QuFRESH MQF Fresh Air Supply Fan Instruction Manual

June 5, 2024
QuFRESH

QuFRESH MQF Fresh Air Supply Fan Instruction Manual

QuFRESH-MQF-Fresh-Air-Supply-Fan-

READ AND SAVE THESE INSTRUCTIONS

READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL,

READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT
YOU AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS cOULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!

RETAIN INSTRUCTIONS FOR FUTURE REFERENCE
GENERAL SAFETY INFORMATION

When using electrical appliances, basic precautions should always be followed to reduce the risk of fire, electric shock and injury to a person, including the following:
WARNING: TO REDUCE THE RISK OF ARĘ, CIRC SHOCK, AND INJURY TO PERSON OBSERVETHEFOLLOWNG

  • be this unit only in the manner intended by the manufacturer.lf you have questions, contact the manufacturer.
  •  service disconnecting means preventing the power fram from being switched accidentally. When the service disconnecting means can not be locked, securely fasten a prominent waning
    the device, such as a tag, to the service panel.
    Before servicing ar deaning the unit, switch power df at the service panel and lock the

WARNING: TO REDUCE THE RISK OF ARĘ, CIRC SHOCK, AND INJURY TO A PERSON, CBSERVETHEFOLLOWNG

  • Installation wark and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-related construction
  • Sufficient air is needed far proper combustion and exhausting d gases through the flue (chimney) of fuel-burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA) and the American Society foar Heating. Refrigeration, and Air Conditioning Engineers (ASHRAE, and the local code authorities
  • When putting drilling into wall ar ogling, donat damage electrical wiring and other hidden utilities

TOBXHALST HAZARDOLSRBPLOSVE MATERIALS AND VA VAPCRSs

CAUTION: FORGEERAL VENILATINGLSE CNLY DO NOT  USE

  • This unit must be grounded
  • To avoid motor bearing damage and noisy and unbalanced impellers, keep drywall spray, construction dust, etc. off the power unit.
  • Read all instructions before installing ar using fan
  • Far residential installations only.
  • Mst use a suitable weather hood with insect screen to protect air intake.

WARNING: to reduce THERSKaF ARE ELECTRIC SHOCK DO NOT USE THS FAN WTHANY SOLID-STATE SPEED CONTROL DANCEAWARNING: DONoT LSE IN INTO-ENS
WARNING: THEDUCINGFROM THS FAN TOTHEaUTSIDE CF TE BUILDING HAS A STRONGEFHECT aN THE ARLON NaSEANDENERGY USECF THE FAN USE THESHORIEST, STRAGHTEST DUCT ROUINGPOSSBLEFORBEST performance AND AVaID INSTALLING THE FANWTH SMALLERDUCTS THAN RECOMMENDED. INSTALLATION AROUND THE DUCTS CAN REDUCE ENERGY LOSS AND
INHIBIT MOLD GROWTH FANS INSTALLED TWISTING DUCTS MAY NOT ACHIEVE SERRATED AIRFLOW

INSTALLATION INSTRUCTIONS

CAUTION: MAKESIFEPONERIS SWTraED CFF AT SERME PANEL BEFCRESTARTINGINSTALLATION

SECTION 1

Preparing the Fan

  1. Unpack fan from the Catan and confirm that all pieces are present. In addition to the fan
    you should have

    • Clar Assembly (attached) 2-Mounting Brackets (attached)
    • 1-Controller (attached) (not included with the P130D model)
    • 1- Instruction/Safety Sheet
  2. choose the location for your fan To ensure the best air ad sound performance, it is recommended that the length d ducting and the number d elbows be kept to a minimum the radius d each elbow be as large as possible far the installation, and that insulated hard during be used This fan will require at least 12 d dearanoe in the ceiling ar wall. The fan mounts using the provided mounting brackets ar can be surface mounted to a wall online.
    NOTE The fan must be installed into a location that can be easily accessed ance installed,

  3. Nbadditicna vibration deadening materials ae needed far this fan

SECTION 2

Mounting the Fan

  1. confirm the fan is positioned so the airflow is in the cart direction

    • Surface Mounting: Locate at least one stud ar just. Mace the fan in position so that the mounting bracket is entered and the stud
      a joist and make the location far the four (4) hales. Remove the fan and install properly rated wall calling anchors far the handles that do nat go directly into ajast a stud. Position farn in place and secure with sarews (not induced) (Figure 1).

    • Mounting to a Joist: Install two- 2×4 headers (nat induced) between the joists. Position the fan housing on top of the headers and secure the mounting brackets with sarews (not induced) to the header (Figure 2).

    • Hanging Bar Mounting: Lift the unit up to the threaded rods and secure in place using appropriate hardware (not included) Figure 3). QuFRESH-MQF-Fresh-Air-Supply-Fan-fig-1

SECTION 3

Ducting
NOTE 6″ RLARCER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE
CAUTION: ALLDuCINGMUST comply with WTHLOCAL AND NATIONAL BUILDING DES
NOTE The ducting from this fan to the outside of the building has a strong effect on the airflow, noise, and energy use of the fan. Use the shortest, straightest duct rating possible
far best performance, and avoid installing the fan with smaller ducts than recommended Insulation around the ducts can reduce energy lass and inhibit mad growth. Fans installed with existing ducts may not achieve their rated ar flow.

AN ALLLOCALAND NATIONAL CODE ANDIS LOCATED AT LEAST 6 FEET AWAY
WARNING: MAKE SURE THE FRESH AIR INTAKE PaRT COMPLIES WTH FROM SOURCES CF CONTAMINATION SUCH AS BUT NOT LIMITED TO DRYER ARNAGE R CENTRAL VACUUM EXHAUSTS, GAS APPLIANCES SUCH AS BBQGRLS GARBAGEANS CROTHEREHALST PORTS
NOTE To ensure quiet operation of in-line ad remote fans, each fan shall be installed using sound attenuation techniques appropriate far the installation This can typically be achieved by installing insulated flexible ducting between the exhaust supply grilles) and the fan

  1. Connect the ducting to the fan’s duct collar (Figure 4). Seal ducting to housing with appropriately rated tape. Ube sCrews ar suitable damps to secure in place. Make sure the fresh air intake is connected to a properly installed intake port that is a suitable weather hood with an insect screen to protect air intake. It is recommended that low restriction termination fittings be used.
  2. Ensure dut joints and exterior penetrations are seated with caik ar other similar material to create an air-tight path to minimize building heat loss ar gain ad to reduce the potential far condensation Raoewrap insulation around duct andar fan in order to minimiæ possible condensation buildup within the dad, as wall as building heat loss ar gain.
    NOTE A the base of the duct adapter, there is a small diameter test part hde covered with a plastic cap. Make sure the test part is ndt covered p with the ducting so that it can be accessed fo pitot tube testing. To access the part, remove the part cover and insert tube.
SECTION 4

Wiring
CAUTION : MAKE SURE PONERIS SWTOHDFAT SERME PANEL PANEL BEFORE STARTING INSTALLATION
CAUTION: WTH ALEERCALCNECTICNS LOCAL CODES CRDINANCEB MUST NATIONAL BE MADE
ELECTRICAL CODE IF YOJAREUNFAMILIARWTH METHODS CFINSTALLINGHBCTRCAL WRNG SEaRETHESERMOESOEAGAIAEDARIRAAN

NOTE This unit includes a side access panel for wiring that does not require the removal df the fan’s blower assembly

  1. Remove the wire compartment cover screw and place cover in a secure place (Figure 5).
  2. Rul the loose black, white and green wires aut from the wiring compartment (additional wires will be present). Install an approved electrical connector to the wire compartment cove (not included). Run a black (hat), white (neutral), and green or bare ground wire from the supply through the electrical connector. Connect all wires from the supply to their corresponding wires within the wire compartment(Figure 6). Uke approved methods for al connections
  3. Carefully tuck wires back inside wire compartment and replace wire compartment cover securing with the sarew that was removed earlier.
SECTION 5

