KLINGER DK-2605 Ultrasonic Flowmeter User Manual

June 5, 2024
KLINGER

KLINGER DK-2605 Ultrasonic Flowmeter

Product component

Inspection should be made before installing the Flowmeter. Check to see If the spare parts are in accordance with the packing list. Make sure that there is no potential damage to the enclosure due to a loose screw or loose wire, which occurred during transportation. Any questions, please contact your representative as soon as possible.

EtM™ installation and Connect

Once the IEtM™ is installed, the How to meter can be connected. You can be found the cable has 5pin terminals, As per wiring the diagram to connect 4-20mA Output, RS485.

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig3

Panel function

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig4

Powering on

As soon as the Flowmeter is switched on, the self-diagnosis program will start to run.

Signal Quality (SQ value)

Q value is short for Signal Quality. It indicates the level of the signal detected. Q value is indicated by numbers from 0-99 represents the minimum signal detected while 99 represent the maximum. Normally, the transducer position should be adjusted repeatedly and the coupling compound should be checked frequently until the signal quality detected is as strong as possible.

Keypad Functions

Follow these guidelines when using the Flowmeter keypad.

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig6

Setting or display mode, when it is setting mode, that can return to the previous menu, and scroll up and down to select the menu, when press move to next digit, press) and the numbers scroll from 0 to 9, you can select the number. Press(to confirm.

Window descriptions

Display Menu

When the power is on, the meter will display Velocity/Net Totalize.

Display date and time, velocity, and net totalize Press will display Flow Rate/Net Totalize, and press will return to the previous menu.

Display signal quality. Time, flow rate, and velocity. Press will display Flow Rate/ Velocity/Net Totalize, press)will return to the previous menu.

Display Run time, Date, Month, and Year net totalize.

Setup Menu

Press will display the Setup menu

The following options are available buttons

  • Pipe parameter
  • System setting
  • Calibration
  • Output setting

Dimensions

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig12

Product warranty

  • The product has been strictly tested before leaving the factory. If any malfunction occurs, please contact us or our agents immediately and provide details of the malfunction.
  • The warranty is for one full year after the date that the product is delivered at the designated place.

Scope of warranty

if any malfunction is caused by us within the one-year warranty, we would repair the product free of charge. The following situations are not covered by the warranty. product is not used properly in accordance with the manual or technical requirements (including unsuitable conditions, unsuitable environment, etc.). The malfunction is caused by purchasers or purchasers’ software. lf product is amended or fixed without our permission.

Setup Menu- Pipe parameter

Press Select Pipe parameter, then display

  • The following options are available (by (or buttons)
  • Outer diameter
  • Wall thickness
  • Material: Move or an option PVC, Carbon steel, Steel,
  • Copper pipe.
  • Fluid type: Move)or O can option Water, Sea Water, Oil, etc.

Setup Menu -System setting

Press Select System setting, then display

  • The following options are available (by or buttons)
  • System Unit Move or an option Metric, English.
  • Flow rate unit Move or can option m3/h, LPM, GPM.
  • Total unit: MoveorOcan m3, L, GAL.
  • Totalize RESET All parameters are reset, Press, move or arrow to select “YES” or “NO”. After “YES” is selected.
  • Time set.
  • Generally, it is unnecessary to modify the date-time as the system is provided with a highly reliable perpetual calendar chip.

System lockKLINGER-DK-2605-Ultrasonic-Flowmeter-Fig15

Once the system is locked, any modifications to the system are prohibited, but the parameter is readable. “Unlock” using your designated password. The password is composed d 1 to 4 numbers.

System INFO

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig16

Display the serial number (SN) of the meter. This SN is the only one assigned to each flowmeter ready to leave the factory. The factory uses it for file setup and for management by the user. Set zero: Press; reset “Zero Point’ which was set by the user. Manual Totalizer: The manual totalize is a separate totalize. Pressto start, and pressto stop it. It is used for flow measurement and calculation.

Setup Menu- Calibration

Press Select Calibration, and then display

Scale factor

  • Refers to the ratio between “actual value” and “reading value”. For example, when the measurement is 2.00, and it is indicated at 1.98 on the instrument, the scale factor reading is 2/1.98. This means that the best scale factor constant is 1.01.

  • 4-20mA CAL: Check if the current loop has been calibrated before leaving the factory. Press (D) move () to display 4mA or 24mA, and at the same time, check with an ammeter to verify that the Current Loop output displayed values. It is necessary to re-calibrate the current loop, if over the permitted tolerance.

  • Set zero: Press reset “Zero Point’ which was set by the user.

  • Low flow cut The flow rate falls below the low flow cutoff value.

  • The flow indication is driven to zero. This function can prevent the flow meter from reading flow after a pump is shut down but there is still liquid movement in the pipe, which will result in a totalization error. Generally, 0.03m/s is recommended to enter as the low flow cutoff point. The low flow cutoff value has no relation to the measurement results once the velocity increases over the low flow cutoff value.

Setup Menu – Output

Press.Select Output setting, and the display 0.RS485 setup

The window is used to set the serial port. It connects with the equipment of its serial port set of parameters that must match. The first choice of data that baud rate: 2400, 4800, 9600, 19200 choices. The second option that is in check, is None. Data length fixed to eight; Stop bit for fixed length Factory serial port parameters for the default “9600, 8, None, 1”. 1.4-20mA Range.

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig23

Enter the low alarm value; any of the measured flow, which is lower than the low value, will activate the alarm in the OCT hardware or relay output signal. Enter the high alarm value; any of the measured flow, which is higher than the high value, will activate the alarm in the OCT hardware or relay output signal.

Performance index

KLINGER-DK-2605-Ultrasonic-Flowmeter-Fig26

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals