Schneider Easy UPS On-Line SRVS Series 6000VA, 10000VA User Manual
- June 6, 2024
- Schneider
Table of Contents
Easy UPS On-Line SRVS Series 6000VA, 10000VA
User Manual Easy UPS On-Line SRVS Series 6000VA, 10000VA
Important Safety Information
Read the instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it. The
following special messages may appear throughout this document or on the
equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning product safety label
indicates that an electrical hazard exists that will result in personal injury
if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
For Professional Business Applications Not For Consumer Use
Safety and General Information
SAVE THESE INSTRUCTIONS This manual contains important instructions that
should be followed during installation and maintenance of the UPS and
batteries. Inspect the package contents upon receipt. Notify the carrier and
dealer if there is any damages.
· This UPS is for indoor use only. · Do not operate this UPS in direct
sunlight, in contact with fluids, or where there is excessive dust or high
humidity.
· Do not operate the UPS near open windows or doors. · Be sure the air vents
on the UPS are not blocked. Allow adequate space for proper ventilation.
Note: Allow a minimum of 20 cm clearance on all four sides of the UPS.
· Environmental factors impact battery life. Elevated ambient temperatures,
poor quality utility power, and frequent discharges will shorten battery life.
Follow the battery manufacturer recommendations.
· Connect the UPS power cable directly to a wall outlet. Do not use surge
protectors or extension cords.
Electrical Safety
· When grounding cannot be verified, disconnect the equipment from the utility
power outlet before installing or connecting to other equipment. Reconnect the
power cord only after all connections are made.
· Connection to the branch circuit (mains) must be performed by a qualified
electrician.
· The protective earth conductor for the UPS carries the leakage current from
the load devices (computer equipment). An insulated ground conductor is to be
installed as part of the branch circuit that supplies the UPS. The conductor
must have the same size and insulation material as the grounded and ungrounded
branch circuit supply conductors. The conductor will be green and with or
without a yellow stripe.
· The grounding conductor is to be grounded to earth at the service equipment,
or if supplied by a separately derived system, at the supply transformer or
motor generator set.
Battery Safety
CAUTION
HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
· Battery must be replaced when they reach end of service life. · Batteries
must be replaced when the unit indicates battery replacement is necessary. ·
When replacing batteries, replace with the same number and type of batteries
originally installed in the unit.
Failure to follow these instructions can result in minor or moderate injury
and equipment damage.
· Do not dispose of batteries in a fire. The batteries may explode.
· Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes, and may be toxic.
· Servicing of batteries should be performed or supervised by personnel
knowledgeable about batteries and required precautions.
· Schneider Electric uses Maintenance-Free sealed Lead Acid batteries. Under
normal use and handling, there is no contact with the internal components of
the batteries. Over charging, over heating or other misuse of batteries can
result in a discharge of battery electrolyte. Released electrolyte is toxic
and may be harmful to the skin and eyes.
· CAUTION: Before replacing batteries, remove conductive jewelry such as
chains, wrist watches, and rings. High energy through conductive materials
could cause severe burns.
2
Easy UPS SRVS Series 6000VA, 10000VA
Radio Frequency Warning
This is a product for commercial and industrial application in the second
environment – installation restrictions or additional measures may be needed
to prevent disturbances.
Product Description
The Schneider Electric Easy UPS is a high performance, uninterruptible power
supply (UPS). The UPS provides protection for electronic equipment from
utility power blackouts, brownouts, sags, and surges and small utility
fluctuations and large disturbances. The UPS also provides battery backup
power for connected equipment until utility power returns to normal levels or
the batteries are fully discharged.
This user manual is available on the enclosed documentation CD and on the
Schneider Electric website, www.apc.com.
Package Contents
Read the Safety Guide before installing the UPS. The packaging is recyclable;
save it for reuse or dispose of it properly.
(1)
(1)
(1)
UPS
User manual
Software, User
documentation CD
(1) USB cable
(1) RS-232 cable
(2) Shipping bracket
NOTE: The model and serial numbers are located on a small, rear panel label.
Optional Accessories
For optional accessories, refer to the Schneider Electric Website at www.apc.com.
Easy UPS SRVS Series 6000VA, 10000VA
3
Specifications
Environment Specifications
NOTICE
RISK OF EQUIPMENT DAMAGE
· UPS must be used indoors only. · The installation location should be sturdy
to withstand the weight of the UPS. · Do not operate UPS where there is
excessive dust or where the temperature or humidity are outside specified
limits.
Failure to follow these instructions can result in equipment damage.
Temperature Operating
Elevation
Storage Operating
Humidity
Storage
0° to 40°C at rated load. 40° to 45°C linearly derated to 85% of maximum load capacity. 45° to 50°C linearly derated to 75% of maximum load capacity. -15° to 60°C 0 – 1,000 m: normal operation 1,000 – 3,000 m: The load reduces @ 1% at an increased height of every 100 m > 3,000 m: UPS will not work 0 – 15,000 m 0 to 95% relative humidity, noncondensing
This unit is intended for indoor use only. Select a location sturdy enough to handle the weight. Do not operate UPS where there is excessive dust or where the temperature or humidity are outside specified limits. Note: Charge the battery modules every six months during storage.
Physical Specifications
UPS model Dimensions with package Width x Height x Depth Dimensions without
package Width x Height x Depth Weight with package Weight without package
Lifting guidelines
SRVS 6000VA 290 mm (11.42in) x 910 mm (35.83in) x 495 mm (19.49 in) 190 mm (7.48 in) x 685mm (26.97in) x 374 mm (14.72 in) 66kg 54kg >55 kg (>120lb)
SRVS 10000VA 320 mm (12.6 in) x 910 mm (35.83in) x 580 mm (22.83 in) 190 mm (7.48 in) x 685 mm (26.97in) x 447 mm (17.6 in) 77kg 65kg >55 kg (>120lb)
4
Easy UPS SRVS Series 6000VA, 10000VA
Input/Output Specifications
UPS Model Input
Output
Voltage Frequency Input Voltage Range (100% load) Input Voltage Range (60% load) Input Power Factor (100% resistive load) Input Protection UPS Capacity Nominal Output Voltage Other Programmable Voltage Efficiency at rated load Output Voltage Regulation
Output Voltage Distortion
Battery
Frequency On Battery Frequency AC Mode Crest Factor Waveform Output Connection Bypass Bypass Range
SRVS 6000VA
SRVS 10000VA 230 Vac Nominal
50 Hz / 60 Hz
176 Vac 300 Vac ± 3%
110 Vac 300 Vac ± 3%
0.99 at 100% load
Thermal circuit breaker
6000 VA / 6000 W
10000 VA / 10000 W
230 Vac
220 Vac, 240 Vac
94% max. ± 1% static · 1% max. for full linear load, · 4% max. for full RCD
load (100% VA, 0.8 PF) · 15% for the last 60 seconds of the backup time (with
full load only for the internal battery) 50 Hz ± 0.1 Hz / 60 Hz ± 0.1 Hz 50 Hz
± 4 Hz / 60 Hz ± 4 Hz
3:1 Sinewave Terminal Internal bypass 185 Vac 250 Vac ± 1%
UPS Model Configuration Type
Battery Bank Voltage
SRVS 6000VA
SRVS 10000VA
Internal battery
Sealed maintenance free (SMF) Sealed maintenance free (SMF)
12 V, 7 Ah
12 V, 9 Ah
192 V
192 V
Front Panel Display
UPS Power On/Off button Status LED LCD Display Mute/Esc button Enter button Up / Down button Alarm LED
Easy UPS SRVS Series 6000VA, 10000VA
5
Rear Panel Features
SRVS 6000VA/SRVS 10000VA
Terminal View
USB port RS-232 Emergency Power Off (EPO) Battery disconnector Intelligent card slot Maintenance bypass
Input circuit breaker Input/Output terminal (Please refer to Terminal view for the details.) Output terminals Ground terminal Input terminals
6
Easy UPS SRVS Series 6000VA, 10000VA
Basic Connectors
USB
Serial port
Intelligent slot card
Battery disconnector
Power management software and interface kits can be used with the UPS. Use
only interface kits supplied or approved by Schneider Electric.
This UPS is equipped internal battery. For batteries without connecting when
the UPS is shipped out from factory. Before turn on the UPS. Please connect
the battery by pulling the handle up, and then pushing it into the unit.
Start Up Settings
Connect the battery
Connect the battery by pulling the battery handle up, and then pushing it into
the unit.
Connect power and equipment to the UPS
CAUTION
HAZARD OF ELECTRIC SHOCK · All electrical work must be performed by a
qualified electrician. · Adhere to all national and local electrical codes. ·
Disconnect the mains power and internal batteries before installing or
servicing the UPS or connected equipment. · UPS AC hardwired and pluggable
outlets may be energized by remote or automatic control at any time. · Do not
use the UPS as safety disconnect. · Turn off all power to this equipment
before working on the equipment. Practice lockout/tagout procedures. · Do not
wear jewelry when working with electrical equipment. Failure to follow these
instructions can result in minor or moderate injury.
1. Connect equipment to the UPS. Avoid using extension cords. 2. Connect
input utility power to the UPS. 3. Switch on the input utility power. Then,
the UPS display panel will illuminate when utility power is available. 4.
Secure the UPS to the ground with two shipping brackets A by fixing four
screws as shown below chart.
Secure the UPS with shipping brackets A only when it is in position with the cable connected.
Easy UPS SRVS Series 6000VA, 10000VA
7
Start the UPS
Press the
button located on the front panel of the UPS.
The battery charges to 90% capacity during the first five hours of normal operation.
Do not expect full battery run capability during this initial charge period.
Cold start the UPS
Use cold start feature to supply power to connected equipment from the UPS batteries.
Press the
button. Then, the display panel will illuminate. Press the
button again to supply
battery power to the connected equipment.
Connect and install management software
Easy UPS SRVS is provided with SchneiderUPS management software for unattended
operating system shutdown, UPS monitoring, UPS control and energy reporting.
The following diagram is a representation of a typical server installation.
1. Connect the USB cable from the rear of the UPS
to the protected device such as a server.
2. For a server or other device with an operating system, load the
SchneiderUPS CD and follow the on-screen set-up instructions.
3. A built-in serial port
is also available
for additional communication options with serial
cable.
4. Even more communication options are available via the built-in intelligent card slot. Refer to www.apc.com for more information.
8
Easy UPS SRVS Series 6000VA, 10000VA
Emergency Power Off
The Emergency Power Off (EPO) function is a feature that will immediately
remove power to all connected equipment. When EPO button is pushed, all
connected equipment will immediately turn off and will not switch to battery
power.
Adhere to all national and local electrical codes. Wiring must be performed by
a qualified electrician. The EPO switch is internally powered by the UPS for
use with non-powered switches or potential free contacts.
Normally closed (N/C) contacts
1. Remove the EPO connector screws beneath pins 1 and 2. 2. Remove the metal
link between pins 1 and 2. 3. Connect N/C relay contacts between pins 1 and 2
of the EPO terminal block. Use
0.5 to 1 mm2 wire. 4. Secure the EPO connector screws beneath pins 1 and 2. If
the N/C is open, the UPS will turn off and power will be removed from the
load.
NOTICE
EQUIPMENT DAMAGE · Do not connect the EPO interface to any circuit other than
a unused circuit. Failure to follow these instructions can result in equipment
damage.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it
only to other SELV circuits. The EPO interface monitors circuits that have no
determined voltage potential. Such closure circuits may be provided by a
switch or relay properly isolated from the utility. To avoid damage to the
UPS, do not connect the EPO interface to any circuit other than a unused
circuit. Use one of the following cable types to connect the UPS to the EPO
switch.
· CL2: Class 2 cable for general use. · CL2P: Plenum cable for use in ducts,
plenums, and other spaces used for environmental air. · CL2R: Riser cable for
use in a vertical run in a floor-to-floor shaft. · CLEX: Limited use cable for
use in dwellings and for use in raceways.
Maintenance Bypass
Maintenance bypass enables the user to isolate the electronic circuitry of the
UPS from the mains and the load without interrupting the load operation by
connecting the loads directly to the bypass utility supply. · This feature is
useful while performing maintenance or service and shall only be executed by
authorized Technical
Service Personnel. · During Maintenance Bypass operation; in case of any mains
interruption occurs, all loads on the output will be
deenergized. Maintenance Bypass Operation should not be preferred for long
time use.
Easy UPS SRVS Series 6000VA, 10000VA
9
Operation
Using The Display
These Easy UPS models are equipped with an intuitive and configurable LCD
display. This display complements the software interface as they convey
similar information and either may be used to configure the UPS settings. The
display consists of the following keys and indicators:
UPS Power On/Off button Status LED
LCD Display Mute/Esc button Enter button Up / Down button Alarm LED
Press this button to turn on the UPS. Press and hold this button until a beep
is heard to turn off the
UPS. Press this button to reset alarms.
The Status LED illuminates green when the power is on. This
LED indicates two different states of output power: Output off: LED blinks.
Press Power On/Off button to
turn the output power on. Output on: LED illuminates green continuously.
The display interface options are visible on this LCD screen. Press
the
or
button to activate LCD, if the
display is not illuminated.
To acknowledge audible alarms and suppress them
temporarily. To exit a sub menu and return to the main menu.
Press this button to enter the menu or to select a menu item/ value
during navigation.
Press these two buttons to scroll through the main menu options and display screens.
This Alarm LED illuminates red when the UPS detects an error and blinks red for UPS notifications. See “Alarms” on page 12 and “Notifications” on page 14 in this manual.
10
Easy UPS SRVS Series 6000VA, 10000VA
LCD Display Icons
On Line: The UPS is drawing utility power and performing double conversion to
supply power to the connected equipment.
On Battery: The UPS is supplying battery backup power to the connected
equipment.
ALARM
Replace Battery: The battery is not connected securely or the battery is
nearing the end of its service life and should be replaced.
Bypass: The UPS is in bypass mode, sending utility power directly to connected
equipment. Bypass mode operation is the result of an internal UPS event or an
overload condition. Under this condition, see “Alarms” on page 12 and
“Notifications” on page 14 in this manual. This icon in combination with Green
Mode icon, indicates that the UPS is in green mode operation. System Alarms:
An internal fault is detected. See “Alarms” on page 12 in this manual.
Overload: The equipment connected to the UPS is drawing more power than rated.
Battery Charge: The battery charge level is indicated by the number of bar
sections illuminated. When all five blocks are illuminated, the battery is
fully charged. Each bar represents approximately 20% of the battery charge
capacity. Load Level: The load percentage is indicated by the number of load
bar sections illuminated. Each bar represents approximately 20% of the maximum
load capacity. Mute: An illuminated line through the icon indicates that the
audible alarm is disabled.
Green Mode: An illuminated icon indicates that the unit is working in Green
mode. The connected equipment is receiving the utility input directly as long
as the input voltage and frequency are within the configured limits.
Alarm or notification: The UPS has detected an error or the UPS is in
configuration mode. See “Notifications” on page 14 in this manual. Event: The
icon is illuminated when the user is viewing the event log.
Easy UPS SRVS Series 6000VA, 10000VA
11
Alarms and System Errors
Status Indicators
One beep every second
4 beeps every 30 sec (first beep starts after 4 sec on battery) Beeper
continuously on Two short beeps every 5 sec
Low Battery State – The battery is nearing its complete discharge state. The UPS is about to shut down. Overload condition – The equipment connected to the UPS is drawing more power than rated. On Battery State – The UPS is supplying battery backup power to the connected equipment. Alarm State – UPS has detected an error. See “Alarms” on page 12 in this manual. Event Bypass State – UPS has detected an error. Connected equipment receives utility input power through the bypass relay.
Alarms
Display code
Description UPS has experienced a short circuit at the output. Unit will try
to autorecover from this condition.
UPS is experiencing an overload condition.
Solution
Check if there is any short circuit at the UPS output. Remove the short circuit wait the unit
auto-recover or Press
button to start
the UPS.
Note: The power supplied to the connected
equipment is dropped when the UPS is in this
condition.
Disconnect nonessential equipment from the UPS to eliminate the overload condition.
The UPS has detected a DC voltage error. Unit will try to auto-recover from
this condition. Temperature of the unit is rising above the set limits.
UPS has detected a charger error.
Bus start failure detected.
If the UPS does not recover automatically, contact Schneider Electric.
Disconnect nonessential equipment from the UPS to reduce the UPS load. Ensure that ambient temperature is within limits. Ensure that adequate clearance is maintained.
Verify if there is any short circuit at the UPS battery terminal.
Press
button to start the UPS.
Contact your dealer.
Bus under
Contact your dealer.
Bus unbalance
Contact your dealer.
12
Easy UPS SRVS Series 6000VA, 10000VA
Display code
Description Inverter soft start failure detected
Solution Contact your dealer.
High Inverter voltage Low Inverter voltage Negative power alert Inverter over current
Contact your dealer. Contact your dealer. Contact your dealer. Contact your dealer.
SPS abnormal
Contact your dealer.
Battery SCR short circuited
Contact your dealer.
Inverter relay short circuited
Contact your dealer.
CAN communication alert
Contact your dealer.
CAN communication alert
Contact your dealer.
CPU communication failure detected
Battery turn-on failure detected
Contact your dealer. Contact your dealer.
PFC current failure detected in battery mode
Bus voltage changes too fast
Contact your dealer. Contact your dealer.
Current detect alert
Contact your dealer.
Contact Schneider Electric for all other alarm codes.
Easy UPS SRVS Series 6000VA, 10000VA
13
Notifications
Display code
Description Battery is not connected.
Over charge
Solution Connect battery to the UPS. See “Start Up Settings” on page 7 in this
manual.
Contact your dealer.
UPS is overload. Devices connected to the UPS are fed directly by the
electrical network via the bypass.
Fan failure detected.
Remove excess loads from UPS output. Contact your dealer.
EPO enabled. Low battery.
Set the circuit in closed position to disable EPO function.
Contact your dealer.
Over temperature Charger failure detected
Contact your dealer. Contact your dealer.
Line situations are different in parallel system
Bypass situations are different in parallel system
Locked in bypass after overload 3 times in 30 minutes.
Cover of maintenance bypass is open.
Bypass unstable
Contact your dealer. Contact your dealer. Contact your dealer. Contact your dealer. Contact your dealer.
14
Easy UPS SRVS Series 6000VA, 10000VA
UPS Display Parameters
Operational data displayed in the display panel is given in the table.
Navigate using the
or
button.
Parameter Output voltage Output frequency Input voltage Input frequency
Battery voltage Charging current Ambient temperature State of battery charge
Load level in percentage (Maximum of Watts or VA) Load level in kVA Total Ah
capacity of connected battery Remaining On Battery runtime
Ah capacity of connected battery
Units Vac Hz Vac Hz V DC A ° C %
%
kVA Ah Minutes Ah
Indicator Icons OUT, V OUT, Hz IN, V IN, Hz BAT, V BAT, A
NUMBER, C BAT, %
OUT, %
OUT, kVA BAT, Ah BAT, Min
BAT, AH
Configuration
Configure UPS Parameters
Follow the steps to configure parameters in the UPS:
1. Press the
button.
2. Press the 3. Press the
or button.
button to navigate to “Set”.
4. Navigate through the parameters using the
or
button.
5. Press the
button to edit a parameter. Icons start flashing to indicate the editing.
6. Press the
or
parameter.
button to navigate between the options available for the selected
7. Press the
button to select the option or
Flashing of icons stops after this.
button to abort the editing of current parameter.
8. Press the
or
button to navigate between parameters.
9. Press the
button to exit menu navigation.
Easy UPS SRVS Series 6000VA, 10000VA
15
UPS Settings
Configure UPS settings using the display interface. See “Configure UPS
parameters” section to edit the parameters.
Function Output voltage Audible alarm
Green mode/ high efficiency mode
Battery Ah capacity Charging current Output voltage adjustment
Inverter voltage adjustment
Factory Default 230 Vac Enable Disabled
9 Ah 1 A 230 Vac Add 0
User Selectable Options 220, 230, 240 Vac Enable, disable Enable/Disable
7~200 Ah 1 to 4 A 220 ±0~9 V 230 ±0~9 V 240 ±0~9 V Add 000~09.9V Sub 000~09.9V
Description Allows the user to select output voltage while the UPS is operating online. UPS will mute audible alarms when setting to disable or when the display panel MUTE button is pressed. When this mode is enabled, connected equipment receives utility input power through the bypass relay as long as input voltage is within the range of ± 5% of configured output voltage and ± 4 Hz of configured output frequency. Inverter is turned off during this mode. If utility power input goes out of range, inverter is turned on. The load is transferred to online mode. The power to the connected equipment may be interrupted up to 10 milliseconds. Allows the user to set the l Ah of the each battery connected to UPS.
Set up charging current of the charger.
You may choose
or
to adjust
Output voltage.
This Parameter can set in Line Mode or Battery
Mode.
You may choose Add or Sub to adjust inverter voltage. The voltage range is from 0V to 9.9V and the default value is 0V. This Parameter can set in Line Mode or Battery Mode.
16
Easy UPS SRVS Series 6000VA, 10000VA
Advance Display Navigation
There are five options in main menu and two sub-menu options in UPS display. Press the
button from the
Home Screen to access these menu options. Use the
or
menu options.
button to navigate between the
Menu Option
Description
Configure the UPS
Use this menu option to configure the UPS parameters. Press the
button to see the
configuration options. See “Configure UPS parameters” on page 16 for details. Press the
button to return to the Home Screen.
Show Event Log Use this menu option to see the UPS event log. The UPS records the last 10 events and displays the codes in this log.
Press the
button to see the log. Use the
or
button to see
the logged events. The
button navigates towards old events and the
button navigates to new events. Every log entry has a numeric and textual event code. At the end of the log, the word “End”
will be displayed. Press the
button to return to the Home Screen.
Show UPS information
Use this menu option to see the UPS information. Press the
button to see the rating
of the UPS.
Press the
button to see the UPS firmware version. Press the
button to
return to the Home Screen.
User Command to bypass
Use this menu option to switch the UPS to bypass mode or bring the UPS to online mode
from bypass mode.
Press
button:
Put: Use to switch the UPS to bypass mode of operation.
Note: Power to the connected equipment will drop, if the mains
voltage is not within the threshold limits.
Out: Bring the UPS out of bypass and restore clean power to the
connected equipment.
Execute Battery Self-Test
Use this menu option to conduct a self-test and determine the battery status. Press the
button to initiate the test.
If the test command is accepted, the UPS will initiate a self-test and will start a count down
on the display.
Display messages are shown at the end of the test.
Test refused. The output is off or battery is not charged.
Test not passed
Press the
Test passed button to return to the Home Screen
Easy UPS SRVS Series 6000VA, 10000VA
17
Troubleshooting
Use the table below to solve minor installation and operation problems. Refer
to the Schneider Electric website, www.apc.com for assistance with complex UPS
problems.
Problem and/or Possible Cause
Solution
UPS will not turn on when utility input is available or there is no power output
The UPS is not turned on. The UPS is not connected to utility power supply.
Press the
button to turn on the UPS.
Check that the power cable from the UPS to the utility
power supply is securely connected at both ends.
See “Start Up Settings” on page 7 in this manual.
Input thermal circuit breaker on the UPS is tripped.
Press the input thermal circuit breaker reset button in the rear panel.
The UPS is operating on battery, while connected to the input utility power
There is high, low, or distorted input voltage or frequency.
Connect the UPS to a different outlet on a different circuit. Test the utility input power to ensure the unit is receiving input power. If display is on, navigate and check the input voltage and frequency.
UPS, when connected to battery, is not supplying power to the connected equipment
The UPS is not turned on. The battery is not connected.
If the UPS has shutdown (the display is not on), follow the procedure “Cold start the UPS” on page 8. Connect battery to the UPS. See “Start Up Settings” on page 7 in this manual.
Low battery cut off. UPS may have
Wait for the utility power to return and charge the battery. To
discharged the battery due to utility power
turn on the output power after utility power returns, press
outage andturned the output off due to low battery condition.
button.
UPS emits an audible beeping sound at long intervals
The UPS is operating normally when running UPS has detected an error. See “Alarms” on page 12 and
on battery.
“Notifications” on page 14 in this manual.
Alarm LED is illuminated. The UPS displays an alarm message and emits a constant beeping sound
The UPS has detected an error.
See “Alarms” on page 12 and “Notifications” on page 14 in this manual.
No audible sounds from UPS even when the Alert LED is illuminated.
Audible alarm is disabled.
Change the UPS configuration to enable audible alarms.
UPS is not providing expected backup time.
The UPS battery is discharged due to a recent power outage.
The batteries require recharging after extended outages. Batteries can wear faster when put into service without proper recharging or when operated at elevated temperatures.
The battery is near the end of its service life.
If the battery is near the end of its service life, consider replacing the battery, even if the replace battery indicator is not illuminated. See “Start Up” on page 8 in this manual.
18
Easy UPS SRVS Series 6000VA, 10000VA
Problem and/or Possible Cause UPS is not turning off
Solution
POWER OFF button not pressed properly Press and hold the
button until the beep is heard
to power off the UPS.
Utility input power is available.
UPS logic power can not be turned off if utility input
power is available. To turn off the UPS, turn off utility
input power and press
button. Release when a
beep is heard.
UPS is in Bypass mode and the LED is not illuminated red.
UPS is in green mode.
Disable green mode if not desired.
UPS is configured to stay in the bypass mode. UPS is in bypass mode even after
over temperature alarm is cleared. The UPS has experienced an overload
condition and transferred to bypass.
UPS detected an error and transferred to bypass.
Change the configuration to exit bypass mode.
Reduce the connected load to <70% to bring the UPS to online mode. Connected
equipment exceeds the “maximum load” as defined in specifications on the
Schneider Electric Website, www.apc.com. The alarms remain on until the
overload condition is corrected. Disconnect nonessential equipment from the
UPS to eliminate the overload condition. The UPS continues to supply power as
long as it is in bypass mode and the circuit breaker does not trip. The UPS
will not provide battery power in the event of a utility voltage interruption.
See “Alarms” on page 12 and “Notifications” on page 14 in this manual.
Easy UPS SRVS Series 6000VA, 10000VA
19
Transport
1. Shut down and disconnect all connected equipment. 2. Disconnect the unit
from mains power. 3. Disconnect all internal and external batteries (if
applicable). 4. Follow the shipping instructions outlined in the Service
section of this manual.
Service
If the unit requires service, do not return it to the dealer. Follow these
steps: 1. Review the Troubleshooting section of the manual to eliminate common
problems. 2. If the problem persists, contact Schneider Electric Customer
Support through the Schneider Electric website, www.apc.com. a. Note the model
number and serial number and the date of purchase. The model and serial
numbers are located on the rear panel of the unit and are available through
the LCD display on select models. b. Call Customer Support. A technician will
attempt to solve the problem over the phone. If this is not possible, the
technician will issue a Returned Material Authorization Number (RMA#). c. If
the unit is under warranty, the repairs are free. d. Service procedures and
returns may vary internationally. For country specific instructions refer to
the Schneider Electric website, www.apc.com. 3. Pack the unit properly to
avoid damage in transit. Never use foam beads for packaging. Damage sustained
in transit is not covered under warranty. Note: Before shipping, always
disconnect battery modules in a UPS or external battery pack. The disconnected
internal batteries may remain inside the UPS or external battery pack. 4.
Write the RMA# provided by Customer Support on the outside of the package. 5.
Return the unit by insured, prepaid carrier to the address provided by
Customer Support.
20
Easy UPS SRVS Series 6000VA, 10000VA
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT), warrants its products to be free
from defects in materials and workmanship for a period of two (2) years from
the date of purchase. The SEIT obligation under this warranty is limited to
repairing or replacing, at its own sole option, any such defective products.
Repair or replacement of a defective product or part thereof does not extend
the original warranty period.
This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase. Products may be registered
online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused
by end user or any third person misuse, negligence, improper installation,
testing, operation or use of the product contrary to SEIT recommendations of
specifications. Further, SEIT shall not be liable for defects resulting from:
- unauthorized attempts to repair or modify the product, 2) incorrect or
inadequate electrical voltage or connection, 3) inappropriate on site
operation conditions, 4) Acts of God, 5) exposure to the elements, or 6)
theft. In no event shall SEIT have any liability under this warranty for any
product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the Schneider Electric website: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
Easy UPS SRVS Series 6000VA, 10000VA
21
Schneider Electric Worldwide Customer Support
Customer support for this or any other Schneider Electric product is available
at no charge in any of the following ways:
· Visit the Schneider Electric website to access documents in the Schneider
Electric Knowledge Base and to submit customer support requests. www.apc.com
(Corporate Headquarters) Connect to localized Schneider Electric websites for
specific countries, each of which provides customer support information.
www.apc.com/support/ Global support searching Schneider Electric Knowledge
Base and using e-support.
· Contact the Schneider Electric Customer Support Center by telephone or
e-mail. Local, country specific centers: go to www.apc.com/support/contact
for contact information.
For information on how to obtain local customer support, contact the Schneider
Electric representative or other distributor from whom you purchased your
Schneider Electric product.
© 2021 Schneider Electric. The Schneider Electric logo is owed by Schneider Electric Industries
EN 990-91094A
S.A.S., or their affiliated companies. All other trademarks are property of their respective owners.
05/2021
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>