Schneider Electric Industries France L Isle D Espagnac XZBWR2STT24 Wireless Transmission System for Sensors Instructions

June 6, 2024
Schneider Electric Industries France L Isle D Espagnac

XZBWE112A24 - QR Code

http://qr.tesensors.com/XZ001

Wireless Transmission System for sensors

XZBWE112A24 - Transmission System

Compatible receiver Max. number of transmitters Output
ZBRRC ZBR Transmission mode 32 XZBWE112A24 (Version ≥ 1.2)
XZBWR2STT24 XZBW Transmission mode 2 XZBWE112A24 (All versions)

& Q2)
ZBRN1| ZBR Transmission mode| 60 XZBWE112A24 (Version ≥ 1.2)| Ethernet modbus TCP
ZBRN2| Modbus serial line

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Disconnect all power before servicing equipment.
  • Use only the specified voltage when operating this equipment and any associated products.

Failure to follow these instructions will result in death or serious injury.

WARNING

UNINTENDED EQUIPMENT OPERATION

  • Do not use this equipment in safety critical machine functions.
  • Use appropriate safety interlocks where personnel and/or equipment hazards exist.
  • Do not disassemble, repair, or modify this equipment.
  • Install and operate this equipment in an appropriately rated enclosure for its intended environment.
  • Install properly rated fuses as indicated on page 3 of this document.
  • Check that the control is not activated if the product falls during transit.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

© 2021 Schneider Electric. “All Rights Reserved.”

(A) Characteristics

XZBWE112A24

Free field radio Range| 100 m
Typical radio range in industrial environment| 25 m
Operating temperature| -25…+55 °C / -13…131 °F
Storage temperature| -40…+70 °C / -40…158 °F
Power supply (transmitter alone)| 24 Vdc -15% / +20%  – 15 mA
Output power supply for sensor| 24 V -15% / +20% – 100 mA max. (no overload protection)
Startup time| < 0,4 s
Response time| 30 ms
Input frequency| < 0,5 Hz
Input time| ON > 100 ms – OFF > 100 ms
Input state 0| < 30% Valim ( 7,2 V … 24 V) – < 1,5 mA
Input state 1| 85% Valim (20,4 V … 24 V) – = 1,6 mA
IP Protection| IP65, IP67
Enclosure type 4 (indoor use and vertical mounting only)
Display| Orange / Green LED
Receiver| XZBWR2STT24 “Only one receiver per transmitter XZBWE112A24”
ZigBee Green Power 2.405 GHz (channel 11 IEEE 802.15.4) compliant
XZBWR2STT24
Operating temperature| -20…+55 °C / -4…131 °F
Storage temperature| -40…+70 °C / -40…158 °F
Power supply (receiver alone)| 24 Vdc – 100 mA max.
Outputs| 2 + 2 PNP – 200 mA (each output)
IP Protection| IP20 enclosure type 1
Display| 1 LED for each output – 1 LED for power supply – 1 LED for signal strength
Startup time| < 0,4 s
Setup (pairing process)| 2 push buttons

(B) Mounting instructions

Dimensions

mm/in.                XZBWE112A24 - Dimensions 1

XZBWE112A24 - Dimensions 2 XZBWE112A24 - Dimensions 3

mm/in.

XZBWE112A24 - Dimensions 4 XZBWE112A24 -
Dimensions 5 XZBWE112A24 -
Dimensions 6

Mounting tips

XZBWE112A24 - Mounting Tips

(1) Metal structure
(2) Wall

Signal attenuation according to the material

Glass window 10…20% (3)
Plaster wall 30…45% (3)
Brick wall 60% (3)
Concrete wall 70…80% (3)
Metal structure 50…100% (3)

(3): Values for indication purposes only. Actual values depend on the thickness and nature of the material.

Unobstructed

XZBWE112A24 - Unobstructed

(4):Typical values that may be modified by the application environment.

Metal cabinet

XZBWE112A24 - Metal cabinet

Mounting Tips for Antenna

XZBWE112A24 - Mounting Tips for Antenna 4

XZBWE112A24 - Mounting Tips for Antenna 3

XZBWE112A24 - Mounting Tips for Antenna 1

XZBWE112A24 - Mounting Tips for Antenna 5

Optimized installation:
The XZBWE, the antenna and the receiver are installed following their vertical axis.

(5): ZBRA1 is incompatible with XZBWR2STT24.

The relay antenna is used to bypass an obstacle and / or increase the range.

XZBWE112A24 - Mounting Tips for Antenna 6 XZBWE112A24 - Mounting Tips for Antenna 7

(C) Wiring diagrams

XZBWR2STT24 / ZBRRC                XZBWE112A24XZBWE112A24 - Wiring
Diagram 1 Imax = 200 mA

XZBWE112A24 - Wiring Diagram 2

(1): 1 A fuse from supplier Bussmann® reference GMA-1A, 250 V fast-blow.

(2): 400 mA fast blow fuse – Telemecanique ref. XUZE04

Mm/in.| | XZBWE112A24 - Wiring Diagram 3c| XZBWE112A24 -
Wiring Diagram 3d|
---|---|---|---|---
mm²| 0,14…0,75| 0,14…2,5| 0,14…4| 0,14…1,5
AWG| 26…18| 26…14| 26…12| 26…16

XZBWE112A24 - Wiring Diagram 4a

Ø 3,5 mm / 0.14 in.

| | Nm| 0,6
---|---|---|---
lb-in| 5.3

XZBWE112A24 - Wiring Diagram 5

Socket Sensor Input

Pin. n°| Signal
XZBWE112A24 - Wiring Diagram 6| 1| +24 Vdc Output to sensor
2| not used
3| 0 Vdc
4| NO NPN or PNP or contact input from sensor
5| not used

Socket Power Supply (male)

Pin. n°| Signal
XZBWE112A24 - Wiring Diagram 7| 1| +24 Vdc
2| not used
3| 0 Vdc
4| not used

(D) LEDs Status

XZBWE112A24 - LEDs Status

1

LED MODE
Power OFF
Input OFF
Input ON
Communication Error with receiver

GN:  Green
OG:  Orange
   Flashing

(E) XZBWE: Transmission mode setting

XZBWE112A24 - XZBWE 1

XZBWE112A24 - XZBWE 2

For the XZBWE setting, use a position switch or a push button

(F) Pairing or Unpairing

XZBWR2STT24

XZBWR2STT24 - Pairing or Unpairing 1

For ZBR products setting, you can refer to the User Guides: https://www.se.com/ww/en/download/document/EIO0000000812 https://www.se.com/ww/en/download/document/EIO0000001177

ZBRRC

XZBWR2STT24 - Pairing or Unpairing 2

LEDs Status

| Green ON
| Yellow ON
| Flashing
XZBWR2STT24 - LED 4| Sequential

XZBWR2STT24 - Pairing or Unpairing 3

(1): All Outputs are inactive for 4 seconds after end of pairing procedure
(2): This function is impossible with the reference XZBWR2STT24

(4) Make a test by actuating the limit switch

Exit

XZBWR2STT24 - Exit 1 XZBWR2STT24 - Exit
3

Electronic Lock/Unlock

This procedure shows how to electronically lock/unlock the receiver.

XZBWR2STT24 - Electronic Lock Unlock 1

: Locked

XZBWR2STT24 - Electronic Lock Unlock 2

XZBWR2STT24 - Electronic Lock Unlock 3

: Unlocked

Total Reset: After a Total Reset the receiver is on factory setting.

XZBWR2STT24 - Reset 1  XZBWR2STT24 -
Reset 4 XZBWR2STT24 - Reset
5 XZBWR2STT24 - Reset
6  XZBWR2STT24 -
Reset 7 XZBWR2STT24 - Reset
8 XZBWR2STT24 - Reset
9

NOTE:
Before disassembly for storage, perform a full reset of the receiver memory.

(E) Servicing and Diagnostic

E1 Diagnostic in RUN mode:

XZBWR2STT24

XZBWR2STT24 - Diagnostic in RUN mode

E2 Output operation

XZBWR2STT24 - Output operation

(1): Sensor
(2): Communication disturbance
(3): td = Delay: < 30 ms
(4): tf = Time-out in fault condition: < 1 mn
(5): tr = Recovery delay: < 1 mn

Schneider Electric logo

Telemecanique logo n1

Simplified EU Declaration of Conformity

We, SCHNEIDER ELECTRIC INDUSTRIES SAS declare, under our sole responsibility, that the radio equipments:

Trademark : Telemecanique
Models : XZBW…

comply with Essential Requirements of following European Directives :

Radio Equipment Directive :
2014/53/EU

Regulations relative to the exposure to electromagnetic fields :
1999/519/EC
2013/35/EU

The full text of the EU Declaration of Conformity is available at the following internet address:
http://qr.tesensors.com/….

WARNING TO USERS IN THE UNITED STATES AND CANADA

WARNING TO USERS IN THE UNITED STATES

Federal Communication Commission Interference Statement
This equipment complies with FCC’s radiation exposure limits set forth for an uncontrolled environment under the following conditions:
1- This equipment should be installed and operated such that a minimum separation distance of 20 cm is maintained between the radiator (antenna) and user’s/nearby person’s body at all times.
2- This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.

If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference.
  2. This device must accept any interference received, including interference that may cause undesired operation.

NO UNAUTHORIZED MODIFICATIONS

CAUTION: This equipment may not be modified, altered, or changed in any way without signed written permission from SCHNEIDER ELECTRIC. Any changes or modifications to this equipment not expressly approved by SCHNEIDER ELECTRIC may cause harmful interference, will void the FCC authorization to operate this equipment and will void the SCHNEIDER ELECTRIC warranty.

WARNING TO USERS IN THE CANADA / ATTENTION POUR LES UTILISATEURS AU

CANADA

This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s license-exempt RSS(s). Operation is subject to the following two conditions:

  1. this device may not cause interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation of the device.

This equipment complies with RSS102’s radiation exposure limits set forth for an uncontrolled environment under the following conditions:

  1. This equipment should be installed and operated such that a minimum separation distance of 20 cm is maintained between the radiator (antenna) and user’s/nearby person’s body at all times.
  2. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.

| XZBWE112A24| XZBWR2STT24
---|---|---
FCC ID| Y7HXZBWE| Y7HXZBWR
IC| 7002C-XZBWE| 7002C-XZBWR
PMN| XZBWE112A24| XZBWR2STT24

Telemecanique logo n1NHA50158_02
10 – 2021

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals