KLINGER US201 Ultrasonic Heatmeter Instruction Manual
- June 3, 2024
- KLINGER
Table of Contents
US201 Ultrasonic Heatmeter
Ultrasonic Heatmeter Operation Manual
Ultrasonic Heatmeter Type US201 Operation Manual
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
Product Overview
1.1. Introduction
Klinger US201 is a wall-mount, clamp- on type ultrasonic flow meter which uses
the transfer time technology. Clamp on type ultrasonic flow meter is easy to
install and no need to cut off the pipe that saves you lots of troubles and
cost. At the same time US201 has our unique calculate software to ensure the
high accuracy and low velocity response.
US201 ultrasonic flow meter widely application in oil industry, water
treatment, pure water, chemical and etc.
US201 could add the RTD model and temperature sensor become an energy meter to
monitoring the energy use, help to save the energy.
1.2. Features of US201
Comparing With other traditional flow meter or ultrasonic flow meter, it has
distinctive features such as high precision, high reliability, high capability
and low cost, the Flow meter features other advantages:
1. With ARM COMA chip, low power consumption, high reliability, anti-jamming
and outstanding benefits.
2. User-friendly menu designed. Parameters of pipe range, pipe material, pipe
wall thickness, output signals, etc can be conveniently entered via the
windows. British and Metric measurement units are available.
3. Daily, monthly and yearly totalized flow: Totalized flow for the last 64
days and months as well as for the last 6 years are may be viewed. With the SD
Card, 512 files can be stored; the time interval can be within 1 second.
4. Parallel operation of positive, negative and net flow totalizer with scale
factor and 7 digit display. Internally configured batch controller makes batch
control convenient.
The flow meter ensures the higher resolution and wider measuring range by the
0.04ns high resolution, high linearity and high stability time measuring
circuit and 32 bits digits processing program.
1.3. Theory of Operation
When the ultrasonic signal is transmitted through the flowing liquid, there will be a difference between the upstream and downstream transit time ( travel time or time of flight ), which is proportional to flow velocity,
V = MD ´ DT sin 2q Tup · Tdown
Remarks:
V Medium Velocity M Ultrasonic frequency of reflection D Pipe Diameter The
angle between the ultrasonic signal and the flow Tup Transit time in the
forward direction Tdown Transit time in the reverse direction T = Tup Tdown
Downstream Transducer
Tdown
Flow
Tup
D
Upstream Transducer
4
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
1.4. Specifications
Performance specifications
Flow Rage
0 ft/s ~ ± 40 ft/s ( 0 m/s ~ ± 12 m/s ).
Accuracy
±1% of measured value.
Repeatability
0.2%.
Pipe Size
1 ~ 48 ( 25 mm ~ 1200 mm ).
Function Specifications
Output
Analog output: 0/4 ~ 20 mA, ( max load 750 ) Pulse output: 0 ~ 9999 Hz, OCT ( min. and max. frequency is adjustable ); Relay output: max. Frequency 1Hz (1A 125VAC or 2A 30VDC ).
Communication Interface
RS232 & RS485.
SD Card ( Option )
Max record: 512 days. Record time interval: 1 ~ 3600 s.
Power Supply
10 ~ 36 VDC.
Keypad
16 light tactile keys.
Display
240*128 lattice, backlit LCD.
Temperature
Transmitter: -40°F ~ 140 °F (- 40 ~ 60 ). Transducer: -40 °F ~ 176 °F ( – 40 ~ 80 , standard ).
Humidity
Up to 0 ~ 99% RH, non – condensing.
Physical specifications
Transmitter
PC/ABS, IP65.
Transducer
Encapsulated design. Standard / Maximum cable length: 30 ft / 1000 ft ( 9m / 305 m ).
Weight
162328cm, 3.2kg
5
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
2. Connection
2.1. Wire Connecting
2.1.1. Power supply option
Customers should pay special attention to specify the desired power supply
when wiring. Factory standard power supply is 10~36VDC/1A max. To ensure the
transmitter can work normally, please pay attention to the followings when
wiring: Ensure that power connections are made in accordance with the
specifications shown on the transmitter.
2.1.2. Transmitter Wiring
Once the electronics enclosure has been installed, the flow meter wiring can
be connected. Open the case, you will find the Power board wiring ports, from
left to right, are as follows; Connect to power supplier, Relay Output, OCT
Output, Transducer wiring, 4-20mA Output, RS232 Output, RS485 Output, Analog
Input. For double-shielded transducer cable: “-” on the Blue wire, “+” on the
Brown wire and “shield” on the Black shield wire. Refer to the below form for
specific connection:
Sign DC+ DC-
RL OUT+ RL OUTOCT OUT+ OCT OUTGND UP+ UPGND DN+ DNI OUT+ I OUT-
Description DC Power DC1036V + DC Power DC1036V Grounding
Relay Output
OCT Output
Upstream sensor Grounding Black Upstream sensor + Brown Upstream sensor – Blue
Downstream sensor Grounding Black Downstream sensor + Brown Downstream sensor
– Blue
40~20mA Output
6
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
AI1 AI2 GND TX HX GND A B IN1+ IN1GND IN2+ IN2GND
Analog Signal Input ( Only Energy Meter )
RS232 Output
RS485 Output Temperature sensor water inline + Temperature sensor water inline
Temperature sensor water inline grounding Temperature sensor water outline +
Temperature sensor water outline Temperature sensor water outline grounding
Warning Wire when it is power-off. Reliable grounding must be taken for the
instrument before installation and use. Use either AC or DC power supply. Do
not connect them both at the same time.
2.2. Powering on
As soon as the flow meter is switched on, the system will run automatically
according to the last input parameters. If the installation is accomplished
when system is switched on, gain adjustment can be monitored in Window M04.
After code “R” are displayed on the upper right corner of the screen, the
system will activate the normal measurement condition automatically. It is
indicated by code “R” on the upper left corner of the screen. If it is the
first time to use or install on a new site, the customer need to input the new
installation site parameters. Any parameters which are set by user will be
saved permanently until they are changed by the user. When the user modifies
the parameters and removes the transducers, the meter will recalculate
automatically, and operate normally with the parameters. The flow meter can
always complete all tasks at the same time. The tasks (Including measurement,
output, etc) will be carried out as usual, no matter in which display window.
7
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
2.3. Keypad Functions
Numbers “0~9” and “.” Input Numbers or Menu Code ” “Backspace or delete
characters to the left or back to the previous menu. “”Return to the last menu
or open the next menu. Acts as “+” and “-” are used to enter numbers. ”
Menu”Select a menu. Press this key first, then input two menu numbers to
display the selected menu.
SD card data memory is an optional.
2.4. Keypad Operation
The flow meter adopts the window software design to consolidate or subdivide
all of the parameters entered, the instrument setup and measurement result
displays into independent windows. The operator can input parameters, modify
settings or display measurement results by “visiting” a specific menu window.
Each window serial number, or so-called window ID code, has a defined meaning.
For example, Window M10 indicates the parameter input for pipe outside
diameter, while Window M14 indicates the mounting spacing between the
transducers, etc. (Refer Windows Display Explanations). The keypad shortcut
to visit a specific window is to press the ” Menu” key at any time, then input
the 2-digit window ID code. For example, to input or check the pipe outside
diameter, just press the ” Menu” “1” “0” keys for window ID code 10. Use “”and
“” to switch. Another method to visit a particular window is to press “”and “”
to scroll the screen. You can check the corresponding parameters by visiting
the Data Type Windows. If you want to modify the parameters, press ” Enter ”
first, input the digits then press ” Enter ” again to confirm.
Attention Generally, press Enter key first if operator wants to enter “modify”
status. If the “modify” is still not possible even after pressing the Enter
key, it means that system is locked by a password. To “Unlock” it, select
“Unlock” in Window M54 and enter the original password.