Setting the Speed

  1. Remove the sarews securing the access panel cover in place and open the cover to gain access. Locate the speed contrd panel inside the unit (figure 7).
  2. Determine the CFM required. The unit can be set from 30 CRM to 130 Cain increments of 10 CM(Figure 8).
SECTION 6

Motorized Damper
An optical motorized damper can be commented to the unit. The damper is
connect via a 24Vtransfamer that plugs ito the receptacle in the unit (Figure 9)
NOTE Make sure to reference the instructions included with the monetarized
damper before installing operating
Operation

  1. then installed the autlet will be energizæd anytime the unit is running.
    This will in tun pen the damper. When the unit stops running, the damper will dose.
SECTION 7

Optional Air Filter
An ar filter (available separately) can be added to this unit to provide additional filtration of the intake air. The unit will accept a 10″ x 10″ x2″ filter. To install:
NOTE Adding an air filter will decrease the airflow f the unit. You will need to increase the CFM selected in SECTICN5 to account for the decreased ar flow. Filters must be changed reguarly. Refer to the filter manufacturer’s recommendations to determine how often the filter should be changed

  1. Remove the sarews securing the access panel cover in place and open the cover to gain access to the controls and filter area
  2. Ensure the filter is facing the correct way and slide the filter into the slat in the housing Make sure the filter is seated all the way to the bottom af the housing (figure 10).
  3. Choose the access panel and reinstall the sarew holding the access panel in place. QuFRESH-MQF-Fresh-Air-Supply-Fan-fig-4
SECTION 8

Completing the Installation
NOTE When fan is mounted inline and o penetration is made into unconditioned spaces, there is no need to use a sealant appropriate for contact with the building materials present arnd for the temperature requirements of the installation to prevent air leakage from unconditioned spaces. Additional material (backing rod, ceiling material) is aso not required.
NOTE This unit is equipped with a wire mesh insect screen Confirm that the screen is installed inside d the unit and the inlet ducting side.

  1. If the screen is not in place, insert the screen into the tab at the base of the unit (make sure the wider side of the screen is running side to side inside the unit) (Figure 11).
  2. Side the screen to the side with the larger top tab making sun the screen fits behind the tab (Figure 11).
  3. Side the screen back over towards the smaller top tab making sre the screen fits behind the tab (Figure 12).
  4. Confirm that the screen is baing held in place by both top tabs (Figure 12).
  5. Close the access panel and reinstall the sarews holding the access panel in place.
  6. Restare power and test yaur instalatian.
SECTION 9

Setting the Controller
The unit-mounted controller monitors the temperature and humidity of incoming air and allows the installer to configure optimal ventilation.
The unit-mounted controller monitors temperature and humidifies incoming air and allows the installer to configure optimally ventilation.

  1. if you have not already pressed the ON button in step one d this sedion, do so now.
  2. Press the” maigre” button ance and the display will show “C and” Temp Uhit” on the right-hand side.
  3. Press the up a down button to display the temperature in Fahrenheit or Qadsus
  4. Press the “ONAGRE button again to set the upper limit temperature This is the temperature that when the outside air coming into the home exceeds, the fan will stop and enter sampling mode. You will see “per Limit and” Temperature on the right-hand side. Use the “UP and “DON buttons to adjust the temperature
  5. Press the “aNAARE button again to set the upper limit humidity level. This is the humidity level that when the outside air coming into the hame exceeds, the fan will stop and enter sampling mode. Y6u will see “Upper Limit and”Humidity on the right-hand side Use the “UP and”DON’ buttons to adjust the temperature
  6. Press the” OAGRE” button again to set the lower temperature level. This is the temperature that when the outside air coming into the home falls below, the fan will stop and enter sampling mode. You will see “Lower Limit” and “Temperature” on the right-hand side. Uke the “UP and “DON buttons to adjust the temperature
  7. Press the “ONAGRE button again to set the lower limit humidity level. This is the humidity level that when the outside air coming into the home falls below, the fan will stop and enter sampling mode. Y6u will see”Lower Limit” and”Humidity” on the right-hand side. Ube the “UP and “DOW buttons to adjust the temperature. Setting this to 0 a”LO will override the humidity set level. This may be necessary in ery low humidity aeas d the country the top left corner af the display At this point, the information has been stared
  8. Press the “aNAGRE button until it returns to the main screen Yu will see “aN in
SECTION 10(QFDC Model)

Using the Controller

  1. Energy Savings Mode : To enter the Energy Savings mode, press the “aVO-F/ENERGY SAMNGS Button until “Energy Savings” appears n the left side of the display. Energy Savings mode engages the settings configured in SECTION 9 Energy Saing Mode
  2. When the unit is an the display will show the current conditions (temperature and humidity level) as well as if it is in Energy Savings mode ar not. Qher icons information that may be on the display indude Fan icon appears when the fan is an “H appears if the intake temperature is above 150°F “Lo° appears if the intake temperature is below 15’E “Lo appears if the intake humidity is below 10%
  3. Optional Heater Unit: An optional heater unit is available for damages that the air coming into the unit falls below 54°F To install the unit, follow the direction that are induced with that unit. The dsplay will show a thermometer icon with either a” 1″ a”12 when the temperature range is at a level where the heating element would comedian if present Stage 1-“1” tuns and when the intake air temperature is between 39°Fand 54° F Stage 1 and 2″12 tum a when the intake ar temperature is between 33° Fand 39° F.
  4. To restore the factory setting, make sure the unit is in the ” CHF setting. Held both the “UP and DON buttons for approximately 5 seconds. The OF and display wil flash to confirm the settings have been restored
SECTION 11

Use and Care
AACAUTION: MAE SURE PONERIS SWTOHEDGFAT SERME
PANEL BEFORE SERMANG THE UNIT.

  1. deaning the Fan Assembly: We all parts with a dy doth or gently vacuum the fan
    NEVERIMMERSEAECIRCAL PARISINWAJER
    NOTE If you notice a large number of insects and debris in the insect filter, this could be a sig that the intake weather hood (roof cap a wall cap) might be compromised and need repair ar replacing

  2.  Optional Air Filter: If an optional air filter is installed, it should be checked every month and replaced at least once every 3 months. Reverse the instructions in the SECTnaN8 of these instructions to remove filter.
    CALIFORNIA RESIDENTS ONLY:
    WARNING: THSPRCDUCT CAN EXPOSE YOU TO TOACHEMICAL[R CHEMICALS KNOWN TO THE STATE CF CALIFORNIA TO CAUSE CANCER
    WARNING: THSPRCDUCT CAN EXPOSE YOU TO TOAG-CHEMICAL [OR CHEMICALS KNOW TO THE STATE CF CALIRORNA LOCALISE REPRODUCTIVE TOXICITY

Troubleshooting Guide

Trouble Probable Cause Suggest ed Rem edy
1. Fan does not operate. 1a. Control setting. 1a.  Check temperature and

humidity level settings. If the intake air is not within the preset range, the fan will not turn on. Either adjust the settings or wait for the intake air temperature and/or humidity to change.
1b. Afuse may be blown or a circuit tripped.| 1b. Replace fuse or reset circuit breaker.
1c. Wiring is not connected properly.| 1c. Turn off power to unit. Check that all wires are connected.
1d Motor has stopped operating.| 1d. Replace motor.
2. Fan is operating, but air moves slower than normal.| 2a. Obstruction in the ducting.| 2a. Check for any obstructions in the ducting. The most common are bird nests in the roof cap or wall cap where the fan intakes fromthe outside.
2b. Filter is clogged.| 2b. Change air filter (if equipped).
2b. Change/clear bug filter.
3. Fan is operating louder than normal.| 3a. Motor is loose.| 3a. Turn off power to unit and check that all screws are fully tightened. Restore power to unit.
3b. Fan blade is hitting housing of unit.| 3b. Call your dealer for service.

LIMITED WARRANTY

WHAT THIS WARRANTY COVERS This product is warranted against defects in workmanship and materials
HOW LONG THSWARRANTYLASTS This warranty extends anly to the original purchaser the product and lasts far fve (5) years from the date df angina purchase ar untl the angina purchaser d the product sells transfers the product, whichever first odors.
WHAT QUFresh WLL DO Dring the warranty period, Ar Nng will, its sale apion, repair ar replace any part or parts that prove to be defective a replace the wide product WItn tne sanely
WHAT THS WARRANTY DOES NOT COVER This warranty does ndt apply if the product was damaged ar failed because d accident, improper handling operation, shipping damage abse misuse, unauthorized repairs made attempted This warranty does not cover shipping cOsts far the return d products to Ar King far repair ar replacement. Ar King will pay return shipping charges from Ar King falling warranty repairs a replacement

ANY AND ALL WARRANTIES PRESSED IMPUTED (INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY MERCHANTABILITY), LAST ONE YEAR FROM THE DATE
AdNAL PURCHASE CRUNTIL THECRGNAL PURCHASER CF THHEPRODUCT SELSR TRANSFERS THEPRODUCTWHCHEVER ARST OOCURSAND IN NOBANT SHALL KINGS LIABUTYUNDERA NY EXPRESS RIMPUEDWARRANTYINCLLDE (2) INGDENTAL RCONSECENMALDAMAGES FROM ANY CALSEWHATSCEVER CR(2) REPLACEMENT OR REPARCF ANY HOLSEFSS OROUTEREAKERS CRRECEPTAaES NOTWITHSTANDING ANYTHING TO THE CONTRARY IN NOEANTSHALLARKNGSUAEUTY UNDER ANY EXPRESS CRIMPUED WARRANTY EXCEED THE PURCHASE PRICECF THEPRODUCTAND ANY SUCH UABLUTY SHALLTERMNATEUPON THE EXPIRATION F THE WARRANTY PERCD

Some states and provinces do not allow limitations on how long an implied warranty lasts r the excursion ar limitation of incidental ar consequential damages, so these excursion imitations may not apply to you This warranty gives yau specific legal rights. u may also have other rights which vary from state to state and province to province Proof d purchase is
required baae a warranty dam wil be applied

CUSTOMER SERVICE
Tall- Free 866-499-3700
ar elastomer Service team is available to assist you with product questions, service center locations, and replacement parts. They can be reached Monday through Friday, 8 am-4pm
Eastern. Please have your model number available, as well as the type and style (located a the label inside o your project
Please do not return the product to place df purchase

PARTS FOR DISCONTINUED CESOLETEAND CERTAIN OTHER PRODUCTS MAY NOT BE AVAILABLE DUE TO SAFETY REASONS, MANY ELECTRONIC COMPONENTS AND MCST
HEATER COMPONENTS ARE NOT AVAILABLE TO NSUMERSFORINSIALLATON QR PLACEMENT.

REPLACEMENT PARTS DIAGRAM

| Qty. Qte.|

Description

| Replacement Part #

depièce remplacement

---|---|---|---
1| 2| Mounting Brackets Support de montage| 5S1650001
2| 1| 6″ Metal Collar (Intake)

Assemblée de collier en métal de 6 po (d’admission)

| 5S1650002
3| 1| 6″ Metal Collar (Outlet)

Assemblée de collier en métal de 6 po (sortie)

| 5S1650003
4| 1| Blower Assembly Assemblée de la Soufflante| 5S1650102
5| 1| Wire Compartment Assembly Assemblée du compartiment du fil| 5S1650101
6| 1| Adjustment Knobs Boutons de réglage| 5S1299802
7| 1| LCDController (QFAMD) Contrôleur LCD(QFAMD)| 5S1650004

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals