SONBEST SM8700 Non-Contact Infrared Temperature Sensor User Manual

June 6, 2024
SONBEST

SM8700
Non-contact infrared temperature sensor
User Manual
File Version: V21.3.24
SONBEST SM8700 No Contact Infrared Temperature Sensor

SM8700 uses the standard, easy access to PLC, DCS, and other instruments or systems for monitoring temperature state quantities. The internal use of high- precision sensing core and related devices to ensure high reliability and excellent long-term stability can be customized RS232, RS485, CAN,4-20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.

Technical Parameters

Technical parameter Parameter value
Brand SONBEST
Temperature measurement range  0~+200°C (Max 300℃)
Temperature measurement accuracy  ± 1 or %1 take the maximum value (maximum ±

3°C)
Repeat measurement accuracy|  ± 0.5 or %0.5 take the maximum value (maximum ± 2°C)
Optical Resolution|  1.6:1
Spectral range|  18-14um
Response time|  100ms
Emissivity| 0.96
Interface| RS485/4-20mA/DC0-5V/DC0-10V
Power| DC12~24V 1A
Dimensions| Φ24mm× 80mm

Product Selection
Product DesignRS485,4-20mA,DC0-5V,DC0-10VMultiple output methods, the products are divided into the following models depending on the output method.

Product model  output method
SM8700B RS485
SM8700M 4-20mA
SM8700V5 DC0-5V
SM8700V10 DC0-10V

How to wiring?

SONBEST SM8700 No Contact Infrared Temperature Sensor -
use

**All need me Various places

**

Real-time monitoring every day, a wide range of applications, high detection efficiency, stability, and reliability, can be used in various indoor environments such as hospitals, factories, warehouses, shopping malls, etc.

SONBEST SM8700 No Contact Infrared Temperature Sensor -
fig1

  • Boiler
    The boiler room refers to the machine room where auxiliary equipment such as boilers and pumps are placed. Generally used for heating and production.
    SONBEST SM8700 No Contact Infrared Temperature Sensor -
fig2

  • Steel milk
    Long-term high-temperature working environment Need to monitor ambient temperature at any time to prevent accidents
    SONBEST SM8700 No Contact Infrared Temperature Sensor -
fig3

  • Power station
    A place with a lot of heat If you don’t pay attention, it is easy to cause accidents. Need to configure instruments for long-term monitoring

Fast and convenient Wiring application

The data line has simple wiring fast response speed high data transmission efficiency long term stability and reliability and excellent performance
RS485 wiring mode

SONBEST SM8700 No Contact Infrared Temperature Sensor -
transfar1| SONBEST SM8700
No Contact Infrared Temperature Sensor - transfar2
---|---
SONBEST SM8700 No Contact Infrared Temperature Sensor -
transfar3

Communication

Protocol

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1

  1. Read Data (Function id 0x03)
    Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 01 84 0A. Device ID| Function id| Start Address| Data Length| CRC16
    ---|---|---|---|---
    1| 3| 00 00| 00 01| 84 0A
    For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6, the response format is parsed as follows:
    Device ID| Function id| Data Length| 1| Check Code
    1| 3| 2| 00 79| 79 A6

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21.
Others and so on.

  1. Data Address Table
    Address| Start Address| Description| Data type| Value range
    ---|---|---|---|---
    40001| 00 00| 1#temperatureregister| Read only| 0~65535
    40101| 00 64| model code| read/write| 0~65535
    40102| 00 65| total points| read/write| 1~20
    40103| 00 66| Device ID| read/write| 1~249
    40104| 00 67| baud rate| read/write| 0~6
    40105| 00 68| mode| read/write| 1~4
    40106| 00 69| protocol| read/write| 1~10
  2. ead and modify device address
    (1) Read or query device address
    If you don’t know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address. Device ID| Function id| Start Address| Data Length| CRC16
    ---|---|---|---|---
    FA| 3| 00 64| 00 02| 90 5F

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.
For the correct query command, the device will respond, for example, the response data is 01 03 02 07 12 3A 79, the format of which is shown in the following table:

Device ID| Function id| Start Address| Model Code| CRC16
---|---|---|---|---
1| 3| 2| 55 3C 00 01| 3A 79

The response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device’s main model is 21820, and the last two bytes 00 01 Indicates that the device has a status quantity.
(2)Change device address
For example, if the current device address is 1, we want to change it to 02, the command is:01 06 00 66 00 02 E8 14.

Device ID| Function id| Start Address| Destination| CRC16
---|---|---|---|---
1| 06| 00 66| 00 02| E8 14

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27, its format is parsed as shown in the following table:

Device ID| Function id| Start Address| Destination| CRC16
---|---|---|---|---
1| 06| 00 66| 00 02| E8 27

The response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.
Read and Modify Baud Rate
(1) Read baud rate
The device’s default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5, and its format is parsed as follows

Device ID| Function id| Start Address| Data Length| CRC16
---|---|---|---|---
1| 03| 00 67| 00 01| 35D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the response data is 01 03 02 00 03 F8 45, the format of which is as shown in the following table:

Device ID Function id Data Length Rate ID CRC16
1 03 02 00 03 F8 45

coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.
(2)Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15.

Device ID| Function id| Start Address| Target Baud Rate| CRC16
---|---|---|---|---
1| 06| 00 66| 00 01| 64 15

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

  1. Read Correction Value
    (1) Read Correction Value
     When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters. Device ID| Function id| Start Address| Data Length| CRC16
    ---|---|---|---|---
    1| 03| 00 6B| 00 02| F5 D6

For the correct query command, the device will respond, for example, the response data is 01 03 02 00 64 B9 AF, the format of which is shown in the following table:

Device ID| Function id| Data Length| Data value| CRC16
---|---|---|---|---
1| 03| 02| 00 64| B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, and humidity have this parameter, the light generally does not have this item.
(2)Change correction value
For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD.

Device ID| Function id| Start Address| Destination| CRC16
---|---|---|---|---
1| 06| 00 6B| 00 64| F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after a successful change.
For example, the range is 0~200℃, the analog output is 4~20mA current signal, temperature, and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated current value. The list of commonly used values is as follows:

current(mA) temperatureValue (℃) Calculation Process
4 0 (200-0)*(4-4)÷ (20-4)+0
5 12.5 (200-0)*(5-4)÷ (20-4)+0
6 25 (200-0)*(6-4)÷ (20-4)+0
7 37.5 (200-0)*(7-4)÷ (20-4)+0
8 50 (200-0)*(8-4)÷ (20-4)+0
9 62.5 (200-0)*(9-4)÷ (20-4)+0
10 75 (200-0)*(10-4)÷ (20-4)+0
11 87.5 (200-0)*(11-4)÷ (20-4)+0
12 100 (200-0)*(12-4)÷ (20-4)+0
13 112.5 (200-0)*(13-4)÷ (20-4)+0
14 125 (200-0)*(14-4)÷ (20-4)+0
15 137.5 (200-0)*(15-4)÷ (20-4)+0
16 150 (200-0)*(16-4)÷ (20-4)+0
17 162.5 (200-0)*(17-4)÷ (20-4)+0
18 175 (200-0)*(18-4)÷ (20-4)+0
19 187.5 (200-0)*(19-4)÷ (20-4)+0
20 200 (200-0)*(20-4)÷ (20-4)+0

As shown in the above formula, when measuring 8mA, current is 54℃。

For example, the range is 0~200℃, the analog output is 0~5V voltage signal, temperature, and voltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is voltage output range upper limit, B1 is the lower limit, X is the currently read

voltage(V) temperature value (℃) Calculation Process
0 0 (200-0)*(0-0)÷ (5-0)+0
1 40 (200-0)*(1-0)÷ (5-0)+0
2 80 (200-0)*(2-0)÷ (5-0)+0
3 120 (200-0)*(3-0)÷ (5-0)+0
4 160 (200-0)*(4-0)÷ (5-0)+0
5 200 (200-0)*(5-0)÷ (5-0)+0

temperature value and C is the calculated voltage value. The list of commonly used values is as follows:
As shown in the above formula, when measuring 2.5V, the current voltage is 100℃。
For example, the range is 0~200℃, the analog output is 0~10V voltage signal, temperature, and voltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is voltage output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated voltage value. The list of commonly used values is as follows:

voltage(V) temperature value (℃) Calculation Process
0 0 (200-0)*(0-0)÷ (10-0)+0
1 20 (200-0)*(1-0)÷ (10-0)+0
2 40 (200-0)*(2-0)÷ (10-0)+0
3 60 (200-0)*(3-0)÷ (10-0)+0
4 80 (200-0)*(4-0)÷ (10-0)+0
5 100 (200-0)*(5-0)÷ (10-0)+0
6 120 (200-0)*(6-0)÷ (10-0)+0
7 140 (200-0)*(7-0)÷ (10-0)+0
8 160 (200-0)*(8-0)÷ (10-0)+0
9 180 (200-0)*(9-0)÷ (10-0)+0
10 200 (200-0)*(10-0)÷ (10-0)+0

As shown in the above formula, when measuring 5V, the current voltage is 100℃。

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability, or the infringement liability for any patent, copyright, or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd
Address: Building 8, No.215 Northeast Road, Baoshan District, Shanghai,China
Web : http://www.sonbest.com
Web: http://www.sonbus.com
SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

Sha nghai Sonbest Industrial Co., Ltd
User Manual
SM8700
http://www.sonbus.com/

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SONBEST User Manuals

Related Manuals