sonbus SM5190B interface atmospheric pressure temperature sensor User Manual

June 5, 2024
SONBUS

sonbus SM5190B interface atmospheric pressure temperature sensor User

Manual

RS485 interface atmospheric pressure, temperature and humidity integrated

sensor User Manual

SM5190B u sing the standard RS485 bus MODBUS RTU protocol,easy access to PLC DCS and other instruments or systems for monitoring atmospheric pressure,temperature,humidity state
quantities.The internal use of high precision sensing core and related dev ices to ensure high reliability and excellent long term stability,can be customized
RS232,RS485,CAN,4 20mA,DC0~5V 10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.

Technical Parameters

Technical parameter Parameter value
Brand SONBEST
Atmospheric pressure range 30~110kpa
Atmospheric pressure accuracy ±0.5%
Temperature measuring range -30℃~80℃
Temperature measuring accuracy ±0.5℃ @25℃
Humidity measuring range 0~100%RH
Humidity accuracy ±3%RH @25℃
Communication Interface RS485
Default baud rate 9600 8 n 1
Power DC9~24V 1A
Running temperature -40~80°C
Working humidity 5%RH~90%RH
 

Product Size

How to wiring?

Application solution

How to use?

Communication Protocol

The product uses RS485 MODBUS RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1
when the device is shipped, the default baud rate is 9600, 8, n,

  1. Read Data (Function id 0x03)
    Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 03 05 CB .
Device ID Function id Start Address Data Length CRC16
01 03 00 00 00 03 05 CB
--- --- --- --- ---

For the correct query frame, the device will respond with data:01 03 06 00 7B 00 00 00 00 C5 7F , the
response format is parsed as follows:

Device ID Function id Data Length Data 1 Data 2 Data 3 Check Code
01 03 06 00 79 00 7A 00 7B C5 7F

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.

1.  Data Address Table

Address Start Address Description Data type Value range
40001 00 00 atmospheric

pressure

| Read Only| 0~65535
40002| 00 01| temperature| Read Only| 0~65535
40003| 00 02| humidity| Read Only| 0~65535
40101| 00 64| model code| read/write| 0~65535
40102| 00 65| total points| read/write| 1~20
40103| 00 66| Device ID| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
40105| 00 68| mode| read/write| 1~4
40106| 00 69| protocol| read/write| 1~10

3 read and modify device address

(1) Read or query device address

If you don’t know the current device address and there is only one devi ce on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

Device ID Function id Start Address Data Length CRC16
FA 03 00 64 00 02 90 5F

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.
For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:

Device ID Function id Start Address Model Code CRC16
01 03 02 55 3C 00 01 3A 79

Response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 00 01 Indicates that the device has a status quantity.

(2)Change device address

For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14 .

Device ID Function id Start Address Destination CRC16
01 06 00 66 00 02 E8 14

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table

Device ID Function id Start Address Destination CRC16
01 06 00 66 00 02 E8 27
--- --- --- --- ---

Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.

4 Read and Modify Baud Rate

  1. Read baud rate

The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protoco l. For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows

Device ID Function id Start Address Data Length CRC16
01 03 00 67 00 01 35 D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.

Device ID Function id Data Length Rate ID CRC16
01 03 02 00 03 F8 45

For the correct query command, the device will respond, for example the response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the following table

Device ID Function id Start Address Target Baud Rate CRC16
01 03 00 66 00 01 64 15

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

5 Read Correction Value

1 Read Correction Value

When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read and modified in the same way for multiple parameters.

Device ID Function id Start Address Data Length CRC16
01 03 00 6B 00 01 F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table.

Device ID Function id Data Length Data value CRC16
01 03 02 00 64 B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters

(2)Change correction value

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters

Device ID Function id Start Address Destination CRC16
01 06 00 6B 00 64 F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after successful change

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd
Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China Web: http://www.sonbest.com

Web:    http://www.sonbus.com SKYPE: soobuu
Email: sale@sonbest.com

Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

SONBUS User Manuals

Related Manuals