netvox R718VB Wireless Capacitive Proximity Sensor User Manual
- June 6, 2024
- netvox
Table of Contents
netvox R718VB Wireless Capacitive Proximity Sensor User Manual
Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.
Introduction
R718VB can detect the toilet water level, hand sanitizer level, presence or
absence of toilet paper, it may also be applied to non-metallic pipes (pipe
major diameter D ≥11mm) liquid level detector.
This device is connected with a non-contact capacitive sensor which can be
mounted to the exterior of the container, without direct contact with the
object to be detected, which may detect the current position of liquid level,
or the presence or absence of liquid soap, toilet paper; the detected data is
transmitted to other devices through the wireless network. It uses the SX1276
wireless communication module .
LoRa Wireless Technology:
LoRa is a wireless communication technology dedicated to long distance and low power consumption. Compared with other communication methods, LoRa spread spectrum modulation method greatly increases to expand the communication distance. Widely used in long-distance, low-data wireless communications. For example, automatic meter reading, building automation equipment, wireless security systems, industrial monitoring. Main features include small size, low power consumption, transmission distance, anti-interference ability and so on.
LoRaWAN:
LoRaWAN uses LoRa technology to define end-to-end standard specifications to ensure interoperability between devices and gateways from different manufacturers.
Appearance
Main Features
- Adopt SX1276 wireless communication module
- 2 ER14505 battery AA SIZE (3.6V / section) parallel power supply
- Non-contact capacitive sensor
- The main protection level of the equipment is IP65/IP67 (optional), and the protection level of the sensor probe is IP65
- The base is attached with a magnet that can be attached to a ferromagnetic material object
- Compatible with LoRaWANTM Class A
- Frequency hopping spread spectrum technology
- Configuration parameters can be configured through third-party software platforms, data can be read and alerts can be set via SMS text and email (optional)
- Applicable to third-party platforms: Actility / ThingPark / TTN / MyDevices / Cayenne
- Low power consumption and long battery life
Note*:
Battery life is determined by the sensor reporting frequency and other
variables.
Please refer to http://www.netvox.com.tw/electric/electric_calc.html
On this website, users can find various types of battery lifetime in different
configurations.
Application
- The water level of the toilet tank
- The level of hand sanitizer
- Presence or absence of toilet paper
Set up Instruction
On/Off
Network Joining
Function Key
Sleeping Mode
Low Voltage Warning
Data Report
The device will immediately send a version packet report along with an uplink
packet including liquid level status, battery voltage.
The device sends data in the default configuration before any configuration is
done.
Default Setting:
Maximum time: 15min
Minimum time: 15min (Detect the current voltage value and liquid level status
by default setting)
Battery Voltage Change: 0x01 (0.1V)
R718VB detection status:
The distance between liquid level and sensor reaches the threshold will
report, and the threshold can adjust sensitivity
The device will detect the status regularly at the MinTime interval.
When the device detects liquid level, status = 1
When the device does not detect liquid level, status = 0
There are two conditions in which the device will report the status of the detected liquid and the battery voltage at Min Time interval:
a. When the liquid level changes from where the device can detect to where the
device cannot detect. (1→0 )
b. When the liquid level changes from where the device cannot detect to where
the device can detect. (0→1)
If none of the above conditions is met, the device will report at the MaxTime
interval.
For the analysis of the data command reported by the device, refer to the
Netvox LoRaWAN Application Command document and
http://loraresolver.netvoxcloud.com:8888/page/index
Note:
The device send data cycle depends on real programming configuration according
to the customer’s inquiry.
The interval between two reports must be the minimum time.
Example for Report Configuration:
Fport:0x07
-
Configure the device report parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
Downlink: 019F003C003C0100000000
The device returns:
819F000000000000000000 (The configuration succeeded)
819F010000000000000000 (The configuration failed) -
Read the device configuration parameters
Downlink: 029F000000000000000000
The device returns:
829F003C003C0100000000 (current configuration parameters)
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
Note: Max Time=Min Time. Data will only be report according to Max Time (Min Time) duration regardless Battery Voltage Change value.
Example#2 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V
Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
Notes :
- The device only wakes up and performs data sampling according to MinTime Interval. When it is sleeping, it does not collect data.
- The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the device reports according to MinTime interval. If the data variation is not greater than the last data reported, the device reports according to MaxTime interval.
- We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too low, the device wakes up frequently and the battery will be drained soon.
