resideo 5800CMBOV Combination Smoke Carbon Monoxide (CO) Detector Installation Guide

June 6, 2024
resideo

resideo 5800CMBOV Combination Smoke Carbon Monoxide (CO) Detector Installation Guide

Quick Installation Guide

This device is intended for use with Resideo control panels that support 5800 series devices including the 5800CMBOV. Check the control for compatibility with this device. This device occupies 3 control panel zones, one zone for each service (smoke detection, heat detection, carbon monoxide detection). NOTE: This device must be installed by a qualified technician.

FEATURES

  • Multi-Criteria Sensing: uses three sensing elements to react faster while minimizing false alarms:
    – Photoelectric smoke sensor detects airborne smoke particles
    – Carbon Monoxide (CO) sensor detects CO concentrations
    – Thermal detection monitors for dangerous rise in temperature

  • CO Detector End-of-Life reporting (detector needs replacing)

  • Smoke detector maintenance reporting (detector needs cleaning or replacing)

  • Low Battery Detection

  • Low temperature sensing: senses ambient temperature and reports if temperature drops below 41°F (5°C)

  • Voice announcements (English or Spanish)

  • Supervision: The detector will transmit its status every 60 to 70 minutes.

See Installation Instructions (R800-26685) ­ www.resideo.com and the Limitations of Fire Alarm Systems Insert (800-15144), System Smoke Detectors Guide (RD-GS101-39-001; ST- QP-RD-001-039/10Y), and Limitations of Carbon Monoxide Detectors (P/N K14670V1).

LED INDICATORS

The 5800CMBOV Smoke/CO detector features a multi-color top LED:
Green = Supervisory indication; blinks during power on, reset, and during normal operation
Amber = Signal maintenance and trouble events
Red = Alarm condition (Smoke, CO or Heat)
Side LED windows indicate alarms:
Red = Smoke or Heat alarm
Blue = CO alarm
The carbon monoxide alarming circuit of this device is designed to detect carbon monoxide gas from ANY source of combustion. The carbon monoxide alarming circuit of this device is NOT designed to detect smoke, fire, or any other gases.
WARNING: This product is intended for use in ordinary indoor residential areas. It is not designed to measure compliance with commercial and industrial standards.

POWER UP and LANGUAGE SELECTION

  • Remove battery pull tab. Be sure batteries are seated properly to avoid a low battery condition after 15 seconds.
  • Upon power up, Green LED Blinks every 2 secs / Sounder is Silent. After power up, the detector prompts for language selection.
  • Select the desired language. English: Press the Smoke (·) test button Spanish: Press the CO (··) test button

resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - POWER UP and LANGUAGE SELECTION

ENROLLMENT

IMPORTANT NOTE: The Smoke and Carbon Monoxide (CO) sensors each have unique serial numbers that are enrolled in separate zones.
Enroll the Smoke Sensor

  1. Remove the detector from the base plate (tamper switch must be faulted when enrolling).
  2. Put the control panel in Zone Programming mode.
  3. Assign a zone number for the smoke detector zone. Loop = 1; Zone Type = 09 (Fire) or 16 (Fire with Verification); Input Type = 03 (Supervised RF) When prompted for the serial number, press and release the Smoke Test button for 1 second. The sensor sends two transmissions for enrolment. Alternatively, you can manually enter the smoke sensor serial number found on the unit’s label.
  4. If Maintenance monitoring is desired: VISTA-15P/20P/21iP, LYNX Touch, & Lyric: Assign a separate zone number using the Smoke Detector serial number. Loop = 2; (maintenance); Zone Type = choose a zone type based on desired operation (ex.24hr Trouble, Monitor, or Auxiliary); Input Type = 03 (Supervised RF) VISTA-128/250 Series: Enable “Smart Contact” option in zone programming menu for the assigned smoke detector zone.
  5. If Low Temperature monitoring is desired, program a separate zone for the smoke detector serial number. Loop = 3; Zone Type = choose a zone type based on desired operation (ex.24hr Trouble, Monitor, or Auxiliary); Input Type = 03 (Supervised RF).

WARNING: The fire protection zone must always be enrolled as Loop 1. Otherwise, fire alarms will not be reported by the control.

