GF 565 Butterfly Valve Instruction Manual
- October 27, 2023
- GF
Table of Contents
GF 565 Butterfly Valve
Our General Terms of Sale apply.
Related documents | Doc. no. |
---|---|
Instruction manual Butterfly valve Type 565 | 700278128 |
Instruction manual Electric Actuator EA25-250 | 700278109 |
Instruction manual Pneumatic Actuator Unit PA30- PA90 | 700278115 |
Instruction manual Smart Actuator dEA | 700278110 |
GF Planning Fundamentals Industry | 700671687 |
EC Declaration of conformity
The manufacturer Georg Fischer Rohrleitungssysteme AG, 8201 Schaffhausen
(Switzerland) declares that the subsequently listed machines are machines
according to the listed unifying design standard in terms of the EC Machine
Directive 2006/42/EC and comply with the requirements of this directive that
apply to machines. The technical documentation for machines has been compiled
in accordance with Annex VII, Section A of this directive and the CE labels on
the machines also indicate this conformity. Furthermore, we declare that the
machines are compatible with the applicable provisions of other stated EU
directives. Modifications to the products that affect the specified technical
data and the intended use make this declaration of conformity invalid.
Additional information can be found in the “GF planning fundamentals.”
Intended use
Actuated industrial valves are exclusively intended to shut off, pass through
or control the flow of approved media within the approved pressure and
temperature limits in a piping system for industrial purposes. The maximum
time of operation is 25 years.
Installation process according to the following configurations
- Bring the actuator and valve in the same position.
- Attach the intermediate element or manual override to the actuator using the included screws.
- Attach the actuator via the intermediate element or manual override to the valve.
Meaning of the signal words
WARNING! Possible danger!
Non-observance may result in serious injuries.
CAUTION! Dangerous situation!
Non-observance may result in minor injuries.
NOTICE! Avoid the situation!
Non-observance will lead to a risk of damage to property.
Abbreviations
FC | Function Failsafe Closed |
---|---|
FO | Function Failsafe Open |
DA | Function Double Acting |
DN | Nominal Diameter |
PA | Pneumatic Actuator |
EA | Electric Actuator |
dEA | Electric Smart Actuator |
General safety information
Observe instruction manual!
The instruction manual is part of the product and an important component
within the safety concept. Non-observance may lead to severe injuries.
- Read and observe instruction manual.
- Always have instruction manual available by the product.
- Give instruction manual to all subsequent users of the product.
Commissioning and use by qualified personnel only!
- Product and accessories shall only be put into operation by persons who have the required training, knowledge or experience.
- Regularly instruct personnel on all questions regarding the local regulations applying to occupational safety and environmental protection, especially for pressurized pipes.
Storage and transport!
The product must be handled, transported and stored with care. Please note the
following points:
- Transport and store the product in its unopened original packing.
- Protect the product from harmful physical influences such as dust, heat, humidity and UV radiation.
- The product and its components must not be damaged either by mechanical or thermal influences.
- Store the product in the delivery state.
- Check the product for general damage prior to installation.
CAUTION!
Use only original parts!
Risk of material damage and/or injury due to non-compatible spare parts.
- Only use original spare parts from GF Piping Systems.
- Order spare parts using the information on the type plate.
- Do not use defective spare parts.
WARNING! Do not use damaged products!
Danger of injury or material damage through the use of defective or damaged
products.
- Do not use a damaged or defective product.
- Replace any damaged or defective products immediately.
CAUTION! Leaking gaskets!
The danger of injury by leaking medium due to damaged or aged gaskets.
- Store gaskets if possible in a cool, dry and dark place.
- Before installing them, the gaskets have to be checked on possible ageing damages, such as fissures and hardenings.
- Regularly check the gaskets and replace, where necessary.
Warnings for actuators in general
WARNING! Pinching during operation!
Risk of injury by pinching of body parts!
- Never enter fingers, hands or other body parts into the opening of the valve when the actuator is active. CAUTION!
Non-compatible actuator!
Faulty opening/closing or increased wear due to non-observance of the valve
and actuator specifications.
- Observe the specifications for the valve and actuator.
- Only install the actuator intended for the valve.
WARNING! Moving parts of the manual override!
During operation, body parts must not be introduced into the movement radius
of the manual override Observe the movement radius of the manual override.
Warnings for electric actuators
WARNING! Risk of injury or damage.
Possible electric shocks or damage to the actuator by short circuit.
- Connect the actuator only according to the connection diagram of the instruction manual.
- Connect wire only via the included cable glands.
- The available protective earth (PE) must be connected to the main circuit board and 2.5 cm longer than the power lines (last contact in case of failure of the cable gland).
- Use insulated ring terminals suitable for the diameter of the connection wires (for 0.5 – 1.5 mm2 wires, ring diameter 0.5 cm).
WARNING! Risk of injury due to faulty power supply!
Do not connect faulty or mixed power potentials or power sources.
- Either connect 230 VAC or 24 VDC (depending on the actuator type) to the return relay.
- Make sure that the power supply is only provided from a single power source.
WARNING! Risk of injury or damage when the lid is removed!
Observe special safety measures prior to removing or opening the actuator lid.
- If possible, always detach the plugs for the infeed and control power.
- Only use insulated tools for adjustment activities on actuators connected to the power supply.
- Do not reach into movable components while the actuator is operating.
- Do not touch ESD sensitive components and take precautions if necessary.
CAUTION! Damage or short circuit of the actuator due to water
ingress!
Prevent moisture or foreign bodies from entering the actuator.
- Mount the cable routing, so it does not point upwards.
- Equip pin connectors with gaskets.
- Regularly check the correct position and functioning of all gaskets.
NOTICE! Signal error and premature component wear!
Repeated drive to the set position if the position signal is not permanent.
- Maintain the signal for the drive to the position also after reaching the set position.
- To prevent signal loss, the OPEN/CLOSE inputs can be connected as changeover contacts.
WARNING! Danger from rotating emergency manual override!
The inserted emergency manual override may perform dangerous rotating
movements if the actuator is activated unintentionally.
- During the use of the emergency manual override, switch off the power of the actuator by removing the device plug.
- When not in use, remove the emergency manual override from the actuator.
Warnings for pneumatic actuators
CAUTION! Incorrect connection!
With incorrect connection, control air can escape uncontrolled, which would
impede the function of the pneumatic actuator.
- Follow the instructions for correct connection in the instruction manual.
- The control air connections are marked on the actuator.
- Prevent the uncontrolled escape of the control air by correct connections.
CAUTION! Poor control air quality!
Premature wear due to insufficient control air quality.
- Observe the poisoning and impurity of the control air according to ISO 8573-1.
CAUTION! Clogged openings!
Clogging of the connection openings (ventilation and exhaust openings) can
obstruct the movement of the actuator.
- Use filter elements to prevent unconnected control connection openings from collecting dirt.
WARNING! Unintended movement of the actuator!
Risk of injury by crushing. Install and uninstall the actuator after
disconnecting the control air lines and while in the safety position.
WARNING! Pre-loaded springs!
Risk of injury by components jumping out. Actuators with FC and FO function
must not be opened or disassembled by customers.
Butterfly Valve Type 565 with reduction gear
Reduction gear with handwheel
Intermediate Element
CAUTION! Tighten all enclosed screws of the intermediate element to a torque of 10 Nm and secure with «Loctite 241» or equivalent
NOTE: Actuator and valve indexing must match during assembly.
Butterfly Valve Type 565 with electric actuator
Manual override or Intermediate Element
CAUTION! Tighten all enclosed screws of the intermediate element to a torque of 10 Nm and secure with «Loctite 241» or equivalent.
NOTE: Actuator and valve indexing must match during assembly.
Butterfly Valve Type 565 with pneumatic actuator
Intermediate Element
CAUTION! Tighten all enclosed screws of the intermediate element to a torque of 10 Nm and secure with «Loctite 241» or equivalent.
NOTE: Actuator and valve indexing must match during assembly.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>