GENERAC 5464 21 Light Surface Mount Remote Annunciator Panel with 8 Relays HTS Owner’s Manual
- June 6, 2024
- Generac
Table of Contents
- GENERAC 5464 21 Light Surface Mount Remote Annunciator Panel with 8
- ANNUNCIATOR DESCRIPTION
- DETAILED SPECIFICATIONS
- INSTALLATION AND MOUNTING
- PARAMETER SELECTION EXAMPLES
- GENERATOR STOP INDICATORS
- SPARE INDICATOR
- SYSTEM KEYPAD SWITCHES
- OTHER FUNCTIONS
- SERIAL INTERFACE
- TERMINOLOGY & ABBREVIATIONS
- TROUBLESHOOTING GUIDE
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
GENERAC 5464 21 Light Surface Mount Remote Annunciator Panel with 8
Relays HTS
ANNUNCIATOR DESCRIPTION
The remote annunciator is available in the following versions:
- 0G5719 – Remote Annunciator has both relays and LEDs/Keypad (RRP & RAP)
- 0G5720 – RRP version – Remote Relay Panel (Relays with no LEDs/Keypad)
- 0G5721 – RAP version – Remote Annunciator Panel (LED’s/Keypad without relays J1 – J8)
The Remote Annunciator provides remote monitoring and annunciation of up to 18 generator parameters using the lights/LEDs located on the annunciator keypad. Selected generator parameters can be annunciated using the eight Form A relays provided on 0G5719 and 0G5720.
The Remote Annunciator also provides two system-level warn-ings which are System Ready and Communications OK. Multiple annunciators can also be connected to obtain remote monitor-ing and annunciation of all 18 generator parameters. Power to the remote annunciator is supplied from the generator battery (+ 12VDC or + 24VDC).
Communication with the Remote Annunciator is via an RS485 serial data link. The remote annunciator is typically configured for listen-only mode (also called slave or passive mode). In this operat-ing mode, the annunciator receives information on the generator status, from the generator controller and activates/deactivates the relay outputs to reflect the status of up to eight selected generator parameters. The remote annunciator can also be configured to request status information from the generator (called master or active mode).
The specific faults to be annunciated using the relay outputs (J1 – J8) can be selected using either the DIP switches located on the annunciator printed circuit board, or the Graphical User Interface (GUI) available using a computer via the RS232 connector on the annunciator printed circuit board (see Figure 2). Relays J1 – J8 provides a set of normally open contacts. All relays are energized (contacts closed) when power is applied to the annunciator. The relay selected to annunciate a particular fault will then open during a fault.
The terminal block connections (J10), used to connect the battery supply and the RS485 communication lines to the remote annun-ciator are shown in Figure
- The location of DIP switches S1, S2, S3 and S4 and the RS232 connector are shown in Figure 2.
DETAILED SPECIFICATIONS
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature – 25°C (-13°F) to + 60°C (140°F) Humidity 0 to 95% Non Condensing
POWER SUPPLY REQUIREMENTS
- Power Supply Source: Generator Battery to comply with NFPA
- Power Supply Voltage: + 12 or + 24VDC (Annunciator operating range is 6V to 30VDC
- Power UsagE: 6 Watts (typical when all the relays and keypad are energized)
- Power Supply Cable: 2 wire – Voltage drop across each conductor must be less that 1V.
COMMUNICATION WITH GENERATOR CONTROL SYSTEM
- Communication Link: 2 wire RS485 fully isolated.
- Communication Cable: 2 wire RS485 — twisted-pair with overall shield/screen (i.e. Belden 3105A).
- Maximum Cable: Length 4,000 feet
- Baud rate Auto-detect: at 57.6K, 38.4K, 9600 or 4800 (no parity,
NOTE:
- The RS485 cable should not be run in the same conduit, or in the same wire grouping as any high voltage or high current conductors.
- The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 communication line.
RELAY OUTPUTS (J1-J8) – 0G5719 & 0G5720 ONLY
- Contact per Channel One Normally Open contact. Energized when annunciator is powered and no faults are present.
- Maximum contact rating: 30VDC/1A
ALARM RELAY OUTPUT (J9)
- Contact Type SPDT (N.O. & N.C. contacts) Energized when annunciator is powered and no faults are present.
- Maximum contact rating: 30VDC/1A
TRANSPORTATION AND STORAGE
Temperature: 30°C (-22°F) to + 80°C (176°F) Humidity 0 to 95% Non Condensing
INSTALLATION AND MOUNTING
- F or ALL models installation must always comply with applicable codes, standards, laws, and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, the generator and related components must be installed completely in conformance with the manufacturer’s instruc-tions and recommendations. Following proper installation, do nothing that might alter a safe installation and render the unit in non-compliance with such codes, standards, laws and regulations.
