Danfoss HC-Z Link HC Hydronic Controller Installation Guide

June 5, 2024
Danfoss

Danfoss HC-Z Link HC Hydronic Controller

Introduction

Danfoss Link™ is a wireless control system for a variety of heating systems. The Danfoss Link™ HC (Hydronic Controller) is a part of this system allowing wireless control of manifolds for water based floor heating/cooling.

Danfoss HC-Z Link HC Hydronic Controller 1

Mounting

The Danfoss Link™ HC should always be mounted in an horizontal upright position.

Mounting on wall

Danfoss HC-Z Link HC Hydronic Controller 2

Remove front and side covers and mount with screws and wall plugs.

Mounting on DIN-rail

Danfoss HC-Z Link HC Hydronic Controller 3

Connections

Make sure that all connections to the Danfoss Link™ HC are completed, before connecting to a 230 V power supply.

Connecting actuators (24 V)
If NC (normally closed) actuators are installed for ON/OFF regulation, no further actuator output con-figuration is needed.

Danfoss HC-Z Link HC Hydronic Controller 4

Connecting pump and boiler controls
The relays for pump and boiler are potential free contacts and can thus NOT be used as direct power supply. Max. load is 230 V, 8 (2) A.

Danfoss HC-Z Link HC Hydronic Controller 5

Connections for Away Function
The Away Function ensures a set room temperature fixed at 15°C for all Room Thermostats, but it can be changed with the Danfoss Link™ CC.

Danfoss HC-Z Link HC Hydronic Controller 6

Connections for Heating & Cooling
When the system is in cooling mode the actuator output will be activated (ON for NC actuators / OFF for NO actuators) when the temperature in a room exceeds the set point. When the system is in cooling mode an independent dew- point alarm function should be installed.

Danfoss HC-Z Link HC Hydronic Controller 7

Power supply
When all actuators, pump and boiler controls and other inputs are installed, connect the supply plug to a 230 V power supply. If the power supply plug is removed during installation, make sure that the connection is made ac-cording to existing law/legislation.
Wiring diagram

Danfoss HC-Z Link HC Hydronic Controller 8

External antenne
The external antenna is installed as diverter when there is no transmission possible through a large building, heavy construction or metal barrier, e.g. if the Danfoss Link™ HC is located in a metal cabinet/box

Danfoss HC-Z Link HC Hydronic Controller 9

Configuration

Adding Danfoss Link™ HC to the system
Adding Danfoss Link™ HC to a system is made from the Danfoss Link™ CC Central Controller. For further information, see the Danfoss Link™ CC instruction manual: Configuration 7: Adding service devices.

Danfoss HC-Z Link HC Hydronic Controller 10

Configure Danfoss Link™ HC
Configuration Danfoss Link™ HC to a system is made from the Danfoss Link™ CC Central Controller. For further information, see the Danfoss Link™ CC instruction manual: Configuration 7: Adding service devices.

Danfoss HC-Z Link HC Hydronic Controller 11

Configure outputs

Danfoss HC-Z Link HC Hydronic Controller 12

Configure inputs

Danfoss HC-Z Link HC Hydronic Controller 13

Add an output to a room
Configuration Danfoss Link™ HC to a system is made from the Danfoss Link™ CC Central Controller. For further information, see the Danfoss Link™ CC instruction manual: Configuration 7: Adding service devices.

Danfoss HC-Z Link HC Hydronic Controller 14

Danfoss HC-Z Link HC Hydronic Controller 15

Configure a room

  • Forecasting method : by activation of the forecast method, the system will automati-cally predict the heating start-up time necessary to reach desired room temperature at desired time.
  • Regulation type: only in connection with electrical heating systems.

Remove an output

Danfoss HC-Z Link HC Hydronic Controller 17

Factory reset

  • Disconnect the power supply for Danfoss Link™ HC.
  •  Wait for green LED to turn off.
  • Press and hold the Install / Link Test.
  • While holding the Install / Link Test, reconnect the power supply.
  • Release the Install / Link Test, when the LED’s are on.

Troubleshooting

Degraded mode| The actuator will be activated with a 25% duty cycle, if the signal from the room thermostat is lost.
---|---
Flashing output / alarm LED(s)| Output or actuator is short-circuited or the actuator is disconnected.

Technical specifications

Transmission Frequency 862.42 Mhz
Transmission range in normal constructions up to 30 m
Transmission power < 1 mW
Supply voltage 230 VAC, 50 Hz
Actuator outputs 10 x 24 VDC
Max. continued output load (total) 35 VA
Relays 230 VAC / 8 (2) A
Ambient temperature 0 – 50°C
IP class 30

Disposal instructions

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals