victron energy ASS030550200 Non Inverting Remote On-Off Cable Instructions
- June 6, 2024
- victron energy
Table of Contents
- victron energy ASS030550200 Non Inverting Remote On-Off Cable
- Non inverting remote on-off cable (ASS030550200)
- Wiring for the Battery Protect BP40i, BP60i and BP200i:
- Wiring for the Skylla-TG battery charger:
- Cable Specifications:
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
victron energy ASS030550200 Non Inverting Remote On-Off Cable
Instructions
Non inverting remote on-off cable (ASS030550200)
Use this cable to connect the following products to the VE.Bus BMS:
- Skylla-TG all models
- Battery Protect models BP40i, BP60i and BP200i (all discontinued).
The cable translates the remote on/off driver logic from the VE.Bus BMS (normally high, and open circuit in case of alarm) to the logic needed by above products: active pull down to switch off.
Wiring for the Battery Protect BP40i, BP60i and BP200i:
Wire the Non inverting remote on-off cable
- between the Load-disconnect-output of the VE.Bus BMS and the Battery Protect.
Wiring for the Skylla-TG battery charger:
Wire the Non inverting remote on-off cable (1) between the Charge- disconnectoutput of the VE.Bus BMS and the Skylla- TG battery charger.
Cable Specifications:
Maximum input voltage: 70V
Maximum output voltage: 70V
Pull down: when input free floating (input will be pulled low by the remote
on-off cable) or when input voltage less than approximately 2V
Pull down current: approximately 30mA (short circuit proof)
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>