Enroll the CO Sensor

  1. Remove the detector from the base plate.

  2. With the control panel in Zone Programming mode, assign a zone number for the CO detector zone.
    Loop = 1; Zone Type =14 (CO alarm); Input Type = 03 (Supervised RF) When prompted for the serial number, press and release the CO Test button for 1 second. The sensor sends two transmissions for enrolment. Alternatively, you can manually enter the CO sensor serial number, which is the smoke serial number plus 1 (ex. if smoke s/n is 0000781, the CO s/n is 0000782).

  3. If End-of-Life monitoring is desired: VISTA-15P/20P/21iP, LYNX Touch, & Lyric: automatically sent VISTA-128/250 Series: program a separate zone for the CO serial number. Loop = 2; Zone Type = choose a zone type based on desired operation (ex.24 hr Trouble or Auxiliary); Input Type = 03 (Supervised RF).

TO SILENCE THE DETECTOR

Press the test switch. The detector sounds again after 5 minutes if the alarm condition continues.
Note: The detector cannot be silenced if the the smoke concentration exceeds 4ft% or the CO concentration exceeds 350ppm.

MOUNTING

After enrolling and before mounting permanently, conduct Go/No Go test (refer to the control panel instructions) to verify adequate signal strength with the device in its intended mounting location. Adjust the device location and orientation as necessary. Refer to Installation Guide (R800-26685) for full mounting instructions. NOTE: This device should not be located within 5 ft (1.5 m) of any cooking appliance.

resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - Ceiling & Wall

RESETTING THE LANGUAGE

  1. Press and hold both the Smoke (·) and CO (··) Test buttons simultaneously for 5 seconds until language message is announced, then release. The green LED flashes rapidly.
  2. Press the Test button corresponding to the desired language: English: Smoke (·) test button Spanish: CO (··) test button

Operation Modes

resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - Operation Modes

FUNCTIONAL TESTING

CANNED CO/SMOKE NOTE: Detector sounds an alarm when using canned smoke only when in Functional Test mode (canned smoke does not cause alarm sounding when in normal mode). Product must be tested at least once each year

resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - FUNCTIONAL TESTINGresideo 5800CMBOV
Combination Smoke Carbon Monoxide \(CO\) Detector Installation Guide -
FUNCTIONAL TESTING

PERIODIC CLEANING

NOTE: Notify the proper authorities that the smoke detector is undergoing maintenance and the system will temporarily be out of service.

resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - PERIODIC CLEANING

BATTERY REPLACEMENT

Caution: The batteries used in this device may present a fire or chemical burn hazard if mistreated. Do not recharge, disassemble, heat above 212°F (100°C) or dispose of in fire. Use only Panasonic CR123A Lithium batteries. Use of other batteries may present a risk of fire or explosion. Keep used batteries away from children. Dispose of used batteries properly. Remove old batteries. Wait 10 seconds and then replace with four new batteries. To avoid a low battery indication when installing new batteries, all 4 batteries must be installed within 15 seconds of installing the first one. Any low battery condition that may have occurred should clear when the backplate is installed.
NOTE: Constant exposure to high or low temperature or high humidity may reduce battery life.
resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - BATTERY REPLACEMENT
LED Indication & Sounder During Test and Trouble

resideo 5800CMBOV Combination Smoke Carbon Monoxide \(CO\) Detector
Installation Guide - LED Indication & Sounder During Test and
Trouble

  • 1a Test activated by pressing and releasing the test switch; Detector is functioning properly (within proper sensitivity). See Functional Test section for Functional Test activation and procedure
  • 1b If Test mode is activated and the LED and Sounder do not function, check for maintenance or trouble conditions.
  • 2 Starts chirping after 30 days, continues until the batteries are replaced or die
  • 3 See Periodic Cleaning section. If maintenance trouble condition persists, the detector may need to be replaced.

SPECIFICATIONS

Battery …. 4 x 3V, CR123A Lithium/Litio; Panasonic CR123A only
Sensitivity…. UL limits 0.9 to 3.50%/ft ; ULC limits 0.9 to 3.08%/ft
Heat alarm …. 135° F (57° C) / 57° C (135° F)
Freeze trouble …. 41° F (5° C) / 5° C (41° F)
Audible Signal …. 85dBA
Dimensions … 6.2 in. Diameter x 1.99 in. Depth
Weight .. 14.3 oz; 406 g
Tamper .. Cover
Operating Temperature …. 32° to 100° F
Storage Temperature .. 14° to 158° F / -10° a 70° C
Relative Humidity . 95% max, non-condensing

2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 © 2021 Resideo Technologies, Inc.
www.resideo.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals