systec therm RAYSTAT-V5 Control Unit Installation Guide
- June 6, 2024
- systec therm
Table of Contents
systec therm RAYSTAT-V5 Control Unit
PRODUCT OVERVIEW
INSTALLATION INSTRUCTIONS
PROGRAM START – QUICK START
Quick Start
-
POWER ON : Flashing
-
Heating cable
-
Pipe/line sensing
-
Ambient sensing
-
Alarm
-
Segment Test
-
Unit name Raystat Version 5
-
Firmware Revision number
-
Parameter DEFAULT : – – – – PiPE Air
-
Quick start: Select Operation Mode for pipe line (PiPE) or ambient temperatures sensing Air – (PASC – Proportional Ambient Control sensing)
-
Parameter PiPE : 0°C… +90°C PASC: AIR (PASC) 0°C… +30°C DEFAULT: 3°C
-
Quick start : Choose Setpoint Temperature
-
Parameters DEFAULT : –20°C: –30 – 0°C
-
(PASC-Air only): Lowest ambient temperature
-
Parameters
01 = Ø < DN 25 / 1”
02 = Ø ≥ DN 25 / 1”
03 = Ø ≥ DN 50 / 2”
DEFAULT: 01
(PASC-Air only): Average pipe diameter level -
Parameters
YES/NO
DEFAULT: NO
Heater operation via external contactor (only if load is not directly connected)
Display
Main display : actual temperature (xxC), setpoint temperature alternating ( txxC)
PARAMETER SETTING
Press Check button for 5 sec. to go in Parameter setting. After 30 sec. without input of parameters the unit is set back to main display.
Escape from parameter settings.
-
Parameters
DEFAULT: 3°C
PiPE: 0°C … +90°C
Air: 0°C … –30°C -
Setpoint SP1 : Setpoint Temperature
-
Parameters PiPE Air
-
Setpoint SP2 : Operation mode (possible to change previously selected parameter with up/down button) for pipe temperature sensing (PiPE) or ambient temperature sensing (Air). Recommendation for pipe sensing: cold water pipes: 3°C; fatty waste water pipes: 40°C.
-
Parameters: –30°C ….0°C
-
Setpoint SP3 (PASC-Air only): Lowest ambient temperature
-
Parameters DEFAULT : 01
01 = Ø < DN 25 / 1″
02 = Ø ≥ DN 25 / 1″
03 = Ø ≥ DN 50 / 2″ -
Setpoint SP 4 (PASC-Air only): Average pipe diameter level
-
Parameters DEFAULT: ON
ON/OFF -
Setpoint SP5: Heater operation in sensor failure mode
-
Parameters
YES/NO
DEFAULT: NO -
Setpoint SP6: Heater operation via external contactor
-
Parameters : 1-5
DEFAULT: 1 -
Setpoint SP7 (Pipe line only): Hysteresis
-
Parameters
OFF/–40°C
DEFAULT: 0°C -
Setpoint SP8 (Pipe line only): Low temperature alarm
-
Parameters
OFF/65°C
DEFAULT: 65°C -
Setpoint SP9 (Pipe line only): Higher temperature alarm Recommendation: Water pipe lines: max. 65°C; Fatty waste water lines: max. 85°C.
-
Parameters:
ON/OFF
DEFAULT: ON -
Setpoint SP10 Alarm sound status
-
Parameters
YES/NO
DEFAULT: NO -
Setpoint SP11: Test program starts, max. 30 min duration.
-
Parameters
Code Nr: 036
DEFAULT: 000 -
Setpoint SP12: Activate/deactivate Key Lock / code: 036
-
Parameters
Code Nr: 012
DEFAULT: 000 -
Setpoint 13: Activate RESET to factory settings / code: 012. If Reset is triggered, Quick Start will be activated.
Note : If Quick Start is not completed, unit will be set back to last settings.
ELECTRICAL SCHEME
Standard: NTC Sensor
Option: PT100 Sensor