Pentatech 3000 Set F3 Wireless Alarm System User Manual
- June 5, 2024
- Pentatech
Table of Contents
- Introduction
- Proper use
- Package contents (see Fig. A, B, C, D, E)
- Description
- Technical data
- Safety instructions
- Planning the system
- Positioning of the components
- Connection and commissioning
- Setting the detectors
- Installation
- Operation
- Alarm
- Changing the batteries
- Wireless range
- Troubleshooting
- Maintenance + cleaning
- Optional accessories
- Enrolling further components to the siren
- Delete all components (Reset)
- Disposal
- Simplified EU declaration of conformity
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
3000 Set F3 Wireless Alarm System
User Manual
Introduction
Read through this user manual completely and carefully and while doing so fold-out page 3 with the illustrations. The user manual is an integral part of the product and contains important information about operation and handling. Always observe all the safety instructions. If you have any questions or are unsure about using the equipment, ask a specialist or obtain information online at www.pentatech.de. Keep this manual in a safe place and pass it on to third parties if necessary.
Proper use
The wireless Alarm System 3000 Set F3 consists of the indoor siren 3000IS with
mains adapter, a wireless-PIR-detector 3000P, a wireless door/window contact
3000M, and two remote controls 3000R.
The wireless PIR detector serves to monitor interior rooms. It detects the
movement of warm objects (eg. persons) day and night. Upon detection, it sends
a wireless signal to the siren.
The wireless door/window contact serves to monitor doors and windows. When a
monitored door or window is opened the unit sends a wireless signal to the
siren.
The siren receives the alarm signals from the detectors and if it is armed the
siren warns acoustically and visually (flashes).
The system is armed and disarmed using the remote control 3000R. An alarm can
be manually activated by pressing the panic button.
It is possible to partially arm the system. In this case, certain detectors
can be deactivated when the dwelling is occupied. Detectors in the
entrance/exit area can operate with a delay, in order to allow comfortable
operation of the system.
The system can be extended by adding optional accessories. Up to 5 remote
controls, 3000R, and a total of 20 detectors (3000P or 3000M) can be enrolled
in the siren.
The 3000 Set F3 can be combined with the GSM-Wireless alarm system 3000 Set
F4.
The power supply
- of the siren, 3000IS is through the delivered mains adapter, connected to a 230 V AC, 50Hz mains outlet
- of the remote control, 3000R is through the delivered lithium battery CR2025
- of the PIR-detector 3000P is through two alkaline 1.5 V AA (LR6) batteries (not included)
- of the door/window contact 3000M is through one alkaline 1.5 V AA (LR6) battery (not included)
The components are for indoor use in private households.
Any other use or modification of the equipment is not authorized and presents
significant risks of accident. No liability will be accepted for consequential
damages or for damages caused by improper use or incorrect operation.
This equipment is not suitable for use by persons (including children) with
limited physical, sensory, or mental abilities or with lacking experience or
lacking knowledge unless they are supervised by a person responsible for their
safety or obtain instructions on how to use the equipment. Children must be
supervised to make sure they do not play with the equipment.
Package contents (see Fig. A, B, C, D, E)
- siren 3000IS with mains adapter
- 2 screws with a wall plug for fixing the siren
- 2x remote control 3000R including battery
- PIR detector with bracket and ball joint
- 2 screws with a wall plug for fixing the PIR detector
- door/window contact 3000M (magnet and sensor)
- adhesive pads for magnets and sensor
- user manual
Description
Siren 3000IS (see Fig. A)
-
indoor siren
-
fixing holes
-
strobe
-
siren
-
cable for mains adapter
-
connection button
-
mains adapter
-
screw
-
wall plug
Remote control 3000R (see Fig. B) -
remote control
-
LED
-
disarm button
-
panic button
-
part arm button
-
keyring
-
arm button
-
battery
-
fixing hole
PIR-detector 3000P (see Fig. C) -
PIR-detector
-
Fresnel lens
-
LED
-
slot for bracket
-
test button
-
battery compartment lid
-
clip
-
screw hole
-
screw
-
brackets
-
fixing hole
-
wall plate
-
ball joint
-
screw
-
wall plug
-
battery compartment
-
LED jumper
-
ZONE jumper
Door/window contact 3000M (see Fig. E) -
sensor
-
LED
-
arrow marks
-
magnet
-
adhesive pad
-
ZONE jumper
-
battery compartment
Technical data
Siren 3000IS
Operating voltage | 12 V DC (mains adapter) |
---|---|
Current consumption | max. 200 mA |
Frequency band | 433,05 MHz – 434,79 MHz |
Maximum radiated transmission power | < 10 mW |
Wireless components | max. 5 remote controls and max. 20 detectors enrollable |
Sound pressure level | approx. 100 dB(A) / 1 m |