- The plastic knockout that is used to route the wires and cables into the annunciator should be removed with the annunciator firmly supported by placing it on a flat surface.
- q Wire tie-downs are provided in two places on the base of the annunciator to provide strain-relief for the connecting cables and wires (Figure 3).
RELAY ANNUNCIATION (J1 – J8)
The user can select up to eight of the following 18 generator parameters to
annunciate via the relays when the 10 positions (S1) and the 8 positions (S2)
DIP switches on the annunciator PCB are being used.
S1 | Parameter | S2 | Parameter |
---|---|---|---|
1 | RPM Sensor Loss | 1 | Battery Charger AC Failure |
2 | Overcrank | 2 | Low Battery Voltage |
3 | Overspeed | 3 | High Battery Voltage |
4 | Low Oil Pressure | 4 | Generator Run |
5 | High Water Temp/Low Water Level | 5 | Generator Power |
6 | Emergency Stop | 6 | Not in Auto |
7 | Pre-Low Oil Pressure | 7 | Line Power |
8 | Pre-High Water Temp | 8 | Spare Channel |
9 | Pre-Low Water Temp | ||
10 | Pre-Low Fuel |
Relay outputs J1 through J8 are assigned to the selected param-eters in sequential order. For example, if DIP1 – 1 through 8 are selected, these faults are assigned to relays 1 through 8 respec-tively as shown in Figures 4 and 5.
Figure 4 — DIP Switch S1 Settings
Figure 5 — DIP Switch S2 Settings
NOTE:
If a unit is wired up and then subsequently an additional DIP switch position
is selected or deselected, all the relay outputs are re-assigned sequentially
and therefore the annunciator terminals may require re-wiring.
PARAMETER SELECTION EXAMPLES
Example 1
DIP S1-1, 3, 5, 10 are initially selected, these are assigned to relays 1, 2,
3, 4 (Figures 6 and 7).
DIP | Parameter | Relay |
---|---|---|
1, 1 | RPM Sensor Loss | 1 |
1, 3 | Overspeed | 2 |
1, 5 | High Water Temp/Low Water Level | 3 |
1, 10 | Pre-Low Fuel | 4 |
Figure 6 — S1
Figure 7 — S2
Example 2
If subsequently DIP1-3 is removed, and DIP2-5 is added, then relays will be
re-assigned (Figures 8 and 9).
DIP | Parameter | Relay |
---|---|---|
1, 1 | RPM Sensor Loss | 1 |
1, 5 | High Water Temp/Low Water Level | 2 |
1, 10 | Pre-Low Fuel | 3 |
2, 5 | Generator Power | 4 |
Figure 8 — S1
PARAMETERS S1.1 – S1.10 & S2.1 – S2.3
When a remote annunciator (0G5719) or Remote Relay Panel (0G5720) is used in
a Modular Power System (MPS), an alarm on any one of the generators causes the
associated relay to activate.
PARAMETER “GENERATOR RUN”
This parameter is defined as any one or more generators in the system
running.
PARAMETER “GENERATOR POWER”
This light/LED indicates different things depending on the type of system
it is attached to.
- It is defined as whether the Transfer Switch is in the Generator Supply Position.
- For a PowerManager System Controller (PM-SC with external transfer switch(es)), generator power is defined as anyone or more generators in the system running and connected to the generator bus.
- For a non-paralleling engine controller (PM-GC WITHOUT internal transfer switch), it represents the status of input 4 (TB2-5) to the generator controller. This should be connected to the generator side auxiliary contact of the external transfer switch. A closure to the ground will cause the light to illuminate. This shows whether the load is powered by the generator.
- For an engine controller that is part of an MPS system, generator power represents the state of the internal contactor that the generator is connected to.
PARAMETER “LINE POWER”
This light/LED indicates different things depending on the type of system
it is attached to.
- Is defined as whether the Transfer Switch is in the Utility Supply Position.
- For a Power Manager System Controller (PM-SC with external transfer switch(es)), line power represents the auxiliary input C (TB6-4).
- For a non-paralleling engine controller (PM-GC WITHOUT inter-nal transfer switch), it represents the status of input 3 (TB2-4) to the generator controller. This should be connected to the utility side auxiliary contact of the external transfer switch. A closure to ground will cause the light to turn ON. This shows whether the load is power by the utility.
- For an engine controller that is part of an MPS system, line power is not used.
PARAMETER “BATTERY CHARGER AC FAILURE”
This light/LED annunciates upon loss of 120VAC power supply to the battery
charger and is communicated to the Annunciator by the generator controller.
GENERATOR STOP INDICATORS
These lights/LEDs will flash when any alarm occurs and the horn will sound as follows:
Annunciator Light | Light Color | Audible Alarm |
---|---|---|
RPM Sensor Loss | Red | Yes |
Overcrank | Red | Yes |
Overspeed | Red | Yes |
Low Oil Pressure | Red | Yes |
High Water Temp | Red | Yes |
Low Water Level | Red | Yes |
Emergency Stop | Red | Yes |
NOTE:
Both the High Water Temp and the Low Water Level LEDs will turn ON if
either fault condition is present. The “Re-arm Horn” switch can be used to
turn off and re-arm the horn, or the alarms can be fully acknowledged using
the “Reset” switch. The “Reset” switch will turn off and re-arm the horn, and
any flash-ing lights will switch to the ON state until the alarms are no
longer present at the generator control panel.
NOTE:
- The alarm condition must be reset at the generator control panel.
- When this annunciator is used in a Modular Power System (MPS), an alarm on any one of the generators will cause the lights/LEDs to light, and alarms to sound.
WARNING INDICATORS
These lights/LEDs will flash when any alarm occurs and the horn will sound
according to the following table:
Annunciator Light| Light Color| Audible Alarm|
Latched
---|---|---|---
Pre-low Oil Pressure| Yellow| Yes| Yes
Pre-high Water Temp| Yellow| Yes| Yes
Pre-low Water Temp| Yellow| Yes| Yes
Pre-low Fuel| Yellow| Yes| Yes
Battery Charger AC Failure| Yellow| Yes| No
Low Battery Voltage| Yellow| Yes| No
High Battery Voltage| Yellow| No| No
Generator Run| Yellow| No| No
Generator Power| Yellow| No| No
Not in Auto| Red| Yes| No
These alarms will be latched/not latched by the annunciator according to the above table. They can be acknowledged at the annunciator using the ‘Reset’ switch— the active lamps will then stop flashing and remain in the ON state until the alarm signal clears from the generator control panel. The “Reset” switch will also turn off and re-arm the horn.
NOTE:
- These lights can only be fully reset when the alarm state is no longer active and “Reset” has been pressed at both the generator control panel and the remote annunciator. Alternatively, at any time the horn can be turned OFF and re-armed with the “Re-Arm Horn” switch.
- When this annunciator is used in a Modular Power System (MPS), a warning on any one of the generators will cause the above lights to light, and alarm to sound (if the warning is audible).
SPARE INDICATOR
The spare indicator light/LED can be activated from the PM-GC or PM-SC by using the Integrated Logic Controller (ILC) feature in the G-panel or H-panel. Also see the section in this manual describing the operation and set-up of the spare keypad switch.
Annunciator Light | Light Color | Audible Alarm |
---|---|---|
System Ready | Green | Yes |
Communication OK | Green | Yes |
Line Power | Green | No |
Spare | Green | No |
SYSTEM STATUS INDICATORS
These lights/LEDs are for Status indication only— the normal condition is ON.
SYSTEM READY
The System Ready is defined as ALL “in service” generators are ready to
start, run, and supply power. Any generators manually declared as “out of
service” will not affect this LED.
Upon a loss of System Ready, the annunciator will respond as follows:
- The System Ready LED will begin to flash.
- The alarm will sound. The “Re-arm Horn” switch can be used to turn off and re-arm the horn, or the alarm can be fully acknowledged using the reset switch at which time the System Ready LED will turn off and remain off until the System Ready status is returned.
COMMUNICATION OK:
This LED will be ON as long as there is proper communication between the
Remote Annunciator Panel and the Generator control system. It typically
requires less than a minute for the Annunciator to determine the correct baud
rate and connect to the RS485 bus. When communication failure occurs, the
Annunciator will flash the communication LED, and sound the horn. The rate of
flashing will be indicative of the cause of error.
- No reply from the generator control system, Frequency = one second ON/one second OFF
- Consecutive data errors, Frequency = 0.5 second ON/two seconds OFF.
This alarm condition can be acknowledged at the Annunciator using the “reset” switch – the horn will be turned off and re-armed, and the communication OK light will continue to flash until proper communication returns.
GREEN STATUS LED (INTERNAL TO UNIT)
- If the green LED is flashing at a one-second on and one-second off rate, the unit is operational and is configured from the Windows Graphical User Interface.
- If the green LED is flashing at a one-second off and five seconds on rate, the unit is operational and is configured from the DIP switches.
- If the green LED is flashing at a half-second on and five seconds off rate, the unit is operational but there are no RS485 communications.
- If the unit is powered for 30 seconds and the Green Status LED does not turn on at all during this time, the circuit board is not functional.
SYSTEM KEYPAD SWITCHES
TEST SWITCH
While the test switch is pressed, all lights/LEDs will light and the horn
will sound. When released the lights/LEDs will return to their original
status. During this test, communication to the generator control system will
be suspended.
RE-ARM HORN SWITCH
The re-arm horn switch will silence the alarm horn and re-arm it for new
alarm occurrences.
RESET SWITCH
The reset switch is used to acknowledge any active alarms. It will re-set
any flashing light/LED’s to a ON (steady) condition (or OFF for normally on
lights). If the alarm no longer exists and it has also been latched OFF at the
generator control panel (pre-alarm indicators only) the active light will go
OFF. It will also silence the horn and re-arm it for new occurrences.
NOTE:
Pre-alarm conditions MUST be reset at the generator set control panel.
SPARE KEYPAD SWITCH
When DIP Switch S3, Position 4, is in the ON position, it allows the SPARE
Keypad Switch to control Relay 8. When this DIP switch is in the ON position,
pushing the SPARE keypad Switch will energize Relay 8 and turn on the spare
light/LED on the keypad. Pushing the SPARE keypad Switch again will de-
energize Relay 8 and turn off the spare light/LED.
NOTE:
The Remote Start capability using the Spare Keypad Switch and Relay 8 is
only available when Remote Annunciator version P/N 0G5719 is used.
OTHER FUNCTIONS
GRAPHICAL USER INTERFACE (GUI) OR DIP
SWITCHES ENABLED – DIP SWITCH S3-1
When Position 1 is in the ON position the Graphical User Interface (GUI) must
be used to set the relay fault conditions. When Position 1 is in the OFF
position the DIP switches on the Annunciator control board must be used to set
the relay fault conditions.
MASTER/SLAVE MODE – DIP SWITCH S3-3
Position 3 is used to configure the Annunciator as either a Slave (OFF
position) or as a Master (ON position). In Slave mode, it is a Modbus slave
and must be connected to a master port on the PM-GC or PM-SC. This method
allows for the connection of more than one Annunciator. In Master mode, the
Annunciator is the Modbus master and will request data from the PM-GC or PM-
SC. The PM-GC or PM-SC must be set as a slave port when the Annunciator is
configured as the Master (Figures 10 and 11).
Figure 10 — Annunciators connected to an
H-panel or G-panel Engine Controller
Figure 11 — Annunciator’s connected to a System Controller (SC) and Multiple G-panels
SPARE KEYPAD SWITCH – DIP SWITCH S3-
Position 4, when it is in the ON position, it allows the SPARE Keypad
Switch to control Relay 8. When this DIP switch is in the ON position, pushing
the SPARE keypad Switch will energize Relay 8 and turn on the spare LED on the
keypad. Pushing the SPARE keypad Switch again will de-energize Relay 8 and
turn off the SPARE LED. This feature can be used to implement a Remote Start
function. This Remote Start feature is only available with the Remote
Annunciator version (0G5719) that has both the Relays and the Keypad.
BAUD RATE SELECTION (DIP SWITCH S4)
DIP Switch S4 can be used to set the Communications Baud Rate to a pre-
determined value (see table).
S4-1 | S4-2 | Baud Rate |
---|---|---|
OFF | OFF | Auto-Baud Rate detect (max rate is 57600) |
OFF | ON | 38400 |
ON | OFF | 9600 |
ON | ON | 4800 |
ALARM RELAY (J9)
The Annunciator provides a relay with both a Normally Open con-tact and a
Normally Closed contact. This relay is energized when DC power is provided to
the Annunciator so that in the event power to the Annunciator fails the relay
contacts will change state. When the Audible alarm is activated this relay
will be de-energized.
RS485 LINE TERMINATION RESISTOR
A 1000 ohm RS485 terminating resistor is installed on the Remote
Annunciator PC board via a 3-position jumper (JMP1 in Figure 2). In most
applications, this 1000 ohm terminating resistor is connected and the jumper
(JMP1) is in the closed or 1-2 position. This jumper can also be moved to the
open or 2-3 position
GRAPHICAL USER INTERFACE (GUI)
A DB9 connector is provided on the Annunciator Control Board for use in
setting the Annunciator functions. A GenBank serial cable (P/N 0F7707) should
be used to connect a laptop computer’s RS232 serial port to the Annunciator
DB9 connector. The GenBank cable is a Null-Modem style serial cable with
female-to-female DB9 connectors.
Shown in Figure 12 is a typical Windows GUI interface as it appears on the computer display.
RS485 COMMUNICATIONS
In a typical application, the Annunciator monitors (i.e. slave mode) the
Generator control system via the RS485 communication line.
SERIAL INTERFACE
Baud Rate: Auto-Detect 57.6K, 38.4K, 9600 or 4800 (No Parity, 2 Stop Bits)
COMMUNICATIONS CONNECT TIME
When an Annunciator is powered up onto an existing RS485 network, there
will be a period of time, during which the unit may report a “communication
failure”. During this time the Annunciator is searching for the correct Baud
rate. The Annunciator will typi-cally communicate within one minute after
being connected.
Figure 12 — Annunciator GUI Interface Display
ERROR HANDLING:
An error will be reported by flashing the Communication OK light—the rate
of flashing will be indicative of the cause of the error.
- No reply from generator control system— frequency one second on/one second off.
- Consecutive data errors— frequency 0.5 seconds on/two seconds off.
The Annunciator, if configured for auto-baud rate detect, will try several times at each of four different baud rates (57.6K, 38.4K, 9600 and 4800) before reporting a communication error by de-energizing all the relays and then flashing the Communication OK light.
LIMITS OF OPERATION
The following communication restrictions apply for multiple units on a
common RS485 line:
- A maximum of 15, 1000 ohm RS485 Loads (i.e. 57.6K Annunciator, G-panel, H-panels, etc) can be connected to the RS485 bus at one time.
NOTE:
There MUST be only ONE (1) master in the RS485 communication bus. All
others must be slaves (PASSIVE).
TERMINOLOGY & ABBREVIATIONS
- GUI: Graphical User Interface for Windows-based computers
- MPS: Modular Power System
- PM-GC: Power Manager – Generator Controller (controls a single Generator)
- PM-SC: Power Manager – System Controller (used to control multiple Generators)
- LEDs: – Light Emitting Diodes
- GenBank: Generator communication system
- ILC: Integrated Logic Controller
- RRP: Remote Relay Panel (Relays with no LEDs/Keypad), 0G5720\
- RAP: Remote Annunciator Panel (LEDs/Keypad without Relays J1 – J8), 0G5721
TROUBLESHOOTING GUIDE
No Lights/LEDs are Lit.| 1. Check for the proper battery supply at terminal block J10 pins 1 and 2.
• J10 pin 1 should be + Battery (12 or 24 volts).
• J10 pin 2 should be – Battery.
• Refer to the “ power supply requirements” section at the beginning of the manual for cable specifications.
---|---
|
The “ Communication OK” LED is flash- ing at the rate: second ON/one second
OFF.| 1. Does the RS485 communications cable meet specifications. Refer to
the “ Communication
with generator control system” section at the beginning of this manual.
2. Check that the RS485 connections are connected properly.
• RS485+ connected to J10 pin 5.
• RS485– connected to J10 pin 6.
• Is the Shield/screen connected correctly. The shield/ screen should be connected at the Generator end only.
3. Check for proper installation of the RS485 cable between the Annunciator and the genera- tor’s control panel. Is this cable sharing a conduit or running next to any high voltage or
high current electrical lines?
4. Use the Generator Controller GenLink communication diagnostics to check if data is being sent or received via the Tx and Rx check boxes. Go to the pull- down menu for diagnostics and select “ Com Ports” . Select the port the Annunciator is connected to (normally port
- and look to see if the check boxes change state. If not, data is not being transmitted/ received, check the cabling. If data is being received, check the baud rate settings of all
connected equipment.
|
The “ Communication OK” LED is flash- ing at the rate: 0.5 seconds ON/two
seconds OFF.| 1. Does the RS485 communications cable meet specifications?
Refer to the “ Communication
with generator control system” section at the beginning of this manual.
2. Is the cable shield connected correctly? The shield/ screen should be connected at the
Generator end only.
3. Check for proper installation of the RS485 cable between the Annunciator and the genera- tor’s control panel. Is this cable sharing a conduit or running next to any high voltage or
high current electrical lines?
4. Use Generator Controller GenLink communication diagnostics to check if data is being sent or received via the Tx and Rx check boxes. Go to the pull- down menu for diagnostics and select “ Com Ports” . Select the port the Annunciator is connected to (normally port 0) and look to see if the check boxes change state. If not, data is not being transmitted/received, check the cabling. If data is being received, check the baud rate settings of all connected
equipment.
The “Green Status LED” (internal to the unit) is flashing at a 0.5 second ON/5
second OFF rate.
| 1. The RS485 Communications is not functioning. See items 1-4 above.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>