---|---|
Refrigerant Charge (lbs.) | 9.26 |
ODU Sound Pressure Max (Cool / Heat) ±1 dB(A)3 | 54 / 56 |
IDU Sound Pressure (H/M/L) ±1 dB(A)3 | 48 / 45 / 44 |
ODU Net / Shipping Weight (lbs.) | 210.9 / 234.1 |
IDU Net / Shipping Weight (lbs.) | 158.7 / 176.4 |
Fan
ODU / IDU Fan Type | Propeller / Sirocco |
---|---|
Fan Speeds (Fan/Cool/Heat) | 3 / 3 / 3 |
Fan Quantity (ODU + IDU) | 2 + 1 |
Motor/Drive | Brushless Digitally Controlled / Direct |
Maximum ODU Air Volume (CFM) | 4,238 |
IDU Air Volume (H/M/L) (CFM) | 1,260 / 1,100 / 1,000 |
Dehumidification Rate (pts/hr)10 | 6.76 |
IDU External Static Pressure Operating
Range (Min~Default~Max) (in-wg)11| 0.1~ 0.3 ~ 1.0
Notes
- Acceptable operating voltage: 187V-253V.
- Piping lengths are equivalent.
- Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
- All power/communication cable to be minimum 14 American wire gage (AWG), 4- conductor, stranded, shielded or unshielded wire and must comply with applicable local and national code. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
- Power wiring cable size must comply with the applicable local and national code.
- The indoor unit comes with a dry helium charge.
- This data is rated 0 ft. above sea level, with 25 ft. of refrigerant line and a 0 ft. level difference between outdoor and indoor units.
- Must follow installation instructions in the applicable LG installation manual.
- If the optional low ambient wind baffle (ZLABGP04A) is used, one wind baffle is required for each ODU fan.
- Dehumidification rate is based on high speed airflow.
- 18k, 24k, and 36k IDU units have ECM fan that automatically adjusts throughout the ESP (External Static Pressure) range. Therefore, there is no default ESP value for these units.
- 18k and 24k VAHUs are supplied with socket adapters for pipe transitions.
- Electric heater accessory available in 3kW, 5kW, 8kW, 10kW, 15kW, and 20kW capacities. Refer to the engineering manual for details.
- Controller not included
Factory Configurations
Field Configurations
Dimensions
For continual product development, LG reserves the right to change
specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG
Life’s Good” is a registered trademark of LG Corp.
/www.lghvac.com