Operating temperature | ±0° C to + 40° C |
PIR-detector 3000P
Operating voltage | 3 V DC |
---|---|
Current consumption | max. 10 mA |
Power supply | 2x 1,5 V AA alkaline batteries (LR6) |
Frequency band | 433,05 MHz – 434,79 MHz |
Maximum radiated transmission power | < 10 mW |
Wireless range | max. 30 m (in free space) |
Detection area | approx 8 m through 110° |
Operating temperature | ±0° C to + 40° C |
Door/window contact 3000M
Operating voltage | 1,5 V DC |
---|---|
Current consumption | max. 40 mA |
Power supply | 1x 1,5 V AA alkaline battery (LR6) |
Frequency band | 433,05 MHz – 434,79 MHz |
Maximum radiated transmission power | < 10 mW |
Wireless range | max. 30 m (in free space) |
Operating temperature | ±0° C to + 40° C |
Remote control 3000R
Operating voltage | 3 V DC |
---|---|
Current consumption | max. 70 mA |
Power supply | 1x 3 V CR2025 |
Frequency band | 433,05 MHz – 434,79 MHz |
Maximum radiated transmission power | < 10 mW |
Wireless range | max. 30 m (in free space) |
Operating temperature | -10° C to + 40° C |
Mains adapter
Input voltage | 230 V ~ 50 Hz |
---|---|
Output voltage | 12 V DC, 500 mA |
Safety instructions
The following instructions are provided for your safety and satisfaction during the operation of the product. Note that non-observance of these safety instructions results in significant risks of accident.
Danger! If this point is not heeded, life and health are endangered.
-
Do not leave small children unsupervised with the product, packaging
material, or small parts. Otherwise, there is a risk of fatal injury due to choking! -
Ensure that the alarm siren is not activated when persons are close to the siren. Wear ear protection when testing the unit, otherwise, there is a danger of hearing damage.
-
Do not damage any gas, electricity, water, or telecommunication lines during drilling and fixing work. Otherwise, there are dangers of personal and fatal injury!
-
Treat the supply lines carefully. Lay these so that they cannot be damaged and do not present any tripping hazard. Fix the cables sufficiently. Do not pull the cables over sharp edges and do not crush or crimp them elsewhere. Otherwise, there are dangers of personal and fatal injury!
-
Use only the supplied mains adapter with the siren. Before connecting the power supply to the mains, ensure that the mains current complies with 230 V ~, 50 Hz and is fitted with a fuse according to regulations. Otherwise, there are dangers of fire and fatal injury.
-
Do not allow the product to contact moisture. Never immerse the product in water. Otherwise, there is a danger of fatal injury!
-
Ensure that the batteries are not short-circuited or exposed to fire. The batteries must not be opened or recharged. Otherwise, there is a risk of fatal injury due to an explosion!
-
Leaking or damaged batteries can cause burns by contact with the skin. Handle these using suitable protective gloves.
-
ATTENTION: Risk of explosion if the battery is not replaced correctly. Replacement only with the same or equivalent type.
Attention! Non-observance of these instructions puts the property at risk of damage.
- Before installing and operating the product check the package for damages and completeness.
- Do not connect any damaged device (e.g. transport damage) and disconnect the power supply immediately in the case of damage.
- Unplug the main adapter from the main socket. Arrange for the damage to be repaired immediately by a specialist!
- Use the product only with the original components or original accessories!
- Use only the recommended battery types.
- Do not expose the product to fire or high temperature!
- Protect the product against strong magnetic or electrical fields and against strong mechanical loads and vibrations!
- Insert the batteries with the correct polarity.
- If the unit is to be unused for a longer period disconnect the mains adapter from the mains supply and remove the batteries.
Planning the system
Consider first which are the vulnerable areas to be monitored. Windows and
doors can be monitored using the door/window contact, in particular, the main
entrance door should be monitored.
PIR detectors can monitor entire rooms, but cannot be used when the room is
occupied. They are also sensitive to pets and warm air currents. A typical
system consists of a mixture of door/window contacts and PIR-detectors
Part arming
The system can be planned so that:
- all detectors are activated when the system is armed or
- that some of the detectors are set so that they are activated when the system is fully armed, but not when the system is part armed
The part arm function is recommended when monitoring is required for an occupied dwelling. In this case, the PIR detectors must be set in Home mode. When the dwelling is occupied, the system should be part armed (the detectors set in Home mode are not active). When the dwelling is unoccupied, fully arm the system (all detectors are active).
