Danfoss RA 2000 Integrated Valve Instructions

June 3, 2024
Danfoss

INSTRUCTIONS
RA 2000
Integrated valve, accessory set
Code No.
013G7361

RA 2000 Integrated Valve

Danfoss RA 2000 Integrated Valve

Screw the integrated valve into the radiator until it is hand-tight and its flange is butting onto the radiator connection. Then, using an open-ended ring spanner, SW21, tighten
the valve into the radiator, this should be turned through an angle of 30° equivalent to one of the notches on the valve body part on which the spanner fits. This equates to a torque of 30 – 35 Nm.
Reference
As the notches on the valve body cannot be seen with the spanner in place, it is a good idea to put two marks on the outside of the ring spanner for guidance:
Mark “1” must be at the top Mark “2” should be spaced one notch distance away in a clockwise direction.Danfoss RA 2000 Integrated Valve -
icon

Capacity: Information on pre-settings at the assembly siteDanfoss RA
2000 Integrated Valve - FigDanfoss RA 2000 Integrated Valve -
Fig 1

Pre-setting

The dimensioned setting values can be selected simply and precisely without tools, prior to the fitting of the sensor. For this purpose, the red scale ring must be turned to ensure that the presetting figure selected matches the setting mark. In setting “N” the preset value is fully open.
Detailed information is available from stockists or from the radiator manufacturer.