8
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
3.Quick start
3.1. Basic settings
For example, let us you have a pipe of 200mm outer diameter4mm pipe thickness,
measuring medium is water, Pipe Material is PVC with no Liner, These
parameters should be operated as follows:
Step1. Pipe Size Settings Find M10; enter the pipe size, the outer diameter of the pipe and the pipe thickness. Press the ” Enter” to confirm.
OD200.0mm
Step2. Pipe Material Use “” to switch to select the material of the pipe.
Press the ” Enter” to confirm.
SizeM.
Step 3. Water Temperature Find M12, select the temperature of the water,
temperature should be 0-80 deg. C.
Press the ” Enter” to confirm. Note: Room temperature is 25 deg.C
M12Medium*R
WTMP
20(C)
9
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
Step4. Transducer Type Find M13, select the transducer type, here we select
the 1. Clamp-On-D, our standard clamp on type transducer. Press the ” Enter”
to confirm. .
Step 5. Transducer Mounting Methods Use “” to switch to select transducers
mounting method, here we select 0. V type, directly method. Press the ” Enter”
to confirm.
Step 6. Installation Spacing Find M14, accurately install the transducer
according to the displayed transducer mounting spacing and the selected
mounting method.
Step 7. Display Measurement Results Menu 01 will display flow rate. (Subject
to the real measurement. )
3.2. Measurement Site Selection
The installation of this ultrasonic flow meter is the simplest one of all
kinds of flow meters. Only one suitable measuring site needed, plug the
transducers on the pipe and then start the measurement. When selecting a
measurement site, it is important to select an area where the fluid flow
profile is fully developed to guarantee a highly accurate measurement. Use the
following guidelines to select a proper installation site: l Choose a section
of pipe that is always full of liquid, such as a vertical pipe with flow in
the upward direction
or a full horizontal pipe.
10
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
l Ensure enough straight pipe length at least equal to the figure shown below
for the upstream and downstream transducers installation. Try to avoid Ensure
enough straight pipe length at least equal to the figure shown below for the
upstream and downstream transducers installation.
l On the horizontal pipe, the transducer should be mounted on the 9 and 3 of
the pipe, avoiding the position of 6 and 12, in case of the signal attenuation
caused by pipe at the bottom sediment or bubblecavitation on the pipe.
l Ensure that the measuring site temperature is under the transducer
temperature limits. l Consider the inside condition of the pipe carefully. If
possible, select a section of pipe where the inside is free
of excessive corrosion or scaling. l Choose a section of sound conducting
pipe.
11
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
12
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
4.Transducer Installation
4.1. Transducer Installation
Please make sure the pipe surfaces where the transducers are to be mounted are
all clean. Including the rust, scale or loose paint to have a smooth surface.
Choose the section and don’t forget apply the coupling compound. Apply the
coupling compound down the center of the face of each transducer as well as on
the pipe surface, ensure there are no air bubbles between the transducers and
the pipe wall, and then attach the transducers to the pipe with the straps
provided and tighten them securely.
Note: The two transducers should be mounted at the pipe’s centerline on
horizontal pipes.
Make sure that the transducer mounting direction is parallel with the flow.
During the installation, there should be no air bubbles or particles between
the transducer and the pipe wall. On horizontal pipes, the transducers should
be mounted in the 3 o’clock and 9 o’clock positions of the pipe section in
order to avoid any air bubbles inside the top portion of the pipe. (Refer to
Transducer Mounting). If the transducers cannot be mounted horizontally
symmetrically due to limitation of the local installation conditions, it may
be necessary to mount the transducers at a location where there is a
guaranteed full pipe condition (the pipe is always full of liquid).
4.1.1. Transducer Spacing
The spacing between the ENDS of the two transducers is considered as the
standard transducer spacing (Refer to MENU14). After entering the required
parameters, Check the data displayed in Window M14 and adjusted the
transducers spacing according to the data displayed in Windows M14.
1.1.2 Transducer Mounting Methods
There are two mounting method, you could use depend on the measuring
environment. V method and Z method (Reflect method and Direct method). V
method is easy to installation and fit for mostly ultrasonic environment but Z
method has stronger signal and works better in the complicated measuring
environment.
4.1.3. V Method
The V method is considered as the standard method. It is convenient to use, but still requires proper installation of the transducers, contact on the pipe at the pipe’s centerline and equal spacing on either side of the centerline.
Side view
Section
Top View
13
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
4.1.4. Z Method
The signal transmitted in a Z method installation has less attenuation than a
signal transmitted with the V method
When the pipes are too large, there are some suspended solid in the fluid, or
the scaling and liner are too thick. This is because the Z method utilizes a
directly transmitted (rather than reflected) signaling which transverses the
liquid only once. The Z method is able to measure on pipe diameters ranging
from 100mm to 5000mm (4 inch to 200 inch) approximately. Therefore, we
recommend the Z method for pipe diameters over 300mm (12 inch).
Side view
Section
Top View
4.2. Transducer Mounting Inspection
Check to see if the transducer is installed properly and if there is an
accurate and strong enough ultrasonic signal
14
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
to ensure proper operation and high reliability of the transducer. It can be
confirmed by checking the detected signal strength, total transit time, delta
time as well as transit time ratio. The “mounting” condition directly
influences the flow value accuracy and system long-time running reliability.
In most instances, only apply a wide band of sonic coupling compound
lengthwise on the face of the transducer and stick it to the outside pipe wall
to get good measurement results. However, the following inspections still need
to be carried out in order to ensure the high reliability of the measurement
and long-term operation of the instrument.
4.2.1. Signal Strength
Signal strength (displayed in Window M04) indicates a detected strength of the
signal both from upstream and downstream directions. The relevant signal
strength is indicated by numbers from 00.0 ~ 99.9. 00.0 represents no signal
detected while 99.9 represent maximum signal strength. Normally, the stronger
the signal strength detected, the longer the operation of the instrument
reliably, as well as the more stable the measurement value obtained. Adjust
the transducer to the best position and check to ensure that enough sonic
coupling compounds is applied adequately during installation in order to
obtain the maximum signal strength. System normally requires signal strength
over 75.0, which is detected from both upstream and downstream directions. If
the signal strength detected is too low, the transducer installation position
and the transducer mounting spacing should be re-adjusted and the pipe should
be re-inspected. If necessary, change the mounting method to be Z method.
4.2.2. Signal Quality (Q value)
Q value is short for Signal Quality (displayed in Window M04). It indicates
the level of the signal detected. Q value is indicated by numbers from 00 ~
99. 00 represents the minimum signal detected while 99 represent the maximum.
Normally, the transducer position should be adjusted repeatedly and coupling
compound application should be checked frequently until the signal quality
detected is as strong as possible.
4.2.3. Total Time and Delta Time
“Total Time and Delta Time”, which displays in Window M04, indicates the
condition of the installation. The measurement calculations in the Flow meter
are based upon these two parameters. Therefore, when “Delta Time” fluctuates
widely, the flow and velocities fluctuate accordingly, this means that the
signal quality detected is too poor. It may be the resulted of poor pipe-
installation conditions, inadequate transducer installation or incorrect
parameter input.
Generally, “Delta Time” fluctuation should be less than ±20%. Only when the
pipe diameter is too small or
velocity is too low can the fluctuation be wider.
4.2.4. Transit Time Ratio
Transit Time Ratio indicates if the transducer mounting spacing is accurate.
The normal transit time ratio should be 100+/-3 if the installation is proper.
Check it in Window M04.
Attention
If the transit time ratio is over 100± 3%, it is necessary to check:
(1) If the parameters (pipe outside diameter, wall thickness, pipe material,
liner, etc.) have been entered correctly,
(2) If the transducer mounting spacing is accordance with the display in
Window M14, (3) If the transducer is mounted at the pipe’s centerline on the
same diameter, (4) If the scale is too thick or the pipe mounting is distorted
in shape, etc.
15
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
4.2.5. Warnings
(1) Pipe parameters entered must be accurate; otherwise the Flow meter will
not work properly. (2) During the installation, apply enough coupling
compounds in order to stick the transducers onto the
pipe wall. While checking the signal strength and Q value, move the
transducers slowly around the mounting site until the strongest signal and
maximum Q value can be obtained. Make sure that the larger the pipe diameter,
the more the transducers should be moved. (3) Check to be sure the mounting
spacing is accordance with the display in Window M14 and the transducer is
mounted at the pipe’s centerline on the same diameter. (4) Pay special
attention to those pipes that formed by steel rolls (pipe with seams), since
such pipe is always irregular. If the signal strength is always displayed as
0.00, that means there is no signal detected. Thus, it is necessary to check
that the parameters (including all the pipe parameters) have been entered
accurately. Check to be sure the transducer mounting method has been selected
properly, the pipe is not worn-out, and the liner is not too thick. Make sure
there is indeed fluid in the pipe or the transducer is not too close to a
valve or elbow, and there are not too many air bubbles in the fluid, etc. With
the exception of these reasons, if there is still no signal detected, the
measurement site has to be changed. (5) Make sure that the Flow meter is able
to run properly with high reliability. The stronger the signal strength
displayed, the higher the Q value reached. The longer the Flow meter runs
accurately, the higher the reliability of the flow rates displayed. If there
is interference from ambient electromagnetic waves or the signal detected is
too poor, the flow value displayed is not reliable; consequently, the
capability for reliable operation is reduced. (6) After the installation is
complete, power on the instrument and check the result accordingly.
16
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
5.Operating Instructions
5.1. System Normal Identification
If the letter “*R” displays on the screen, it indicates system normal. If the
letter “D” is displayed, it indicates that system is adjusting the signal gain
prior to the measurement. Also, it means system normal. Only when the
adjustment takes too long without stopping, can system be identified as
abnormal. Letter “E” indicates no signal is being detected. Check the
transducer wiring connections are correct, the transducers are installed
firmly, etc. For further information, please refer to “Error Diagnosis”.
5.2. Low Flow Cutoff Value
The data in M21 is Low Flow Cutoff Value. If the flow rate falls below the low
flow cutoff value, the flow indication is driven to zero. This function can
prevent the flow meter from displaying flow as “0”after a pump was shut down,
but there is still liquid movement in the pipe, which will result in
cumulative error. Generally, 0.03m/s is recommended to enter as the low flow
cutoff point. The low flow cutoff value has no relation to the measurement
results once the velocity increases over the low flow cutoff value.
5.3. Zero Settings
Once zero flow occurs, a zero point may indicate on each measuring instrument,
but the displayed measuring value is not equal to “0”, this value indicates
“Zero”. To any measuring instrument, the smaller the “Zero” is, the better the
quality is. Conversely, if the Zero is too big, that indicates the quality of
the instrument is poor. If the zero set point is not at true zero flow, a
measurement difference may occur. The smaller the physical measurement
capacity is, the larger the measurement difference from the zero point will
exist. Only when zero point reduced to a definite degree, as compared with the
physical measurement capacity, can the measuring difference from zero point be
ignored. For an ultrasonic Flow meter, the measurement error from zero point
cannot be ignored under low flow conditions. It is necessary to perform a
static zero set calibration to improve low flow measurement accuracy. Cutoff
Zero In Window M22- Cutoff- 1.Yes, window will show the “success” and back to
M01 when you cut off the zero point successfully. Performing Set Zero In
Window M22- Reset
5.4. Scale Factor
Scale factor refers to the ratio between “actual value” and “reading value”.
For example, when the measurement is 2.00, and it is indicated as 1.98 on the
instrument, the scale factor reading is 2/1.98. This means that the best scale
factor constant is 1. However, it is difficult to keep the scale factor as “1”
on the instrument especially in batch productions. The difference is called
“consistency”. During operation, there still exists possible difference in
pipe parameters, etc. The “scale factor” may be necessary when used on
different pipes. Thus, scale factor calibration is specially designed for
calibrating the differences that result from application on different pipes.
The scale factor entered must be one that results from actual flow
calibration. The scale factor can be input in Window M26.
17
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
5.5. System Lock
System lock is intended to prevent operation error due to tampering by
unauthorized personnel. M54 is for system lock, unlock it by using the
selected password only. If “lock” is displayed on the screen, then enter the
correct password. Keep the password in mind or recorded in a safe place,
otherwise the instrument cannot be used.
5.6. 4 ~ 20mA Current Loop Output
With a current loop output exceeding an accuracy of 0.1%, the flow meter is
programmable and configurable with outputs such as 4 ~ 20mA or 0 ~ 20mA
selected in Menu 32. For details, please refer to Menu 32 in “Window Display
Explanations”. In Window M32- Range- LowL, enter a 4mA flow value. Enter the
20mA flow value in Window M32Range-UpperL. For example, if the flow range in a
specific pipe is 0 ~ 1000m3/h, enter 0 in Window M32 and 1000 in Window M32.
If the flow ranges from -1000 ~ 0 ~ 2000m3/h, configure the 20 ~ 4 ~ 20mA
output by selecting in Window M32 when flow direction is not an issue. Enter
1000 in Window M32 LowL and 2000 in Window M32 UpperL. When flow direction is
an issue, module 0 ~ 4 ~ 20mA is available. When the flow direction displays
as negative, the current output is in range of 0 ~ 4mA, whereas the 4 ~ 20mA
is for the positive direction. The output module options are displayed in
Window M32. Calibrating and testing the current loop is performed in Window
M32-Check. Complete the steps as follows: Use “” and “” to switch. “check
4mA”, “check 8mA”, “check 16mA”, “check 20mA” readings, connect an ammeter to
test the current loop output and calculate the difference. Calibrate the
4-20mA is in M62.
5.7. Frequency Output
The flow meter is provided with a frequency output transmitter function. The
high or low frequency output displayed indicates the high or low flow rate
reading. The user can reset the frequency output as well as flow rate as the
user’s actual requirements. For example: if a pipe flow range is 0 ~ 5000m3/h,
the relative frequency output required is 100 ~ 1000Hz, and the configuration
is as follows: In Window M33-Range-LowerL (lower limit frequency output flow
value), input 0; In Window M33-Range -UpperL (upper limit frequency output
flow value), input 5000; In Window M33-Mode-Frange( frequency range), input
1001000; In Window M33-Mode-Option, select “a.Flow Rate”; Typical OCT Output
wiring diagram as below:
18
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
5.8. Totalizer Pulse Output
Each time the flow meter reaches a unit flow, it may generate a totalizer
pulse output to a remote counter. The totalizer pulse output can be
transmitted through OCT or a relay. Therefore, it is necessary to configure
OCT and the relay accordingly. (Please refer to Window M33 and M34). For
example, if it is necessary to transmit the positive totalizer pulse through a
relay, and each pulse represents a flow of 10m3, the configuration is as
follows: In Window M41-Unit, select the totalizer flow unit “m3”; In Window
M41-MULT, select the scale factor “e. x10”; In Window M34-Option, select “g.
POS Total “;
Attention Make sure to select an appropriate totalizer pulse. If the totalizer
pulse is too big, the output cycle will be too long; if the totalizer is too
small, the relay will operate too faster, you may shorten the life of the
relay, as well as skip some pulses. The totalizer is recommended to transmit
within the range of 1 ~ 3 pulse per second.
5.9. Alarm Programming
The on-off output alarm is generated through OCT or transmission to an
external circuit by opening or closing a relay. The on-off output signal is
activated under the following conditions:
(1) Signal not detected; (2) Poor signal detected; (3) The flow meter is not
ready for normal measurement; (4) The flow is in the reverse direction (back
flow). (5) The analog outputs exceed span by 120%. (6) The frequency output
exceeds span by 120%. (7) The flow rate exceeds the ranges configured
(Configure the flow ranges using the software alarm system.
There are two software alarms: Alarm#1 and Alarm #2. Example 1: When flow rate
exceeds 300 ~ 1000 m3/h, in order to program the relay output alarm, Complete
the steps as follows:
(1) In Menu 35, Alarm1 LowL 300; (2) In Menu 35, Alarm1 Upper 1000; (3) In
Menu 34, Relay Setting-Option-d.Alarm1
5.10.4-20mA Analog Output Calibration
Attention Each flow meter has been calibrated strictly before leaving factory.
It is unnecessary to carry out this step except when the current value
(detected while calibrating the current loop) displayed in Window M32 is not
identical with the actual output current value.
The hardware detect window must be activated prior to calibration the Analog
Output. The procedure is as follows: Menu 62 is for 4-20mA calibration, if you
need enter the pass word to enter. With no effect to next power on, this
window will close automatically as soon as the power is turned off. Use “” and
“” to switch. Calibrate the current loop 4mA output. Use an ammeter to measure
the output current of current loop and adjust the displayed numbers at the
same time. Watch the ammeter until it reads 4.00.
19
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
Stop at this point, the 4mA has been calibrated. Use “” and “” to switch.
Calibrate the current loop 20mA output. The method is the same as 4mA
calibration. The results are automatically saved in EEPROM and won’t lose when
power off.
5.11.SD Card Operation
5.1.1. Specifications
Data collection interval: any interval settings from 1 to 3600 seconds are OK
according to the requirement. Data content: date and time, flow rate, flow
velocity, total flow, positive totalizer, negative totalizer. Data storage
format:
a=2017-11-16,16:21:12 b=+2.652471E+00 m3/h c=+9.380460E-02 m/s d=+3.520580E+02
m3 e=+3.520580E+02 m3 f=+0.000000E+00 m3 g=+0.000000E+00 GJ/h h=+0.000000E+00
GJ i=+0.000000E+00 GJ j=+0.000000E+00C k=+0.000000E+00
CFile system format:
FAT16. File type: plain text file (.TXT). File number: maximum 512pcs. It can
save 120 bytes of data each time. If it is set to save once in per 5 seconds,
the capacity of storing file in 24 hours is 1203600/5242073600byte2.1Mbyte,
therefore, 1Gbyte SD card can store for days: 1024/2.1= 487.6487 days. When
the capacity of the SD card is full, the new data will override the earliest
files automatically.
5.1.2. Install or Remove the SD card while the meter is powered on
If the operator desires to insert the SD card with power on, please remove the
power with power off. The following operation is to be used:
Attention: Do not remove the SD card from the reader while actively working
with the data. Data should be saved and stored in a separate location on the
PC, and then processed form that file location. Processing the data directly
from the SD card file location on the PC could result in losing or destroying
data if the SD card is removed while still being processed.
20
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
5.1.3. ESN
We provide the flow meter with a unique electronic serial number to identify
each flow meter for the convenience of the manufacturer and customers. The
ESN, instrument types and versions are able to view in Window M50.
ATTENTION
Other Operating Refer to “6.2 Window Display Explanations”.
21
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
6. Windows Display Explanations
6.1. Windows Display Codes
M0X M1X M2X M3X
Easy Introduction Display Value and Condition R- System Normal E – Signal
Not Detected *D- Adjusting Gain
Installation Setting
Calibration Setting
Input and Output Settings
A class of the menu M00 Flow Totalizer M01 Flow Rate M02 Hot M03 Cool M04 Status M10 Pipe Settings M11 Lining Settings M12 Liquid Settings M13 Transducer Settings M14 Installation Space M20 Damping M21 Low Flow Cut off Value M22 Zero Point Settings M23 Totalizer M24 Temperature M25 Power -off COMP M26 K Factor M27 Correction M28 SQA M30 Serial Port Parameter M31 AI Settings M32 CL Settings M33 OCT Settings
22
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M3X M4X M5X M6X
Input and Output Settings Flow Unit Opinions System Settings Others
M34 Relay Settings M35 Alarm Value Settings M36 Ration M37 Micro SD Settings (option ) M40 Toggle Units M41 Flow Units M42 Energy Units M43 Temperature Units M50 Serial Number M51 Time and Date M52 Key Ton M53 Language M54 System Lock M55 System Reset M60 Date Totalizer M61 Running Timer M62 CL Adjust M63 RTD Adjust M64 AI Adjust
NOTEThe other menu features are retained by manufacturers.
23
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
6.2. Display Explanations
M00
Flow Total Display Net Totalizer. Display Positive totalizer. Display Negative
totalizer.
Use
and
to switch.
M01
Flow Rate
Display the Flow Rate and Flow Total
Display the Velocity.
- Flow Rate and the Flow Total switch every 6 seconds, Use the ENTER to stop the switch.
24
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M02
Heat Rate Display the Heat Total. Display the Heat Rate and the Inlet Water
Temp and Outlet Water Temp. NOTE: Instrument needs energy capacity.
x 0.001 (E-3)
x 0.01(E-2)
x 0.1(E-1)
x 1(E+0)
x 10(E+1)
x 100(E+2)
x 1000(E+3)
x 10000(E+4)
- Heat Rate and the Heat Total switch every 6 seconds, Use the ENTER to stop the switch.
Cool Rate
Display the Cool Total.
Display the Cool Rate and the Inlet Water Temp and Outlet Water Temp.
NOTE: Instrument needs energy capacity.
x 0.001 (E-3)
x 0.01(E-2)
x 0.1(E-1)
x 1(E+0)
x 10(E+1)
x 100(E+2)
x 1000(E+3)
x 10000(E+4)
- Cool Rate and the Cool Total switch every 6 seconds, Use the ENTER to stop the switch.
25
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M04
Status Display the Signal strength, the Upstream signal strength and
Downstream signal strength. Signal quality Q is indicated by 00 ~ 99.
Therefore, 00 indicates the poorest signal while 99 indicates the best signal.
Normally, signal quality Q value should be better than 60
Display the measured fluid sound velocity. Normally this value should be
approximately equal to the entered value in Window M12. If the difference is
too large, it probably results from an incorrect value entered in Window M12
or improper installation of the transducers. Display the ratio between the
actual measured transmit time and the calculated transmit time according to
customer’s requirement. Normally the ratio should be 100±3. If the difference
is too large, the user should check that the parameters are entered correctly,
especially the sound velocity of the fluid and the installation of the
transducers. This data is of no use before the system is ready. Display the
measured ultrasonic average time (unit: us) and delta time of the upstream and
downstream (unit: ns) time. The velocity calculation in the flow meter is
based on the two readings. The delta time is the best indication that the
instrument is running steadily. Normally the fluctuation in the ratio of the
delta time should be lower than 20%. If it is not, it is necessary to check if
the transducers are installed properly or if the parameters have been entered
correctly.
26
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M10
Pipe settings Enter the pipe outer diameter; the pipe outer diameter must
range from 25mm to 1200mm. Note: Enter Either pipe outer diameter or pipe
outer perimeter Enter the pipe wall thickness. Pipe wall thickness is
necessary.
Enter pipe material. The following options are available: 0. PVC 1. CS Carbon
Steel 2. SSP Stainless Steel Pipe 3. CIP Cast Iron Pipe 4. DIP Ductile Cast
Iron Pipe 5. Copper 6. Alu. Aluminum pipe 7. ACP Asbestos Cement Pipe 8. FPG
Fiberglass Pipe 9. Other It is possible to enter other materials, which are
not included in previous eight items. Once item 9 is selected, the relevant
pipe sound velocity must be entered.
M11
Lining Enter liner thickness. Refer to item 9 “Other”; it is possible to enter
other materials, which are not included in previous eight items. Once item 9
is selected, the relevant pipe sound velocity must be entered. Use and to
switch.