Entry/Exit delay
In order to arm the system from within the dwelling before leaving, or to
disarm the system after entering, without causing an immediate alarm, set the
detectors which monitor the entrance/exit area to delay. These detectors will
not signal an alarm during the exit delay period (15 or 30 seconds
selectable). Similarly, if these detectors make a detection when the system is
armed, they will trigger an entrance delay (15 or 30 seconds selectable)
before causing an alarm. The delay period is indicated by the beeping of the
siren.
The delay period can be set on the siren for 0, 15, or 30 seconds. If 0
seconds is selected the detectors are set for the delay, which will cause an
immediate alarm.
Tip: To reduce false alarms, it is recommended to set the detectors in
the entrance/exit area to delay, even if it is intended to arm and disarm the
system from outside the dwelling.
Immediate alarm
All detectors which are set for “immediate” alarm will cause an immediate alarm when the system is armed or part armed.
Example plan of a 3 room apartment (see Fig. F)
components in the set:
IS siren 3000IS
P PIR-detector 3000P, set in home mode
M door/window contact 3000M, set in delay mode
optional components:
P PIR-detector 3000P, set in home mode
M door/window contact 3000M, set in immediate mode
Positioning of the components
Before installing the components plan the system and test the wireless
connection from the proposed positions.
Consider the following:
- The range of each component depends on many factors.
- Walls, floors, doors, metal areas eg. refrigerators, shelving, mirrors, or volume of the water block the wireless signals.
- The wireless range can be influenced by electromagnetic fields and other wireless devices. Ensure separation from microwave ovens, cordless phones, WiFi, mobile phones, wireless devices, electric motors, and wiring.
- Ensure a minimum distance of 2 m between the components – also whilst testing.
- Place the components so that they are not immediately visible to the intruder.
Siren 3000IS
- Position the siren near the middle of the dwelling to optimize the wireless connection to all components.
- Place it near a mains socket considering the cable length of the adapter.
- Mount the siren after all components have been successfully enrolled.
PIR-detector 3000P
- The PIR detector should be wall-mounted using the bracket.
- Position the PIR-detector to monitor an area that is likely to be crossed by an intruder, eg. a hallway.
- The sensor reacts to changes in temperature, eg. movement of persons, within the monitored area (up to 8m over 110° (see Fig. I) using the ideal mounting height of 2.2m).
- Do not cover the lens of the detector, otherwise, the sensor cannot detect!
- As the sensor reacts to temperature changes, ensure that there are no heat sources in the monitored area, eg. radiators, lamps, air conditioning, ventilators, windows, cooking appliances, or draughts.
- The detector should look into the room, and not be aimed at windows (see Fig. F).
- Pets can also trigger an alarm, ensuring that these cannot enter the monitored area when the system is armed. If this is not possible install the detector upside down so that the floor area is not monitored. In this case, test that an intruder will still be detected.
- How quickly the detector reacts is also dependent on the ambient temperature. In a colder environment, it reacts quicker.
- Motion across the monitored area is detected much quicker than motion directly towards the detector. Position the detector so that an intruder will move across the area (see Fig. D).
Door/window contact 3000M (see Fig. G, H)
- Place the sensor on the window or door.
- Place the magnet on the frame of the opening side of the door or window directly adjacent to the sensor. The arrow marks must be opposite each other and the distance between separating distances in closed conditions should not exceed 10 mm (see Fig. E).
Connection and commissioning
Siren 3000IS
- Connect the DC-plug of the mains adapter (7) with the cable (5).
- Connect the mains adapter with a suitable mains outlet. The siren is now ready for use.
The delay can be set by pressing the connection button (6) using a ballpoint pen. The setting will be confirmed by a beep and a flash.
Delay | Press connection button |
---|---|
15 seconds | 2x |
30 seconds | 3x |
no delay | 4x |
factory default: 30 seconds
PIR-detector 3000P
The detector in the set is already enrolled in the siren.
- Open the housing by pressing the clip (25) with a small screwdriver.
- Insert two suitable alkaline 1.5 V, AA batteries into the battery compartment (34) observing correct polarity.
- Close the housing fully so that it clicks. After inserting the batteries the detector enters a 3 minutes stabilizing period indicated by flashing of the LED (21) every 3 seconds. Afterward, the detector is in operating mode.
To test the detector enters the test mode by pressing the test button (23).
