Danfoss AFA / VFG 2(1) Pressure Relief Controller User Guide

October 27, 2023
Danfoss

Danfoss AFA / VFG 2(1) Pressure Relief Controller User Guide

Danfoss AFA VFG 2\(1\) Pressure Relief Controller

AFA/VFG 2(1) / 73696430

www.danfoss.com

FIG 1

FIG 2

FIG 3

FIG 4

FIG 5

FIG 6

FIG 7

FIG 8

FIG 9

FIG 10

FIG 11

FIG 12

FIG 13

FIG 14

Safety Notes

Prior to assembly and commissioning to avoid injury of persons and damages of the devices, it is absolutely necessary to carefully read and observe these instructions.

Necessary assembly, start‑up, and maintenance work must be performed only by qualified, trained and authorized personnel.

Prior to assembly and maintenance work on the controller, the system must be:

  • depressurized,
  • cooled down,
  • emptied and
  • cleaned.

Please comply with the instructions of the
system manufacturer or system operator.

Definition of Application

The controller is used for pressure relief of steam, water and water glycol mixtures for heating, district heating and cooling systems.

The technical data on the label plates determinethe use.

Scope of Delivery ❶

Impulse tube AF, accessory, for connection to
the pipeline.

Mounting ❷

Admissible Installation Positions
DN 15‑80 media temperatures up to 120 °C:
Can be installed in any position ①.

DN 100‑250 and DN 15‑80, media temperatures higher >120 °C.

Installation only permitted in horizontal pipelines with the actuator hanging downwards ②.

Installation Scheme ❸

Note: The valve is closed without pressure and is opening on rising pressure ② before the valve.

Valve Installation ❹

  1. Install strainer ❸ ① before the controller.

  2. Rinse system prior to installing the valve.

  3. Observe flow direction ③ on the valve body.
    Flanges ④ in the pipeline must be in parallel position and sealing surfaces must be clean and without any damage.

  4. Install the valve.

  5. Tighten screws crosswise in 3 steps up to the max. torque.

Valve Actuator Installation ❺

Valves DN 150 – 250 ① :
The actuator stem must be screwed into the valve stem.
Observe the Installation Instructions ② for the DN 150 – 250 valves.

Valves DN 15‑125:

  1. Place actuator at the valve.
  2. Align actuator, observe position of impulse tube connection ③.
  3. Tighten union nut ④
    Torque 100 Nm

Impulse Tube Installation ❻

Note: When installing seal pots ①, please observe the Installation Instructions for the seal pots.

Which impulse tubes to use?
Use the impulse tube set AF (1×) ②:
Order No.: 003G1391 or use the following pipes:

FIG 15 Which impulse tubes to use

The impulse tube ③ can be connected directly to the valve ④ or to the pipeline ⑤.
⑥ ventilation socket, do not connect impulse tube.

Installation ❼

  1. Remove plug ① at the valve.
  2. Screwed in threaded joint G ¼ ② with copper seal, Torque 40 Nm.
  3. Cut pipe in rectangular sections ③ and burr.
  4. For copper pipe: insert sockets ④ on both sides.
  5. Verify the correct position of the cutting ring ⑤.
  6. Press impulse tube ⑥ into the threaded joint up to its stop.
  7. Tighten union nut ⑦ Torque 40 Nm

Insulation ❽

For media temperatures up to 100 °C the pressure actuator ① may be insulated.

Dismounting ❾

Danger
Danger of injury by hot water!
Valve without actuator is open ①, seal ② is in the actuator.
Prior to dismounting, depressurize system!
Carry out dismounting in reverse order to mounting.

Leak and Pressure Tests ❿

Observe max. permitted pressure, see below.
The pressure ① behind the valve must not exceed the pressure ② before the valve.

Caution:
The valve is closed without pressure and is opening on rising pressure before the valve. Non-compliance may cause damages at the controller ③.

Prior to pressure tests, it is absolutely
necessary to remove the impulse tube at the valve ④.

Close connections with plugs G ¼ ISO 228.
Max. pressure [bar] with connected impulse tube

FIG 16 Prior to pressure tests

Observe nominal pressure ⑤ of the valve.
Max. test pressure is 1.5 × PN.

Filling the System, First Start-up ⓫

The pressure ① behind the valve must not exceed the pressure ② before the valve.

Caution:
The valve is closed without pressure and is
opening on rising pressure before the valve.

Non-compliance may cause damages at the controller ③ .

  1. Open shut-off valve ④ at the impulse tube, if any.
  2. Slowly open shut-off unit ⑥.
  3. Slowly open shut-off unit ⑤.
  4. Only for actuator 630 cm²:

Open ventilation screw ⑦ by about 2 turns.
As soon as water is penetrating, close screw.

Putting out of Operation ⓬

  1. Slowly close shut-off units ①.
  2. Slowly close shut-off units ②.

Setpoint Adjustment ⓭

Set-point range see rating plate ①.

  1. Start system, see section “First Start-up”.

  2. Start pump ②.

  3. Observe pressure indicator ③.

  4. Slightly close fitting ④ behind the pump (in flow direction) so that the pressure ③ is rising.

  5. Adjusting the setpoint ⓮:
    Turning to the right ① reduces the set-point (unstressing the spring, tension spring)
    Turning to the left ② increases the set-point (stressing the spring)

  6. If the required pressure ③ cannot be set, further close the fitting ④.

  7. The set-point adjuster ⑤ may be sealed.

Dimensions, Weights ⓯

Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.

Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.

All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.