27
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M11
Lining Enter liner thickness. Select the Liner Material. The following options
are available: 0. No liner 1. Tar Epoxy 2. Rubber 3. Mortar 4. PP
Polypropylene 5. Polystryol 6. PS Polystyrene 7. Polyester 8. PE Polyethylene
9. Ebonite 10. Teflon 11. Other Item 11 “Other” is available to enter other
materials that are not included in previous ten items. Once the “Other” is
selected, the relevant liner sound velocity must be entered.
M12
Medium Select the temperature of water. Temperature should be 0-80 deg. C.
Press “Enter” to confirm. Note: Room temperature is 25 deg.C
28
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M13
Transducer Select transducer type The following options are available: 0.
Clamp-On C 1. Clamp-On D 2. Clamp-On X 3. Plus-In 4. Plus-In X Select
transducer Mounting Methods Three mounting methods are available: 0. V Reflect
method 1. Z Direct method 2. N
29
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M14
Installation space This value is calculated by the flow meter The operator
must mount the transducer according to the transducer spacing displayed
(ensure that the transducer spacing is measured precisely during
installation). The system will display the data automatically after the pipe
parameter had been entered.
M20
Damping The damping factor ranges from 1 ~ 999 seconds.1 indicates no damping;
999 indicates the maximum damping. The damping function will stabilize the
flow display. Usually a damping factor of 3 to 10 is recommended in
applications.
M21
Low Vel. Cut off Low Flow Cut off is used to make the system display as “0”
value at lower and smaller flows to avoid any invalid totalizing. For example,
if the cutoff value is set as 0.03, system will take all the measured flow
velocity values from – 0.03 to + 0.03 as “0”. Generally, 0.03 is recommended
in most applications.
30
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M22
Zero Settings When fluid is in the static state, the displayed value is called
“Zero Point”. When “Zero Point’ is not at zero in the flow meter, the
difference is going to be added into the actual flow values and measurement
differences will occur in the flow meter. Set zero must be carried out after
the transducers are installed and the flow inside the pipe is in the absolute
static state (no liquid movement in the pipe). Thus, the “Zero Point”
resulting from different pipe mounting locations and parameters can be
eliminated. The measuring accuracy at low flow is enhanced by doing this and
flow offset is eliminated.
Select “YES”; reset “Zero Point” which was set by the user.
This method is not commonly used. It is only suitable for experienced
operators to set zero under conditions when it is not preferable to use other
methods. Enter the value manually to add to the measured value to obtain the
actual value. For example: Actual measured value 240 m3/H Value Deviation 10
m3/H Flow meter Display 250 m3/H Normally, set the value as “0”. Use “” and “”
to switch.
31
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M23
Totalizer Select the totalizer type 0. POS Positive Totalizer 1. NEG Negative
Totalizer 2. NET Select energy type 0. Heat 1. Cool Select “ON”/”OFF” to
switch the totalizer.
Select the flow totalizer value you want Reset 0. POS Positive Totalizer 1.
NEG 2. NET Negative Totalizer 3. All Select the energy totalizer value you
want Reset 0. Heat 1. Cool 2. All
M24
Temperature Select Heat Input Options: 0. RTD 1. AI Use “” and “” to switch
32
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
Temperature Sensitivity Setting When the delta temperature is less than the
sensitivity set, energy will not be accumulated. Set the adjustable
temperature range of 0 ~ 20. The factory default setting is 0.2 . Select
Specific Heat Options: 0. CJ128 SHC 1. Other Use “” and “” to switch.
M25
Power Down Correction Switch With the function of power down automation
correction switch, the flow lost in an offline session can be estimated and
automatically adjusted. The estimate is based on the average value, which is
obtained from flow rate before going offline and flow measured after going
online the next time, multiplied times the time period that the meter was
offline. Select “ON” to use this function, select “OFF” to cancel this
function.
M26
K Factor The K factor is used to modify the measurement results. The user can
enter a numerical value (other than “1”) according to the actual calibration
results.
33
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M27
Correction K-Array Sectional Correction ON: Open the Sectional Correction
Function; OFF: Close the Sectional Correction Function
Delay correction Engineer menu, suggest customer use the factory setting.
TPC Transducers power control Engineer menu, suggest customer use the factory
setting. 0. Auto 1. Low 2. High
34
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M28
SQA Statistic Analysis
M30
RS232/RS485 Serial Port Setting . 2400 None . 4800 None . 9600 None . 19200
None . 38400 None . 56000 None You can setting the order as following : a.
1-0: 3-2 b. 0-1:2-3 c. 3-2:1-0 d. 2-3:0-1
35
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M31
AI Setting Display analog input AI1 analog value.
Display analog input AI2 analog value.
M32
CL Setting Current Loop Mode Options
Select the CL Range value Set the CL output value according to the flow value
at 4mA or 0MA. Set the CL output value according to the flow value at 20mA.
36
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
4-20mA check opinions a. Check 4mA b. Check 8mA c. Check 12mA d. Check 20mA
M33
OCT Setting The following signal options are available: a. Flow Rate b. POS
Total c. NEG Total d. NET Total e. Energy Rate f. Heat Total g. Cool Total h.
Rationing i. Uart CTRL
Select the OCT Range value.
OCT check opinions a. Check 500 b. Check 1000 c. Check 3000 d. Check 5000
37
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M34
Relay Setting The following signal options are available: a. No Signal b. *E
c. Reverse d. Alarm1 e. Alarm2 f. Ration g. POS Total h. NEG Total i. NET
Total j. Not Using
M35
Alarm Setting Enter the Lower alarm value, any of the measured flow, which is
lower than the low value, will activate the alarm in the OCT hardware or relay
output signal.
Enter the Upper alarm value, any of the measured flow, which is higher than
the high value, will activate the alarm in the OCT hardware or relay output
signal.
38
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M36
Ration Following is the Ration opinions: a. Key CTRL b. AI1 CTRL c. AI2 CTRL
d. Uart CTRL
M37
Micro SD Following is the opinions for the record. a. No Energy b. All Input
the data collection time interval in this menu. Time is in seconds. The
interval can be selected in the range of 1 ~ 3600 seconds. NOTE: this is an
option.
M40
Toggle Unit Select the measurement unit as follows: a. Metric b. British
M41
Flow Unit
The following flow rate units are available:
0. Cubic Meters (m3)
1. Liters
(1)
2. USA Gallons (GAL)
3. Imperial Gallons (Imp gal)
4. Million Gallons (mg)
5. Cubic Feet
(cf)
6. USA Barrels (US bbl)
7. Imperial Barrels (Imp bbl)
8. Oil Barrels
(Oil bbl)
The following time units are available:
/Day
/Hour
/Min
/Sec
39
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
Factory default is Cubic Meters/hour.
a. x 0.001 (E-3)
b. x 0.01(E-2)
c. x 0.1(E-1)
d. x 1(E+0)
e. x 10(E+1) g. x 1000(E+3)
f. x 100(E+2)
h. x 10000(E+4)
M42
Energy Unit The following Energy units are available:
0. Giga Joule (GJ) 1. Kilocalorie (Kc)
2. MBtu
3. KJ
4. Btu
5. KWh
6. MWh
7. TH
a. x 0.001 (E-3) c. x 0.1(E-1) e. x 10(E+1) g.x 1000(E+3)
b. x 0.01(E-2) d. x 1(E+0) f. x 100(E+2) h.x 10000(E+4)
M43
Temperature Unit a. b. Use “” and “” to switch.
40
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M50
Serial Number Display electronic serial number (S/N) of the instrument. This
S/N is the only one assigned to each flow meter ready to leave the factory.
The factory uses it for files setup and for management by the user. SVN is the
software version
M51
Time and Data Date and time modifications are made in this menu.
M52
Key Tone Use this menu to “ON”/ “OFF” the key tone.
M53
Language Setting the language of the flow meter 0.English 1.Chinese
41
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M54
System Lock Lock the instrument. Once the system is locked, any modification
to the system is prohibited, but the parameter is readable. Entering your
designated password correctly can be the only way to “Unlock”. The password is
composed of 6 numbers. (Please contact the representative or manufacturer as
soon as possible when the password is lost.)
M55
System Reset Select 1. Reset to make the instrument back to factory.
M60
Date Totalizer The following options are available:
0. Day 1. Month 2. Year In this window, it is possible to review the
historical flow data net totalizer for any day for the last 31 days, any month
for last 12 months and any year for last 6 years.
M61
Running Time With this function, it is possible to view the total Working days
since the flow meter left the factory.
42
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
M62
CL Adjust This menu is for the 4-20mA calibration; enter the pass word to
adjust.
M63
RTD Adjust This menu is for the RTD calibration; enter the pass word to
adjust.
M64
RTD Adjust This menu is for the AI calibration; enter the pass word to adjust.
Warning The entire Menu which related to the temperature, cooling, heating,
energy. Only display when it’s an energy meter. Flow meter doesn’t have the
function.
43
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
7. Error Diagnoses
The ultrasonic flow meter has advanced self-diagnostics functions and displays
any errors in the upper right corner of the LCD via definite codes in a
date/time order. Some errors can be detected during normal operation.
Undetectable errors caused by unskilled operation, incorrect settings and
unsuitable measurement conditions can be displayed accordingly during work.
This function helps the user detect the errors and find causes quickly; thus,
problems can be solved in a timely manner according to the solutions listed in
the following table.
If a problem still exists, please contact the factory or the factory’s local
representative for assistance.
7.1. Table 1. Error Codes and Solutions (during operation)
Codes
The upper right corner of the screen
*R System Normal
Signal Not Detected
*E
Adjusting Gain *D
Causes
Solutions
-
System normal.
-
Signal not detected.
-
Spacing is not correct between the transducers or not enough coupling compound applied to face of transducers.
-
Transducers installed improperly.
-
Scale is too thick.
-
New pipe liner.
-
Attach transducer to the pipe and tighten it securely. Apply a plenty of coupling compound on transducer and pipe wall.
-
Remove any rust, scale, or loose paint from the pipe surface. Clean it with a file.
-
Check the initial parameter settings.
-
Remove the scale or change the scaled pipe section. Normally, it is possible to change a measurement location. The instrument may run properly at a new site with less scale.
-
Wait until liners solidified and saturated.
-
Adjusting gain for normal measurement.
44
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
7.2. Frequently Asked Questions and Answers
Question: New pipe, high quality material, and all installation requirements
met: why still no signal detected?
Answer: Check pipe parameter settings, installation method and wiring
connections. Confirm if the coupling compound is applied adequately, the pipe
is full of liquid, transducer spacing agrees with the screen readings and the
transducers are installed in the right direction.
Question: Old pipe with heavy scale inside, no signal or poor signal detected: how can it be resolved?
Answer:
Check if the pipe is full of fluid. Try the Z method for transducer
installation (If the pipe is too close to a wall, or it is necessary to
install the transducers on a vertical or inclined pipe with flow upwards
instead of on a horizontal pipe).
Carefully select a good pipe section and fully clean it, apply a wide band of
coupling compound on each transducer face (bottom) and install the transducer
properly.
Slowly and slightly move each transducer with respect to each other around the
installation point until the maximum signal is detected. Be careful that the
new installation location is free of scale inside the pipe and that the pipe
is concentric (not distorted) so that the sound waves do not bounce outside of
the proposed area.
For pipe with thick scale inside or outside, try to clean the scale off, if it
is accessible from the inside. (Note: Sometimes this method might not work and
sound wave transmission is not possible because of the a layer of scale
between the transducers and pipe inside wall).
Question: Why is the CL output abnormal?
Answer: Check to see if the desired current output mode is set in Window
M32-Mode. Check to see if the maximum and minimum current values are set
properly in Windows M32-Range. Re-calibrate CL and verify it in Window
M32-Check.
Question: Why is the flow rate still displayed as zero while there is fluid
obviously inside the pipe and a symbol of “R” displayed on the screen?
Answer: Check to see if “Set Zero” was carried out with fluid flowing inside
the pipe (Refer to Window M22). If it is confirmed, recover the factory
default in Window M22-Reset.
45
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
8. Appendix 3 Serial Interface Network Use and Communications Protocol
8.1. Overview
The flow meter has perfect communication protocol. It can also be connected to
a RS-485 Modbus .
Two basic schemes can be chosen for networking, i.e. the analog current output
method only using the flow meter or the RS232 communication method via serial
port directly from the flow meter. This method is suitable to replace dated
instruments in old monitoring networks. The later method is used in new
monitoring network systems. It has advantages include low hardware investment
and reliable system operation.
When the serial port communications method is directly used to implement a
monitoring network system, the address identification code of the flow meter
is used as a network address code. Expanded command set with [W] is used as
communication protocol.
RS-232 (Cable length 0 ~ 15m ) or RS-485 ( cable length 0 ~ 1000m ) can be
directly used for data transmission links for a short distance. Current loop
can be used in medium or long distance transmission.
When the flow meter is used in a network environment, various operations can
be performed by a host device, except for programming of the address
identification code, which needs to be done via the flow meter keyboard.
The command answer mode is used in data transmission, i.e. the host device
issues commands and the flow meter answers correspondingly.
Common/special flow / thermal data monitoring system developed by our company
can be used for flow data collection. Based on characteristics of the flow
meter, the system makes full use of software and hardware designs with flow
meter features. The system is simple, clear, economical, and reliable in
operation.
Attention
In the communication protocol used functions, RS232 and RS485 serial
communications cannot be used at the same time.
8.2. Serial port definitions
Flow meter – RS232: TXD send RXD receive GND ground
PC: PIN 1 empty PIN 2 RXD send
PIN 3 TXD send PIN 4 ground PIN 5 ground PIN 6 empty PIN 7 empty PIN 8 empty PIN9empty
46
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
8.3. Direct connection via RS232 to the host device
See the below list of flowmeter serial port definitions.
8.4. Communications protocol and the use
The flow meter supports these three communication protocols: FUJI Protocol,
MODBUS-C Protocol, MODBUS-I Protocol.
8.4.1. HL Protocol
The communication protocol format used by the ultrasonic flow meter is an
expanded set of the HL FLV series flow meter protocol. The host device
requests the flow meter to answer by sending a “command”. The baud rate of
asynchronous communication (Primary station: computer system; Secondary
station: ultrasonic flow meter) is generally 9600BPS. A single byte data
format (10 bits): one start bit, one stop bit and 8 data bits. Check bit:
none.
A data character string is used to express basic commands and a carriage
return (ENTER) is used to express the end of a command. The characteristic is
that the string of data is flexible. The order applies to both RS232 and
RS485. Frequently used commands are as follows:
Communications commands
Command
Description
Data format
RFR(cr)(lf)
Return instantaneous flow
±d.ddddddE±dd(cr) Note1
RVV(cr)(lf)
Return instantaneous velocity
±d.ddddddE±dd(cr)
RT+(cr)(lf)
Return positive accumulative flow
±ddddddd.dE±d(cr) Note 2
RT-(cr)(lf)
Return negative accumulative flow
±ddddddd.d±d(cr)
47
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
RTN(cr)(lf)
Return net accumulative flow
±ddddddd.d±d(cr)
RTH(cr)(lf)
Return net accumulative energy(hot)
±ddddddd.d±d(cr)
RT-(cr)(lf)
Return net accumulative energy(cold)
±ddddddd.d±d(cr)
RER(cr)(lf)
Return instantaneous energy value
±d.ddddddE±dd(cr)
RA1(cr)(lf)
Return analog input value of AI1 (Temperature, Pressure, etc.)
±d.ddddddE±dd(cr)
RA2(cr)(lf)
Return analog input value of AI2 (Temperature, Pressure, etc.)
±d.ddddddE±dd(cr)
RID(cr)(lf)
Return Net address of the instrument
ddddd(cr) 5 bits in length
RSS(cr)(lf)
Return signal intensity
UP:dd.dDN:dd.dQ=dd(cr)
REC(cr)(lf)
Return current error code
R/D/*E Note 3
RRS(cr)(lf)
Return Relay Status
ON/OFF(cr)
RDT(cr)(lf)
Current date and time
yy-mm-ddhh:mm:ss(cr)
RSN(cr)(lf)
Return serial number
dddddddt(cr) Note 4
SFQdddd.d(cr)(lf) OCT setting
dddd.d(cr) Successful setting will back to “OK”
SCLdd.d(cr)(lf)
Current setting
dd.d(cr) Successful setting will back to “OK”
SRS(cr)(lf)
Start quantitative control
OK(cr) Successful setting will back to “OK”
P
Prefix of return command with check
Note 5
W
Networking command prefix of numeric string address
Note 6
Note:
1.(cr)expresses carriage return. Its ASCII value is 0DH. (lf) expresses line
feed. Its ASCII value is 0AH.
2.”d” expresses 0-9 number. 0 value is expressed as +0.000000E+00.
3.”d” expresses 0-9 numbers. There is no decimal point in integral part before
“E”.
4. dddddddd means the serial number of the instrument, t means the model of
the instrument.
5. The character P can be added before every basic command. It means that the
transferred data has CRC verification. The method of verification is to add
all of the data back to the data, which is cumulative and binary, and its low
8-bit binary data is taken.
E.g. The return information of the RT(cr)(lf) is :+1234567E+0m3(cr)(lf), (the
relative binary system data is 2BH31H32H33H34H35H36H37H45H2BH30H6DH33H20H0DH
48
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
0AH) The sum of all of its return data is =2BH+31H+32H+33H+34H+35H+
36H+37H+45H+2BH+30H+6DH+33H+20H=2F7, The low 8-bit data of its binary is F7.
Therefore, the data of the order PRT (cr) (lf) is called + 1234567E + 0m3!F7
(cr) (lf), “!”For delimiters, the preceding is the character of the summation,
followed by a check code of 1 byte.
6.Usage of prefix W: W+ numeric string address code +basic command. Value
range of the numeric string is 0 ~ 255, except 13 (0DH carriage return ), 10 (
0AH line feed ). If the instantaneous velocity of No. 123 flow meter is to be
accessed, the command W123DV (cr)(lf) can be issued. The corresponding binary
code is 57H, 31H, 32H, 33H, 44H, 56H, 0DH, 0AH, only the same instrument with
the same address of the Internet address and command will send back the data.
7.W and P commands can be used in combination, for example, W123PRT +, which
means that the instrument that reads the network address is the cumulative
value of the instrument with 123, and its return data has eight accumulations
and checksums.”s” expresses ON or OFF or UD. For example, “TR:ON, RL:ON”
expresses that the OCT and relay are in an actuated status; “TR:UDRL:UD”
expresses that the OCT and relay are not actuated.
8.4.2. MODBUS-I Communication Protocol
This MODBUS-I Protocol uses RTU transmission mode. The Verification Code uses
CRC-16-IBM (polynomial is X16+X15+X2+1, shield character is 0xA001) which is
gained by the cyclic redundancy algorithm method. MODBUS-I RTU mode uses
hexadecimals to transmit data.
1. MODBUS-I Protocol Function Code and Format The flow meter protocol
supports the following two-function codes of the MODBUS:
Function Code
Performance data
0x03
Read register
0x06 2. MODBUS Protocol function code 0x03 usage The host sends out the read register information frame format:
Write single register
Slave Address 1 byte
Operation Function Code
1 byte
First Address Register 2 bytes
Register Number 2 bytes
Verify Code 2 bytes
0x01 ~ 0xF7
0x03
0x0000 ~ 0xFFFF
0x0000 ~ 0x7D
CRC (Verify )
The slave returns the data frame format:
Slave Address
Read Operation Function Code
Number of Data Bytes
1 byte
1 byte
1 byte
0x01 ~ 0xF7
0x03
2xN*
N* = Data register number 3. MODBUS Protocol function code 0x06 usage
Data Bytes Nx2 byte Nx2 ( Data )
Verify Code 2 bytes
CRC ( Verify )
49
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
The host sends a command to write a single register information frame format ( function code 0x06 ):
Slave Address 1 byte
Operation Function Code
1 byte
Register Address 2 bytes
Register Data 2 bytes
Verify Code 2 bytes
0x01 ~ 0xF7
0x06
0x0000 ~ 0xFFFF
0x0000 ~ 0xFFFF CRC ( Verify )
The slave returns the data frame format ( function code 0x06 ):
Slave Address 1 byte
Operation Function Code
1 byte
Register Address 2 bytes
Register Data 2 bytes
Verify Code 2 bytes
0x01 ~ 0xF7
0x06
0x0000 ~ 0xFFFF
0x0000 ~ 0xFFFF CRC ( Verify )
The range of flow meter addresses 1 to 247 (Hexadecimal: 0x01 ~ 0xF7 ), and
can be checked in the Menu 46. For example, decimal number “11” displayed on
Menu 46 means the address of the flow meter in the MODBUS protocol is 0x0B.
The CRC Verify Code adopts CRC-16-IBM (polynomial is X16+X15+X2+1, shield
character is 0xA001) which is gained by the cyclic redundancy algorithm
method. Low byte of the verify code is at the beginning while the high byte is
at the end.
For example, to read the address 1 (0x01) in the RTU mode, if the instantaneous flow rate uses hour as a unit m3/h, namely reads 40005 and 40006 registers data, the read command is as follows:
0x01
0x03
0x00 0x04
0x00 0x02
0x85 0xCA
Flow meter Address Function Code First Address Register Register Numbers CRC Verify Code Flow meter returned data is (assuming the current flow=1.234567m3/h)
0x01
0x03
0x04
0x06 0x51 0x3F 0x9E0x3B 0x32
Flow meter Address Function Code Data Bytes Data1.2345678 CRC Verify Code
The four bytes 3F 9E 06 51 is in the IEEE754 format single precision floating point form of 1.2345678.
Pay attention to the data storage order of the above example. Using C language to explain the data, pointers can be used directly to input the required data in the corresponding variable address, the low byte will be put at the beginning, such as the above example 1.2345678 m/s, 3F 9E 06 51 data stored in order as 51 06 9E 3F.
For example, it converts the address 1 (0x01) to 20x02under the RTU mode, so to write the data of flowmeter 44100 register as 0x02, the write command is as follows:
0x01
0x06
0x10 0x03
0x00 0x02 0xFC 0xCB
Flow meter Address Function Code Register Address Register Number CRC Verify Code
Flow meter returned data is:
0x01
0x06
0x10 0x03
0x00 0x02 0xFC 0xCB
Flow meter Address Function Code Register Address Register Number CRC Verify Code
4. Error Check
The flow meter only returns one error code 0x02 which means data first address in error.
50
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
For example, to read address 1 (0x01) of the flow meter 40002 register data in the RTU mode, the flow meter considers it to be invalid data, and sends the following command:
0x01
0x03
0x00 0x01
0x00 0x01 0xD5 0xCA
Flow meter Address Function Code Register Address Register Number CRC Verify Code
Flow meter returned error code is:
0x01
0x83
0x02
0xC0 0xF1
Flow meter Address Error Code Error Extended Code CRC Verify Code
5. MODBUS Register Address List The flow meter MODBUS Register has a read register and a write single register. a) Read Register Address List (use 0x03 function code to read)
PDU Address
Register
Read
$0000
40001 Flow/s – low word
$0001
40002 Flow/s – high word
$0002
40003 Flow/m – low word
$0003
40004 Flow/m- high word
$0004
40005 Flow/h – low word
$0005
40006 Flow/h – high word
$0006
40007 Velocity low word
$0007
40008 Velocity high word
$0008
40009 Positive total low word
$0009
40010 Positive total high word
$000A
40011 Positive total exponent
$000B
40012 Negative total low word
$000C
40013 Negative total high word
$000D
40014 Negative total exponent
Write
Type
No. registers*
32 bits real
2
32 bits real
2
32 bits real
2
32 bits real
2
32 bits int.
2
16 bits int.
1
32 bits int.
2
16 bits int.
1
51
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
$000E $000F $0010 $0011 $0012 $0013 $0014 $0015 $0016 $0017 $0018 $0019 $001A
$001B $001C
$001D
40015 Net total low word
40016 Net total high word
40017 Net total exponent
40018 Energy flow low word
40019 Energy flow high word
40020 Energy total(hot) low word
40021 Energy total(hot) high word
40022 Energy total(hot) exponent
40023 Energy total(cold ) high word
40024 Energy total(cold ) exponent
40025 40026 40027 40028 40029
Energy total(cold ) exponent Up signal int low word Up signal int high word Down signal int low word Down signal int high word
40030 Quality
$001E
40031 Error code char 1
$003B $003C $003D $003E $003F
40060 Flow velocity unit char 1,2 40061 Flow velocity unit char 3,4 40062 Flow rate unit char 1,2 40063 Flow rate unit char 3,4 40064 Flow total unit char 1,2
32 bits int.
2
16 bits int.
1
32 bits int.
2
32 bits real 16 bits int. 32 bits real 16 bits int. 32 bits real
2
1
2
1
2
0 ~ 99.9
32 bits real 16 bits int.
String String
2
0 ~ 99.9
1
0 ~ 99
Refer to “Error
1
Analysis” for detailed codes
meanings.
2
Only m/s right now
String
2
String
1
Note 1
52
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
$0040 $0041 $0042 $0043 $0044 $0045 $0046
40065 Energy rate unit char1,2 40066 Energy rate unit char 3,4 40067 Energy total unit char 1,2 40068 Instrument address low word 40069 Instrument address high word 40070 Serial number char 1,2 40071 Serial number char 3,4
String
2
String
1
32 bits real
2
String
4
Note 2
$0047 $0048
40072 Serial number char 5,6 40073 Serial number char 7,8
String
4
$0049 $004a $004b $004c
40074 Analog Input AI1 Value- low word 40075 Analog Input AI1 Value- high word
32 bits real
40076 Analog Input AI2 Value- low word 40077 Analog Input AI2 Value- high word
32 bits real
2
Returned temperature value with RTD option
2
$004d $004e
40078 4-20mA Value- low word 40079 4-20mA Value- high word
32 bits real
2
Unit: mA
b) Single Write Register Address List ( use 0x06 performance code to write )
PDU Address Register
Description
Read/W rite
Type
No. registers*
$1003
44100
Flow meter address ( 1 – 255 )
R/W
16 bits int.
1
Communication Baud Rate 0 =
$1004
44101
2400,1 = 4800, 2 = 9600, 3 =
R/W
16 bits int.
1
19200, 4 = 38400,5 = 56000
Notes: 1.
The following flow rate units are available: 0. “m3” Cubic Meter 1. “l” Liters 2. “ga” Gallons
53
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
3. “ig” Imperial Gallons 4. “mg” Million Gallons 5. “cf” Cubic Feet 6. “ba”
US Barrels 7. “ib” Imperial Barrels 8. “ob” Oil Barrels 2. The following
energy units are available 0. “GJ” Giga Joule 1. “Kc” Kilocalorie 2. “MB” MBtu
3. “KJ” Kilojoule 4. “Bt” Btu 5. “Ts” US Tonnes 6. “Tn” US Tons 7. “kw” Kwh 3.
16 bits int–short integer, 32 bits int long integer, 32 bits real–floating
point number, String–alphabetic string
54
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
9. Appendix 6 – Flow Application Data
9.1. Sound Velocity for Various Materials Commonly Used
Pipe Material Steel ABS Aluminum Brass Cast iron Bronze Fiber glass-epoxy Glass Polyethylene PVC
Sound Velocity (m/s) 3206 2286 3048 2270 2460 2270 3430 3276 1950 2540
Liner Material Teflon Titanium Cement Bitumen Porcelain enamel Glass Plastic Polyethylene PTFE Rubber
Sound Velocity 1225 3150 4190 2540 2540 5970 2280 1600 1450 1600
55
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
9.2. Sound Velocity in Water (1 atm) at different temperatures
t()
v(m/s)
t()
v(m/s)
t()
0
1402.3
34
1517.7
68
1
1407.3
35
1519.7
69
2
1412.2
36
1521.7
70
3
1416.9
37
1523.5
71
4
1421.6
38
1525.3
72
5
1426.1
39
1527.1
73
6
1430.5
40
1528.8
74
7
1434.8
41
1530.4
75
8
1439.1
42
1532.0
76
9
1443.2
43
1533.5
77
10
1447.2
44
1534.9
78
11
1451.1
45
1536.3
79
12
1454.9
46
1537.7
80
13
1458.7
47
1538.9
81
14
1462.3
48
1540.2
82
15
1465.8
49
1541.3
83
16
1469.3
50
1542.5
84
17
1472.7
51
1543.5
85
18
1476.0
52
1544.6
86
19
1479.1
53
1545.5
87
20
1482.3
54
1546.4
88
21
1485.3
55
1547.3
89
22
1488.2
56
1548.1
90
23
1491.1
57
1548.9
91
24
1493.9
58
1549.6
92
25
1496.6
59
1550.3
93
26
1499.2
60
1550.9
94
27
1501.8
61
1551.5
95
28
1504.3
62
1552.0
96
29
1506.7
63
1552.5
97
30
1509.0
64
1553.0
98
31
1511.3
65
1553.4
99
32
1513.5
66
1553.7
33
1515.7
67
1554.0
Refer to the sound velocity of other fluids and materials, please contact the factory.
v(m/s) 1554.3 1554.5 1554.7 1554.9 1555.0 1555.0 1555.1 1555.1 1555.0 1554.9 1554.8 1554.6 1554.4 1554.2 1553.9 1553.6 1553.2 1552.8 1552.4 1552.0 1551.5 1551.0 1550.4 1549.8 1549.2 1548.5 1547.5 1547.1 1546.3 1545.6 1544.7 1543.9
56
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
Ultrasonic Heatmeter Operation Manual
10Selection Code
Tr a n s m i t t e r
Ultrasonic Flowmeter (Energy version) Wall mounted transmitter Flow Range:
±0.03m/s … ±5m/s Accuracy : ±1% measured value Repeatability: 0.2% measured
value Display: 240*128 LCD backlit Power supply: 10-36VDC@1A max Transmitter
housing: IP65, ABS (Temperature: -20grC…50grC) Output: Frequency/pulse output
0-10KHz, Relay, 4-20mA CommuniCation: RS232, Modbus Protocol
Code
Type Transmitter
1
Pulse/frequency, Relay, RS232/RS485, 4-20mA
2 Code
Pulse/frequency, Relay, RS232/RS485, 4-20mA / RTD Type Transmitter
CD01
Clamp-on, IP68. Temperature: -40grC … +80grC
C1U XXX 030 XXX
Clamp-on, IP68. Temperature: –40grC … +130grC Sensor cable length Standard length 9m Max. length 274m
Code
Temperature sensor
PT1000
Pt1000 temperature sensor
Code
Option
AC
AC power, 90 … 245 VAC
SD
SD card (datalogger)
Sample:
Ultrasonic Flowmeter (Energy version) w. Pulse, Relay, RS485, 4-20mA output,
2xPt1000 sensors, max 80grC, 9 m cable
Code: US201-2-CD01-030-PT1000
57
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 |
salesinstrumentation@klinger.dk | www.klinger.dk
KLINGER Danmark A/S Nyager 12-14
DK-2605 Broendby Denmark
Phone +45 4364 6611
www.klinger.dk
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>