You now have 3 minutes time to test the coverage of the sensor: Hold the
detector in the proposed position and then ask somebody to walk across the
monitored area. Detection will be indicated by the LED (21). After 5-10
seconds of deactivation, the sensor is reactivated and is ready for another
detection.
After 3 minutes in Test mode, the deactivation period is increased to 3-5
minutes, to save battery power (operating mode) which means that the PIR only
sends a signal to the siren after it has not registered movement for a period
of 3 to 5 minutes.
- Set the LED/ZONE jumpers (35/36) to the desired setting (see chapter 10 – note: in this case all components must be enrolled again).
- Secure the housing with screw (27) into screw-hole (26) using a small screwdriver.
Door/window contact 3000M
The detector in the set is already enrolled in the siren.
- Slide the battery compartment lid downwards and lift it from the sensor (37).
- Set the ZONE jumper (42) to the desired setting (see Chapter 10 – note in this case all components must be enrolled again).
- Insert a suitable alkaline 1.5 V, AA battery into the battery compartment (43) observing correct polarity.
- Close the housing fully so that it clicks. The detector is now in operating mode.
- Test the detector from the proposed position, and detection will be indicated by the LED (38).
Remote control 3000R
The remote control in the set is already enrolled to the siren and is operational since the battery is already installed.
Setting the detectors
The detectors can be set according to the position of jumpers that connect two
pins together.
Remove batteries before changing the jumper positions.
After the position of a jumper in any enrolled detector has been changed it
is necessary to reset the siren and reenroll all components (see chapters 20
and 19).
** jumper connected
Ο** jumper not connected
ZONE jumper (36/42) (3000P, 3000M)
D0 D1 D2 D3 | setting | reaction |
---|
| Immediate alarm| immediate alarm in full and part arm
| delayed alarm| delayed alarm in full and part arm*
| Home mode| immediate alarm by the full arm, no alarm in
part arm
- If the delay in the siren is set for no delay a delayed detector will give an immediate alarm.
Factory default: delayed alarm
All functions are described in chapter 7.
LED jumper [35] (3000P)
OFF ON|
---|---
| LED active (LED indicates a detection and low battery)
| LED deactivated
factory default: LED on
Installation
Siren 3000IS
- Disconnect the mains adapter (7) from the mains socket.
- Mark the fixing positions on the wall through the fixing holes (2).
- Drill two holes and insert the wall plugs(9).
- Fix the siren with screws (8) to the wall.
- Connect the mains adapter with the power socket
PIR-detector 3000P
- Mark the fixing positions on the wall through the fixing holes [29] of the bracket [28].
- Drill two holes and insert the wall plugs(33).
- Fix the bracket with screws (32) to the wall.
- Press the ball joint (31)into the bracket [30].
- Slide the bracket into the slot (22) on the back of the detector.
- Position the detector such that it is vertical, not tilted, and the LED (21) is beneath the lens.
Door/window contact 3000M
Remove the protective film from one side of the adhesive pads [41].
- Attach the pads to the middle of the rear housing of the magnet [40] and sensor [37].
- Remove the foil from the other side of the pads.
- Fix the magnet vertically on the window/doorframe directly next to the window/door edge. Attach the sensor so that the arrows are level, leaving a maximum gap of 10mm in closed conditions (see Fig. E and G).
** The contact will not operate on the hinged side.
Note:**
If the window frame is thick, attach the magnet to the edge of the frame to
ensure a maximum gap of 10mm (see Fig. H).
Operation
With each remote control 3000R that is enrolled to the siren the system can be
fully armed, part armed, disarmed, and a panic alarm can be activated.
Use ear protection when testing the system.
Pay attention not to cover the front part of the remote control in order not
to block the wireless connection.
**** Ensure that the beeping of the siren is audible as confirmation of the
command and so that you are reminded to leave/disarm the system.
Full arm
- Press the full-arm button [16]. The siren confirms with one beep and one flash. If a delay has been set the siren will beep every 5 seconds and you have time to leave the dwelling during the delay period.
- If you wish to arm without confirmation beeps then press the part arm button (14) before pressing the full-arm button. The armed status is indicated by a red LED (3).
Part arm
See chapter 7.1
- Press the part arm button (14). The siren confirms with one beep and one flash. If a delay has been set the siren will beep every 5 seconds.
- If you wish to part the arm without confirmation beeps then press the part arm button two times.
The armed status is indicated by a red LED (3). The detectors which are set to home mode will not cause an alarm by detection.
Disarm
- Press the disarm button (12). The siren confirms with two beeps and two flashes. The LED (3) no longer lights and the system is disarmed.
- If you wish to disarm without confirmation beeps then press the part arm button (14) before pressing the disarm button.
Panic alarm
- Press the panic button (13). The siren will sound alarmed for approx. 3 minutes.
- You can silence the alarm by pressing the disarm button (12).
Alarm
Upon detection, a detector will send an alarm signal to the siren. If the system is armed, the siren will sound and flash for up to 3 minutes. If the detector was set to delay, then the alarm will be delayed accordingly.
- To stop the alarm press the disarm button. If the alarm is not canceled it will stop automatically after 3 minutes and the system remains armed.
**** Note that in operating mode a PIR-detector will be deactivated for 3-5 minutes after each detection) which means that the PIR only sends a signal to the siren after it has not registered movement for a period of 3 to 5 minutes.
Changing the batteries
The batteries in detectors will last typically 6 months. For a PIR detector in a room where there is much movement, this period can be shorter. A weak battery will be indicated by flashing the detector LED every 6 seconds. Replace the batteries as soon as possible to ensure continued operation. After the low battery warning starts the detector will operate for a maximum of 3 weeks (assuming no detection within this period). If the remote control becomes weak the battery is weak and must be replaced.
- Disarm the siren.
- Open the housing.
- Replace the batteries with suitable new ones.
**** Open and close the housing of the remote control with care, to ensure that the LED cover and PCB do not slip out of place.
Wireless range
Note that the wireless range of each component can differ. The range is
dependent on various factors. A reduction in the range can be caused by the
following:
Ο Walls and floors, especially those containing metal, metalized foil,
reinforced concrete or stone
Ο Coated windows (eg. Energy saving windows), radiators, refrigerators,
mirrors, metalic surfaces or doors
Ο Electrical wiring and electrical appliances (eg. motors, microwave
ovens)
Ο Devices using the same or similar wireless frequency.
Troubleshooting
Fault | Cause | Remedy |
---|---|---|
short wireless range of remote control | antenna is covered | do not cover the |
front of the remote control
Alarm without apparent reason| PIR-detector reacts to temperature differences|
check the positioning of PIR, do not point towards heat sources
PIR-detector does not react| In operating mode deactivated for up to 5 minutes
after each detection| Wait, or press the test button (23). After the
deactivation period, the unit will detect immediately
siren no longer reacts to the detector or remote control| to detector or
control is no longer enrolled; e.g. jumper position has been changed| reset
the siren and enroll all components
Maintenance + cleaning
Ο Regularly check the technical safety and function
Ο Before you clean the device, pull the main adapter out of the main
socket and remove the batteries.
Ο Use a soft, dry, or slightly moist cloth or a dry brush for cleaning
the surfaces.
Optional accessories
Ο 3000M, Door/window contact, Art.Nr.33531
Ο 3000R, Remote control, Art. Nr. 33532
Ο 3000P, PIR-detector, Art. Nr. 33530
Ο 3000 Set F4, GSM-wireless alarm system, Art. Nr. 33523
Enrolling further components to the siren
Use ear protection
- Use a ballpoint pen to press the connect button (6) on the siren. The siren beeps and the LED (3) lights yellow/orange for 10 seconds. Within this period you can enroll in one of the following components:
Ο Remote control: press the disarm button (12) once
Ο PIR-detector: press the test button (23) twice
Ο door/window contact: trigger by separating the magnet from the sensor The enrollment will be confirmed by the siren with a beep and LED (3) will flash.
Delete all components (Reset)
If remote control is lost, delete all components and then enroll the remaining components again (see chapter 19), to maintain the security of the system.
- To delete all remote controls and detectors hold the connect button (6) on the siren with a ballpoint pen pressed until the deletion is confirmed by a beep and flash.
Tip: Enroll a remote control as the first item, by pressing the disarm button (12) 2 times, then you can cancel an unwanted alarm.
Disposal
The packaging material used in batteries or electrical products must not be disposed of as household waste. Use your recycling system. Details are available from your local authority.
Simplified EU declaration of conformity
Hereby, INDEXA GmbH declares that the radio equipment type 3000 SET F3 is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: http://www.pentatech.de/de/downloads/cat_view/13-ceerklaerungen.html.
References
- Funk-Alarmanlagen Funk-Videoüberwachung Funk-Rauchmelder VdS - Alarmanlage System 8000 Funkalarmanlage System 9000 - Videoüberwachung und Sicherheitstechnik von Indexa
- Funkalarmanlagen Funk-Videoüberwachung VdS Funk-Rauchmelder Sicherheitstechnik von Pentatech
- Downloads | CE Konformitätserklärungen
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>