Controller for C.H. pump and H.W. pump
Model: PC12HW
Manual
Introduction
The PC12HW controller is designed to control C.H. and H.W. pumps. C.H. pump turns ON when boiler temperature exceeds user setpoint temperature. H.W. pump work depends on the temperature difference. H.W. pump turns on when boiler temperature exceeds the temperature of the tank by hysteresis value set by the user. H.W. pump works until the temperature of the boiler and the temperature of the tank will be equal or the setpoint temperature of the tank will be achieved.
Product Compliance
This product complies with the essential requirements and other relevant provisions of the following EU Directives: EMC 2014/30/EU, RoHS 2011/65/EU.
Safety Information
Use in accordance to national and EU regulations. Use the device as intended,
keeping it in dry condition. Product for indoor use only. Installation must be
carried out by a qualified person in accordance to national and EU
regulations.
Before carrying out any activities related to the power supply (connecting
wires, device installing etc.), make sure that main power
is not connected to the controller! Incorrect wiring connections may cause
device damage.
Controller description
1. Power supply indicator
2. C.H. pump operation indicator
3. H.W. pump operation indicator
4. Display
5. Increasing setpoint temperature or value
6. Menu button
7. Decreasing setpoint temperature or value| 8. Sound alarmed
9. C.H. temperature sensor
10. H.W. temperature sensor
11. H.W. pump power supply
12. C.H. pump power supply
13. Controller power supply
14. ON/OFF power supply switch
---|---
Wiring diagram
Controller operation
Hysteresis and setpoint temperatures for C.H and H.W. pumps can be changed by
pressing the button (menu option). On the display will appear flashing
letter „C”, „U”, or „H” and at this point we can change the desired setpoint
temperatures using or buttons. After few seconds controller will go itself
into operating mode and display the current temperature.
C – above this temperature C.H. pump will be turned on
U – above this temperature H.W. pump will be turned off
H – H.W. pump will be turned on when H.W. sensor temperature will detect lower
temperature than „U-H”
P Function (priority)
With the priority enabled, the pumps are prioritized. H.W. pump turns on
firstly and then, after reaching setpoint temperature of the H.W. tank – C.H.
pump starts to work. With the priority turned off pumps are working
independently without priority for the H.W. pump.
To activate priority, press and hold the button until the „P” and „L”
letters will appear on the display. Use or buttons to select „P” and then
confirm your selection with the button. Use or buttons to activate (ON) or
deactivate (OFF) priority function. Confirm the selection with the
button.
L function (summer mode)
This function deactivates C.H. pump. Only H.W. pump is running and C.H. pump
will turn on only when boiler reaches 90°C temperature
– protecting function will protect the boiler against overheating.
To activate summer mode, press and hold the button until the „P” and „L”
letters will appear on the display. Use or buttons to select „L” and then
confirm your selection with the button. Use or buttons to activate (ON) or
deactivate (OFF) summer mode. Confirm the selection with the button.
Manual mode
Manual control of the C.H and H.W pump depends on the operation mode and
safety rules in the central heating phase (overheating). Holding down the
and buttons will enable/disable the central heating pump for continuous
operation. Holding down the and buttons will enable/disable the hot
water pump for continuous operation. The hot utility water pump turns off
always after reaching the maximum temperature of the reservoir or until the
temperatures are equal.
Tank temperature preview is available on pressing the button. After a few
seconds, the controller will return to displaying the boiler temperature.
Histeresis
It is the temperature difference between turning the pump on and off. For example
- For the central heating system, the controller has a constant 2-step hysteresis. After setting the temperature in the „C” parameter, eg at 30 °C, the pump will be turned on after exceeding 30 °C, and it will be turned off when the temperature drops below 28 °C.
- In the H.W system, after setting the temperature in the „U” parameter to 50 °C, the H.W pump will be turned off when the temperature exceeds 50 °C. However, it will be activated when the temperature drops below the „U-H” value.
Additional functions
Controller has an „anti-stop” function which protects the pump against limescale when there is no heating season. The pump is turned on every 14 days for 15 seconds. Additional protection is the frost protection function, which runs the pump permanently when the temperature on the sensor drops below 5°C.
Alarm
The controller is equipped with an acoustic alarm signaling too high
temperature on the boiler 90 ° C.
Full error list:
E1 – short circuit in the C.H. sensor circuit or the temperature exceeded 99 °
C
E2 – broken C.H. sensor
E3 – short circuit in broken H.W. sensor
E4 – broken H.W. sensor
E3 and E4 errors are visible after pressing the button.
PLEASE NOTE!
If the E1 or E2 error is displayed, the CH pump works all the time until the
fault is removed.
Technical specification
Power supply | 230 V / 50Hz ±10% |
---|---|
Power consumption | 2 W |
Ambient temperature | -10 to 50°C |
Max load of C.H. pump and H.W. pump | 6 A each |
Temperature measurement range | 0 to 99°C |
Setpoint temperature range | C.H. |
H.W. | 20 to 80°C |
Sensor temperature range | -10 to 120°C |
Sensor cable lenght | C.H. |
H.W. | 3 m |
Adjustable H.W. tank hysteresis | 5 to 30°C |
DISTRIBUTOR OF SALUS CONTROLS:
QL CONTROLS Sp. z o.o., Sp. k.
Rolna 4
43-262 Kobielice
Poland
www.salus-controls.eu