- Whenever the device sends a report, no matter resulting from data variation, button pushed or MaxTime interval, another cycle of MinTime/MaxTime calculation is started.
Application Scenario
When the use case is for detecting the water level of the toilet tank, please
install the device at a desired level of the toilet tank.
Turn on the device after it is fixed to the toilet tank and powered.
The device will detect the status regularly at the MinTime interval.
There are two conditions in which the device will report the status of the
detected liquid and the battery voltage at MinTime interval:
a. When the liquid level changes from where the device can detect to where the
device cannot detect
b. When the liquid level changes from where the device cannot detect to where
the device can detect
If none of the above conditions is met, the device will report at the MaxTime interval
Installation
Wireless Capacitive Proximity Sensor (R718VB) has two magnets on back.
When using it, the back of it can be adsorbed a ferromagnetic material object,
or the two ends can be fixed to the wall with screws (should be purchased)
Note:
Do not install the device in a metal shielded box or other electrical
equipment around it to avoid affecting the wireless transmission of the
device.
8.1 Measured liquid medium viscosity
8.1.1 Dynamic viscosity:
A. Less Than 10mPa·s when the normal measurement.
B. 10mPa < Dynamic viscosity < 30mPa·s would affect the detection
C. Greater than 30mPa·s due to a large amount of liquid attached to the
container wall, cannot be measured.
Note:
With the temperature rise viscosity decreases, most of the high viscosity of
the liquid by the temperature is more obvious, so when measuring the viscosity
of the liquid when the liquid temperature attention.
8.1.2 Dynamic (absolute) viscosity Explanation:
Dynamic (absolute) viscosity is the tangential force per unit area required to move one horizontal plane with respect to an other plane – at an unit velocity – when maintaining an unit distance apart in the fluid.
8.1.3 Common substances
Reference source: https://en.wikipedia.org/wiki/Viscosity
8.2 Requirements of container and Installation Instruction
- Could either glue the probe or use a support to fix the probe on the outside of the container.
- Avoid metal materials at the probe mounting site so as not to affect the detection.
- The place where the probe is installed should avoid the liquid and the flow path of the liquid.
- There should be no silt or other debris inside the container where the low-level probe is directly facing, so as not to affect the detection.
- Containers made of non-metallic materials with flat surface, uniform thickness, tight material and good insulation performance; such as glass, plastic, non-absorbent ceramic, acrylic, rubber and other materials or their composite materials.
Example of the
installation method of the sensor with the square or flat non-metallic
container
8.3 Adjust sensitivity
Adjust the sensitivity knob with a small screwdriver, rotate counterclockwise to increase the sensitivity, and rotate clockwise to decrease the sensitivity (sensitivity from high to low 12 cycles in total.)
8.4 Information about Battery Passivation
Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density.
However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high. This lithium chloride layer prevents rapid self-discharge caused by continuous reaction between lithium and thionyl chloride, but battery passivation may also lead to voltage delay when the batteries are put into operation, and our devices may not work correctly in this situation.
As a result, please make sure to source batteries from reliable vendors, and the batteries should be produced within the last three months.
If encountering the situation of battery passivation, users can activate the battery to eliminate the battery hysteresis.
*To determine whether a battery requires activation
Connect a new ER14505 battery to a 68ohm resistor in parallel and check the
voltage of the circuit.
If the voltage is below 3.3V, it means the battery requires activation.
*How to activate the battery
- Connect a battery to a 68ohm resistor in parallel
- Keep the connection for 6~8 minutes
- The voltage of the circuit should be ≧3.3V
Important Maintenance Instruction
Kindly pay attention to the following in order to achieve the best maintenance of the product:
- Keep the device dry. Rain, moisture or any liquid might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.
- Do not use or store the device in dusty or dirty environment. It might damage its detachable parts and electronic components.
- Do not store the device under excessive heat condition. High temperature can shorten the life of electronic devices, destroy batteries, and deform or melt some plastic parts.
- Do not store the device in places that are too cold. Otherwise, when the temperature rises to normal temperature, moisture will form inside, which will destroy the board.
- Do not throw, knock or shake the device. Rough handling of equipment can destroy internal circuit boards and delicate structures.
- Do not clean the device with strong chemicals, detergents or strong detergents.
- Do not apply the device with paint. Smudges might block in the device and affect the operation.
- Do not throw the battery into the fire, or the battery will explode. Damaged batteries may also explode.
All of the above applies to your device, battery and accessories. If any device is not working properly, please take it to the nearest authorized service facility for repair.