systec therm RAYSTAT-V5 Control Unit Installation Guide

June 6, 2024
systec therm

systec therm RAYSTAT-V5 Control Unit

PRODUCT OVERVIEW

systec therm RAYSTAT-V5 Control Unit fig 1 systec therm RAYSTAT-V5 Control Unit fig 2 systec therm RAYSTAT-V5 Control Unit fig 3

INSTALLATION INSTRUCTIONS

systec therm RAYSTAT-V5 Control Unit fig 4 systec therm RAYSTAT-V5 Control Unit fig 6 systec therm RAYSTAT-V5 Control Unit fig 8

systec therm RAYSTAT-V5 Control Unit fig 9

systec therm RAYSTAT-V5 Control Unit fig 10

PROGRAM START – QUICK START

Quick Startsystec therm RAYSTAT-V5 Control Unit fig
11

  • POWER ON : Flashing

  • Heating cable

  • Pipe/line sensing

  • Ambient sensing

  • Alarmsystec therm RAYSTAT-V5 Control Unit fig 12

  • Segment Testsystec therm RAYSTAT-V5 Control Unit fig 13

  • Unit name Raystat Version 5

  • Firmware Revision number

  • Parameter DEFAULT : – – – – PiPE Air

  • Quick start: Select Operation Mode for pipe line (PiPE) or ambient temperatures sensing Air – (PASC – Proportional Ambient Control sensing)

  • Parameter PiPE : 0°C… +90°C PASC: AIR (PASC) 0°C… +30°C DEFAULT: 3°Csystec therm RAYSTAT-V5 Control Unit fig 16

  • Quick start : Choose Setpoint Temperature

  • Parameters DEFAULT : –20°C: –30 – 0°Csystec therm RAYSTAT-V5 Control Unit fig 17

  • (PASC-Air only): Lowest ambient temperature

  • Parameters
    01 = Ø < DN 25 / 1”
    02 = Ø ≥ DN 25 / 1”
    03 = Ø ≥ DN 50 / 2”
    DEFAULT: 01systec therm RAYSTAT-V5 Control Unit fig 18
    (PASC-Air only): Average pipe diameter level

  • Parameters
    YES/NO
    DEFAULT: NOsystec therm RAYSTAT-V5 Control Unit fig 19
    Heater operation via external contactor (only if load is not directly connected)

Display

Main display : actual temperature (xxC), setpoint temperature alternating ( txxC)

PARAMETER SETTING

Press Check button for 5 sec. to go in Parameter setting. After 30 sec. without input of parameters the unit is set back to main display.systec
therm RAYSTAT-V5 Control Unit fig 22

Escape from parameter settings.

  • Parameters
    DEFAULT: 3°C
    PiPE: 0°C … +90°C
    Air: 0°C … –30°C

  • Setpoint SP1 : Setpoint Temperature

  • Parameters PiPE Airsystec therm RAYSTAT-V5 Control Unit fig 24

  • Setpoint SP2 : Operation mode (possible to change previously selected parameter with up/down button) for pipe temperature sensing (PiPE) or ambient temperature sensing (Air). Recommendation for pipe sensing: cold water pipes: 3°C; fatty waste water pipes: 40°C.

  • Parameters: –30°C ….0°C

  • Setpoint SP3 (PASC-Air only): Lowest ambient temperature

  • Parameters DEFAULT : 01
    01 = Ø < DN 25 / 1″
    02 = Ø ≥ DN 25 / 1″
    03 = Ø ≥ DN 50 / 2″systec therm RAYSTAT-V5 Control Unit fig
26

  • Setpoint SP 4 (PASC-Air only): Average pipe diameter level

  • Parameters DEFAULT: ON
    ON/OFFsystec therm RAYSTAT-V5 Control Unit fig 27

  • Setpoint SP5: Heater operation in sensor failure mode

  • Parameters
    YES/NO
    DEFAULT: NOsystec therm RAYSTAT-V5 Control Unit fig 28

  • Setpoint SP6: Heater operation via external contactor

  • Parameters : 1-5
    DEFAULT: 1systec therm RAYSTAT-V5 Control Unit fig 29

  • Setpoint SP7 (Pipe line only): Hysteresis

  • Parameters
    OFF/–40°C
    DEFAULT: 0°C

  • Setpoint SP8 (Pipe line only): Low temperature alarm

  • Parameters
    OFF/65°C
    DEFAULT: 65°C

  • Setpoint SP9 (Pipe line only): Higher temperature alarm Recommendation: Water pipe lines: max. 65°C; Fatty waste water lines: max. 85°C.

  • Parameters:
    ON/OFF
    DEFAULT: ON

  • Setpoint SP10 Alarm sound status

  • Parameters
    YES/NO
    DEFAULT: NO

  • Setpoint SP11: Test program starts, max. 30 min duration.

  • Parameters
    Code Nr: 036
    DEFAULT: 000

  • Setpoint SP12: Activate/deactivate Key Lock / code: 036

  • Parameters
    Code Nr: 012
    DEFAULT: 000systec therm RAYSTAT-V5 Control Unit fig
35

  • Setpoint 13: Activate RESET to factory settings / code: 012. If Reset is triggered, Quick Start will be activated.
    Note : If Quick Start is not completed, unit will be set back to last settings.

ELECTRICAL SCHEME

Standard: NTC Sensorsystec therm RAYSTAT-V5 Control Unit fig
36

Option: PT100 Sensorsystec therm RAYSTAT-V5 Control Unit fig
37

  • HEATING CABLE